DTK-DF120S12 

User Guide 

DITEK CORPORATION

One DITEK Center 1720 Starkey Road Largo, Fl 33771

    1-800-753-2345 www.diteksurgeprotection.com

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  

Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA

MCOV Rating: 150 L-N, 150 L-G

VPR: 600 L-N, 600 L-G

Suitable for use on a circuit capable of delivering not more than

10,000 rms symmetrical amperes, 120 Volts maximum when pro-

tected by a 20 ampere circuit breaker rated 120 volts minimum.

Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  

Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA

MCOV Rating: 150 L-N, 150 L-G

VPR: 600 L-N, 600 L-G

Suitable for use on a circuit capable of delivering not more than

10,000 rms symmetrical amperes, 120 Volts maximum when pro-

tected by a 20 ampere circuit breaker rated 120 volts minimum.

Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  

Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA

MCOV Rating: 150 L-N, 150 L-G

VPR: 600 L-N, 600 L-G

Suitable for use on a circuit capable of delivering not more than

10,000 rms symmetrical amperes, 120 Volts maximum when pro-

tected by a 20 ampere circuit breaker rated 120 volts minimum.

Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  

Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA

MCOV Rating: 150 L-N, 150 L-G

VPR: 600 L-N, 600 L-G

Suitable for use on a circuit capable of delivering not more than

10,000 rms symmetrical amperes, 120 Volts maximum when pro-

tected by a 20 ampere circuit breaker rated 120 volts minimum.

Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  

Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA

MCOV Rating: 150 L-N, 150 L-G

VPR: 600 L-N, 600 L-G

Suitable for use on a circuit capable of delivering not more than

10,000 rms symmetrical amperes, 120 Volts maximum when pro-

tected by a 20 ampere circuit breaker rated 120 volts minimum.

Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  

Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA

MCOV Rating: 150 L-N, 150 L-G

VPR: 600 L-N, 600 L-G

Suitable for use on a circuit capable of delivering not more than

10,000 rms symmetrical amperes, 120 Volts maximum when pro-

tected by a 20 ampere circuit breaker rated 120 volts minimum.

Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  

Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA

MCOV Rating: 150 L-N, 150 L-G

VPR: 600 L-N, 600 L-G

Suitable for use on a circuit capable of delivering not more than

10,000 rms symmetrical amperes, 120 Volts maximum when pro-

tected by a 20 ampere circuit breaker rated 120 volts minimum.

Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  

Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA

MCOV Rating: 150 L-N, 150 L-G

VPR: 600 L-N, 600 L-G

Suitable for use on a circuit capable of delivering not more than

10,000 rms symmetrical amperes, 120 Volts maximum when pro-

tected by a 20 ampere circuit breaker rated 120 volts minimum.

Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  

Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA

MCOV Rating: 150 L-N, 150 L-G

VPR: 600 L-N, 600 L-G

Suitable for use on a circuit capable of delivering not more than

10,000 rms symmetrical amperes, 120 Volts maximum when pro-

tected by a 20 ampere circuit breaker rated 120 volts minimum.

Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  

Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA

MCOV Rating: 150 L-N, 150 L-G

VPR: 600 L-N, 600 L-G

Suitable for use on a circuit capable of delivering not more than

10,000 rms symmetrical amperes, 120 Volts maximum when pro-

tected by a 20 ampere circuit breaker rated 120 volts minimum.

Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  

Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA

MCOV Rating: 150 L-N, 150 L-G

VPR: 600 L-N, 600 L-G

Suitable for use on a circuit capable of delivering not more than

10,000 rms symmetrical amperes, 120 Volts maximum when pro-

tected by a 20 ampere circuit breaker rated 120 volts minimum.

Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  

Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA

MCOV Rating: 150 L-N, 150 L-G

VPR: 600 L-N, 600 L-G

Suitable for use on a circuit capable of delivering not more than

10,000 rms symmetrical amperes, 120 Volts maximum when pro-

tected by a 20 ampere circuit breaker rated 120 volts minimum.

Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

Summary of Contents for DTK-DF120S12

Page 1: ...ker rated 120 volts minimum Convient a des circuits produisant au plus 10 000 A eff WARNING SHOCK HAZARD DO NOT OPEN AVERTISSEMENT RISQUE DE CHOC NE PAS OUVRIR C U R US DITEK Surge Protection MODULE STATUS DTK DF120M 120VAC R ENERGIZED GROUNDED GOOD REPLACE MADE IN USA DEFLECTOR SERIES Pat www diteksurgeprotection com patents Model DTK DF120M SPD TYPE 2CA Electrical Ratings 120VAC 20A 50 60 Hz Sin...

Page 2: ...DTK DF120S12 User Guide THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 3: ...arizing keys insure that the correct voltage module will mate with its corresponding base WARNING When the DTK 120M module has gone end of life or is missing the base is susceptible to damage from surge energy Make sure you always have a spare module available No substitutions shall be permitted DITEK Surge Protection MODULE STATUS DTK DF120M 120VAC R ENERGIZED GROUNDED GOOD REPLACE MADE IN USA DE...

Page 4: ...the enclosure 5 Connect the Neutral white conductor supply wire from the distribution panel to the NEUTRAL terminal at the N1 IN lug 6 Connect the Phase black conductor supply wire from the distribution panel to the Phase terminal at the L1 IN lug Note Circuit 1 must be connected first The diagnostic circuits get their power from this input 7 Connect the Neutral white conductor for the connected l...

Page 5: ...XAMPLE MONITORING CIRCUIT DRY CONTACT CIRCUIT INFORMATION DTK DF120S12 Wiring Diagram EARTH Grounding Point This grounds the board to the chassis Use 12 AWG Str Cu only 3 8 strip 20 in lb torque Toggle Switch Center Normal Bypass Left or Right Multi Position Grounding Buss Load Side Multi Position Grounding Buss Supply Side Power Lugs Use 12 AWG Str Cu only 3 8 strip 20 in lb torque 240VAC Input O...

Page 6: ...uit breaker rated 120 volts minimum Convient a des circuits produisant au plus 10 000 A eff WARNING SHOCK HAZARD DO NOT OPEN AVERTISSEMENT RISQUE DE CHOC NE PAS OUVRIR C U R US DITEK Surge Protection MODULE STATUS DTK DF120M 120VAC R ENERGIZED GROUNDED GOOD REPLACE MADE IN USA DEFLECTOR SERIES Pat www diteksurgeprotection com patents Model DTK DF120M SPD TYPE 2CA Electrical Ratings 120VAC 20A 50 6...