background image

UNIWAVE Series

Product Description

The UNIWAVE Series is a new range of modern wireless interfaces which allows users to manage all comfort settings for a room. Allure UNIWAVE is a
wireless wall-mounted sensor which is particularly suitable for renovation or retrofit projects or areas where wiring is impossible.

General Installation Requirements

For proper installation and subsequent operation of the device, pay special attention to the following recommendations:

£

Allow for proper clearance, at least 15cm (6”), around the device’s enclosure to provide easy access for hardware configuration and maintenance.

£

The device must not be installed in a place where it can be affected by direct sunlight.

£

Install the device in a location of average temperature and approximately 1.5 m (5 ft) above the floor.

£

The device should not be installed on an exterior wall.

£

The device should not be installed near a heat source.

£

The device should not be installed near an air discharge grill.

£

Install the device in an area that provides proper device ventilation. Nothing must restrain air circulation to the device.

£

Upon unpacking, inspect the contents of the carton for shipping damages. Do not install a damaged device.

£

Orient the device with the ventilation slots towards the top to permit proper heat dissipation.

£

The device is designed to operate under the following environmental conditions:

– Operating temperature from 32°F to 122°F (0°C to 50°C)
– Storage temperature from 32°F to 122°F (0°C to 50°C)
– Relative humidity from 0% to 80%, non-condensing.

The UNIWAVE device has not been designed for outdoor use.

Any type of modification to any Distech Controls product will void the product’s warranty

I n s t a l l a t i o n   G u i d e

Summary of Contents for UNIWAVE Series

Page 1: ...and approximately 1 5 m 5 ft above the floor The device should not be installed on an exterior wall The device should not be installed near a heat source The device should not be installed near an air...

Page 2: ...2 9 Product Dimensions Figure 1 Allure UNIWAVE dimensions Figure 2 Remote UNIWAVE and wall holder dimensions...

Page 3: ...backing plate using hardware that is appropriate for the mounting surface 1 To remove the front cover of the unit begin by loosening the security screw using an appropriately sized hex key 2 Use a sm...

Page 4: ...kaline batteries RISK OF SHORT CIRCUIT The batteries must be removed before screwing the backing plate to the wall If replacing the batteries only use new batteries Do not use rechargeable batteries w...

Page 5: ...opriate for the mounting surface See Product Dimensions pg 2 for hole placement 1 Insert a small flat screwdriver in the slot for the battery cover and lever the screwdriver upwards as shown below 2 R...

Page 6: ...ician mode screen navigate down to Remote channel and press OK 6 Choose either channel A or channel B for the UNIWAVE device and press OK 7 Navigate to BLE PIN Code and press OK 8 If using Private Con...

Page 7: ...en must be displayed for the device to be found Pairing Number Input the pairing number here The pairing number is required for the UNIWAVE device to connect with the EC Multi Sensor BLE to be able to...

Page 8: ...must be the same one that was assigned to the EC Multi Sensor BLE in the initial programming of the ECLYPSE controller The BLE PIN Code can be viewed or changed from the ECLYPSE Web Interface for that...

Page 9: ...ss B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates...

Reviews: