Wiring
All wiring must conform to NEC and local codes and regulations.
Use earth ground isolating step-down Class 2 transformers. Do not use
autotransformers.
The sum of the VA ratings of all actuators and all other components
powered by one transformer must not exceed the rating of the
transformer.
Determine the supply transformer rating by summing total VA of all
actuators used. It is recommended that one transformer power no
more than 10 actuators.
All six outputs of the dual auxiliary switch (A and B) must
only be connected to:
-
Class 2 voltage (UL/CSA).
-
Separated Extra-Low Voltage (SELV) or Protective
Extra Low Voltage (PELV) (according to HD384 4 41)
for installations requiring conformance.
Installations requiring
Conformance
-
All wiring for CE rated actuators must only be
separated extra low voltage (SELV) or protective extra
low voltage (PELV) per HD384-4-41.
-
Use safety-isolating transformers (Class III transformer)
per EN 61558. They must be rated for 100% duty cycle.
-
Overcurrent protection for supply lines is maximum
10A.
Wiring Diagrams
Counterclockwise Damper Rotation of DA-088N024Fxxxx
If the damper blades turn counterclockwise to open (CCW), reverse the
6 (violet) and 7 (orange) wires at the controller.
Do not wire different types of actuators (such as DA-221N
Series or DA-310N Series actuators) in parallel with these
models.
(For DA-088N floating control actuator series only) To prolong actuator
life, use a controller and/or software that provide a time-out function.
This function removes the actuator drive signal after the signal has
been on for a predefined time.