Start-Up / Commissioning 

1.  Check that the wires are connected correctly. 

2.  Check that offset and slope are set correctly, if used.  

3.  Check  that  the  direction  of  rotation  switch/cable  matches  the 

rotation of the damper shaft. 

4.  Connect  wires  1  (red)  and  2  (black)  to  a  Digital  Multimeter  (DMM) 

with the dial set at AC V to verify that the operating voltage is within 
range. 

 

Check operation: 

1.  Connect wires 1 (red) and 2 (black) to the actuator.  

2.  Set the DMM dial to Vdc. 

3.  Connect wires 2 (black) and 8 (gray) to the DMM. 

4.  Apply a full-scale input signal (10 Vdc) to wire 8 (gray).  

5.  Allow the actuator shaft coupling to rotate from 0 to 90°. 

6. 

Disconnect  wire  8  (gray)  and  the  shaft  coupling  returns  to  the  “0” 
position. 

 

Check Feedback: 

1.  Set the DMM dial to Vdc. 

2.  Attach wires 2 (black) and 9 (pink) to the DMM. 

3.  Apply  a  full-scale  input  signal  to  wire  8  (gray).  The  reading  at  the 

DMM should increase. 

4. 

Remove  the  signal  from  wire  8  (gray).  The  reading  at  the  DMM 
should  decrease  and 

the actuator shaft coupling returns to the “0” 

position.

 

 

Check the Auxiliary Switch A:  

1.  Set the DMM dial to ohms (resistance) or continuity check. 

2.  Connect 

wires 

S1 

and 

S3 

to 

the 

DMM.  

The DMM should indicate open circuit or no resistance. 

3.  Apply  a  full-scale  input  signal  to  wire  8  (gray).  The  DMM  should 

indicate contact closure as the actuator shaft coupling reaches the 
setting of switch A. 

4.  Connect  wires  S1  and  S2  to  the  DMM.  The  DMM  should  indicate 

open circuit or no resistance. 

5. 

Stop  the  signal  to  wire 8 (gray). The DMM should indicate contact 
closure as the actuator shaft coupling reaches the setting of switch 
A.

 

 

Check the Auxiliary Switch B: 

1.  Set the DMM dial to ohms (resistance) or continuity check. 

2.  Connect  wires  S4  and  S6  to  the  DMM.  The  DMM  should  indicate 

open circuit or no resistance. 

3.  Apply  a  full-scale  input  signal  to  wire  8  (gray).  The  DMM  should 

indicate contact closure as the actuator shaft coupling reaches the 
setting of switch B. 

4.  Connect  wires  S4  and  S5  to  the  DMM.  The  DMM  should  indicate 

open circuit or no resistance. 

5.  Stop  the  signal  to wire 8 (gray). The DMM should indicate contact 

closure as the actuator shaft coupling reaches the setting of switch 
B. 

 

 

 

Summary of Contents for DA-088N Series

Page 1: ...Avoid areas where corroding deteriorating or explosive vapors fumes or gases may be present Ensure that all equipment is installed according to local regional and national regulations Personal injury...

Page 2: ...lever to the right Return the switch to automatic See Figure 17 To mount a modulating DA 088N024Pxxxx set the Dual In line Package DIP switches to the required positions 1 To access the DIP switches...

Page 3: ...g Actuator to Damper Shaft Figure 8 Installing the Position Indicator b Figure 9 Attaching the Mounting Bracket Operation A continuous 0 to 10 Vdc signal from a controller to wire 8 Y operates the dam...

Page 4: ...e Ys changes When the mechanical limitation of the angle of rotation and self adapt function are ON 100 does not equal 90 Setting for 10V slope 0 Vdc offset Figure 11 Examples in Figure 10 Uo Offset V...

Page 5: ...the feature on the actuator will enter a five minute calibration cycle as the actuator adjusts to the rotation limits of the system A software reset happens after power on or may be caused by electros...

Page 6: ...slope and offset features this example assumes Offset Uo 0 Vdc Slope U 10 Vdc Mechanical Range Limitation and Self Adapt Feature 1 To use the entire 0 to 10V input signal to control the adjusted range...

Page 7: ...formance Installations requiring Conformance All wiring for CE rated actuators must only be separated extra low voltage SELV or protective extra low voltage PELV per HD384 4 41 Use safety isolating tr...

Page 8: ...lue S6 Switch B N O Q24 Black pink P1 Feedback Potentiometer 0 to 100 P1 P2 a White red P2 Feedback Potentiometer Common b White blue P3 Feedback Potentiometer 100 to 0 P3 P2 c White pink Each wire ha...

Page 9: ...9 14 Figure 23 0 to 10 Vdc Modulating Control...

Page 10: ...or shaft coupling returns to the 0 position Check the Auxiliary Switch A 1 Set the DMM dial to ohms resistance or continuity check 2 Connect wires S1 and S3 to the DMM The DMM should indicate open cir...

Page 11: ...able precabled Numbers listed associate with terminal positions M9109 Series is not available precabled Numbers listed associate with terminal positions Floating Control Distech Controls DA 088N Serie...

Page 12: ...12 14 Dimensions Figure 24 Dimensions of the DA ASK75 7U Weather Shield in Inches Millimeters...

Page 13: ...13 14 Dimensions cont d Figure 25 Dimensions of the DA 088N Actuator and Mounting Bracket in Inches mm...

Page 14: ...cialist installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail safe environments Distech Controls reserves the right to change delete...

Reviews: