background image

6

discoverbattery.com

M8” bolt (supplied with battery)

Copper compression lug

Shrink-wrap to 

color-code the cable

Terminal surface

Lock washer (supplied with battery)

Flat washer (supplied with battery)
Battery cable lug 
Ensure nothing is between 

the terminal surface and the 

battery cable lug

M8” bolt (supplied with battery)

Copper compression lug

Shrink-wrap to 

color-code the cable

Terminal surface

Lock washer (supplied with battery)

Flat washer (supplied with battery)
Battery cable lug 
Ensure nothing is between 

the terminal surface and the 

battery cable lug

4.2 VE.Direct MPPT Settings 

During normal operation the MPPT charge characteristics are governed by the CCGX via DVCC, with instructions from the 
connected AES battery. 

The settings below are precautionary. This section presumes familiarity with VictronConnect (Bluetooth App) used to 
configure, monitor and diagnose Victron MPPT products which feature Blue-tooth, or are equipped with a VE.Direct Port.

MPPT Charge Controller Settings

44-24-2800

42-48-6650

Battery voltage

24 V

48 V

Max current per battery installed 

(Recommended < Maximum)

 

(9)

installed x 

(78 A < 110 A)

installed x 

(92 A < 130 A)

Charger enabled

Enabled

Enabled

Battery preset

User Defined

User Defined

Absorption voltage

27.2 V

54.8 V

Maximum absorption time 

(10)

1.0 < 3.0 Hr

1.0 < 3.0 Hr

Float voltage

26.8 V

54.0 V

Equalization voltage

26.8 V

54.0 V

Auto equalization

Disabled

Disabled

Temperature compensation

Disabled

Disabled

Low temperature cut off

5

0

 C

5

0

 C

(9) May be set to lower value if necessitated by charger controller size.

(10) 

Duration of absorption period after the bulk charge interval. The recommended minimum is 1.0 hour. A longer 

period of time may be required to compensate for multiple batteries to achieve a smooth completion of charge. 

5. Installing LYNK and Connecting LYNK to the Victron Network

5.1 Installing the LYNK Edge Card

The LYNK Edge Card for Victron is a Slot 0 Type which only inserts into the left side slot on the bottom of the LYNK 
Communication Gateway. 

 NOTE

• 

The LYNK Edge Card type to be used is determine by the brand of power 
conversion equipment.

• 

If LYNK Edge Card is in the wrong slot, it will not function.

• 

If LYNK Edge Card is not firmly seated, it will not function.

Slot 0 Type

Summary of Contents for LYNK Edge Card Victron

Page 1: ...950 0016 VCTRN LYNK Edge Card Victron User Manual 4 13511 Crestwood Place Richmond BC V6V 2E9 Canada 1 778 776 3288 info discoverbattery com discoverbattery com 805 0020 REV A 5 Installing LYNK and C...

Page 2: ...ified personnel to ensure compliance with applicable installation codes and regulations Failure to follow these instructions can result in death or serious injury CAUTION HAZARD OF EQUIPMENT DAMAGE Do...

Page 3: ...l Discover Reference Documents Discover Energy 808 0004 42 48 6650 Data Sheet Discover Energy 808 0005 44 24 2800 Data Sheet Discover Energy 805 0015 AES LiFePO4 Battery 44 24 2800 42 48 6650 Manual D...

Page 4: ...apacity Battery charge and discharge rates are managed automatically by the AES LiFePO4 Battery and Victron CCGX device Using very large solar arrays with battery banks that are too small can exceed t...

Page 5: ...le Charge curve 2 Select Fixed Select Fixed Absorption voltage 2 27 2 V 54 4 V Float voltage 2 26 8 V 53 6 V Charge current per battery installed Recommended Maximum installed x 78 A 110 A installed x...

Page 6: ...tery voltage 24 V 48 V Max current per battery installed Recommended Maximum 9 installed x 78 A 110 A installed x 92 A 130 A Charger enabled Enabled Enabled Battery preset User Defined User Defined Ab...

Page 7: ...these instructions can damage equipment NOTE Power electronics are not AEBus devices and should not be connected to AEBus 5 3 Connecting LYNK to the Victron Network Before connecting LYNK to the Vict...

Page 8: ...batteries NOTE If Discover does not appear on the Device List confirm that the CAT5 communication cable is a normal patch type and not a cross over type Use manufactured cables to avoid bad crimps and...

Page 9: ...indicated Battery Monitor DISCOVER on CAN bus DVCC DistributedVoltage and Current Control ON SVS Shared voltage sense OFF 7 STS Shared temperature sense OFF Limit charge current ON Max charge current...