Front Desk Control

The PTAC can be remotely turned on and off via the front desk 

control by applying a 24VAC signal across terminals FC(L) and 

FC(N). If 24VAC is present, the PTAC will turn on.  

If 24VAC is not present, the PTAC will turn off.

The FRONT DESK CONTROL dip switch can turn the front 

desk control feature on and off. If the dip switch is in the 

DOWN position, the front desk control feature is disabled.  

If the dip switch is in the UP position, the front desk control 

feature is enabled.

Notes

•  Use terminal 4-way for heat pump connection only.

•   The PTAC has a built-in 3-minute compressor protection time. If the compressor protection time 

on the thermostat is set for less than 3 minutes, the default PTAC 3-minute compressor protection 

time will take precedence.

•   If connecting thermostat to a heat pump unit, thermostat must be set to heat pump operation, 

with the 4-way valve connection set to be energized in heat mode.

•  For thermostats that have only one fan speed output (on or auto), the fan speed is determined by 

how the terminal connector is wired. If low fan is desired, wire the G output from the thermostat 

to (LOW-FAN) on the unit’s terminal block. If high fan is desired, wire the G output from the 

thermostat to (HI-FAN) on the unit’s terminal block.

•   A connected thermostat will only control the set temperature of the PTAC within the temperature 

range setting of the PTAC.

•  For 15k BTU resistance heat units: if the wall thermostat only has one electrical heater output, connect 

heater output to HEAT1; jumper HEAT1 and HEAT2 together

•   Please do not remove the control panel.

Recommended Wired and Wireless Thermostat Settings and Connections

10

Dip switch for FRONT

DESK CONTROL

Fig.4

DIP Switch Settings for All Thermostats (U = Up, D = Down)

S8

S7

S6

S5

S4

S3

S2

S1

A4

A5

S11 S10

S9

X

Upper Blue

Lower Blue

U

D

D

U

U

U

D

D

U

U

U

U

D

U

D

U

Connections Between PTAC Terminal Block & Thermostat Terminal Block

Thermostat Model

PTAC Type/ 

BTU Rating

Low  

Fan

Hi  

Fan

4-Way Heat1 Heat2 Comp 24V(N) 24V(L)

Pro1 Wireless 

Thermostat

Resistance Heat  
(7k, 9k, 12k models only )

GL

GH

-

W

-

Y

C

R

Resistance Heat  
(15k models only)

GL

GH

-

W

W

Y

C

R

Heat Pump (all models)

GL

GH

O/B

-

-

Y

C

R

Honeywell PRO3000  

Wired Thermostat

Resistance Heat  
(7k, 9k, 12k models only)

-

G

-

W

-

Y

C

R

Resistance Heat  
(15k models only)

-

G

-

W

W

Y

C

R

Heat Pump (all models)

-

G

B

-

-

Y

C

R

Summary of Contents for E7822

Page 1: ...rom Direct Supply Equipment Furnishings Please read this entire guide carefully and keep it for future reference This guide will provide you with instructions warnings warranty information and other i...

Page 2: ...with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible...

Page 3: ...WARNING Do not use a product you suspect is not functioning properly Immediately contact Direct Supply Equipment Furnishings CAUTION When the air filter is to be removed do not touch the metal parts...

Page 4: ...hich is located on the side of the cabinet and behind the grille Be sure the air conditioner is properly grounded To minimize shock and fire hazards proper grounding is important The power cord is equ...

Page 5: ...so indicated by a light on the plug head TEST RESET Plug in press RESET NOTE Some plugs have buttons on the top NOTES Do not use this device to turn the unit on or off Always make sure the RESET butto...

Page 6: ...P MODELS ONLY If the room temperature is 8 F below the setpoint temperature the heat pump will shut off and the electric heater will turn on until the setpoint is reached HIGH TEMPERATURE PROTECTION I...

Page 7: ...7827 E7835 E7828 E7836 E7829 E7837 G1250 PERFORMANCE DATA Cooling Btu 7200 6800 7200 9000 8800 9000 12000 11800 12000 14700 14500 14700 14700 14500 Cooling Watts 610 576 610 796 778 796 1142 1124 1142...

Page 8: ...erature is not too low this function is off Automatic Quick Warm up heat pump models only If the room temperature falls to 8 F 4 5 C below the setpoint temperature the reverse cycle heat is shut off a...

Page 9: ...e compressor cycles off 3 When frost builds up to the evaporator coils the unit will defrost automatically and the compressor will cycle off FAN Fan operation only without heating and cooling UP DOWN...

Page 10: ...Cycle for Cooling S9 Used with some types of wall thermostats Used with other types of wall thermostats Try with switch in the UP position first If this doesn t work try again with the switch in the D...

Page 11: ...llow the fan to operate in continuous or cycle modes while the unit is in heating and cooling mode CON Continuous Allows the fan to run continuously circulating air even when the temperature setting h...

Page 12: ...ted around or under NEVER through the wall sleeve The wire should then be routed behind the front panel to the terminal connector NOTE Refer to thermostat installation instructions for details on inst...

Page 13: ...connector is wired If low fan is desired wire the G output from the thermostat to LOW FAN on the unit s terminal block If high fan is desired wire the G output from the thermostat to HI FAN on the un...

Page 14: ...ng sleeve remove all baffles from the rear grille prior to installation of the PTAC To avoid vibration and noise make sure the unit is installed securely and firmly When installing the sleeve make cer...

Page 15: ...til firmly against front of wall sleeve and secure with four screws and washers supplied in the SLEEVE ASSEMBLY through the unit flange holes See Fig 7 and Fig 8 Vent control lever Vent open Vent clos...

Page 16: ...he unit The most important thing you can do to maintain unit efficiency is to clean the filters once every two weeks as required Clogged filters reduce cooling heating and airflow Keeping filters clea...

Page 17: ...ormal during operation of unit Water Dripping Outside If a drain kit has not been installed condensation runoff during hot and humid weather is normal See Note 2 If a drain kit has been installed and...

Page 18: ...Supply PTAC Extruded Architectural Grill C9782 Direct Supply PTAC Drain Kit C9783 Direct Supply PTAC Air Filter E7838 Sub Base Assembly for Direct Supply PTAC Units 265V 30 Amp Units E7839 Sub Base As...

Page 19: ...have other rights which vary from state to state Please note that our limited warranty period begins when we ship the product to you The limited warranty period and our obligations under the warranty...

Page 20: ...by Direct Supply Manufacturing Inc 6635 N Industrial Road Milwaukee WI 53223 2015 2018 Direct Supply Manufacturing Inc All Rights Reserved Direct Supply and all associated logos are the registered tra...

Reviews: