This manual describes how to install, operate and troubleshoot the SMART NAVIGATOR Faulted 
Circuit Indicator for distribution voltage overhead lines. It covers the following part number: 
 

43-XXXX-XXX SMART NAVIGATOR 

 
 
The manual consists of 4 main parts: 
 
 

Part 1 – Introduction 
Gives an overview of the Navigator / SMART NAVIGATOR overhead line fault indicator 

 

Part 2 – Functionality 
Describes the functionality of the Navigator / SMART NAVIGATOR 

 

Part 3 – Installation & Operation 
Describes how to install, operate and troubleshoot the Navigator / SMART NAVIGATOR 

 

Part 4 – Technical Data 
Contains the technical data of the Navigator / SMART NAVIGATOR 

 
 

1.2

 

A

BBREVIATIONS

 

 
 

Abbreviation Definition 
DA Distribution 

Automation 

FCI 

Faulted Circuit Indicator 

ISM 

Industrial / Scientific / Medical 

RF Radio 

Frequency 

RTU  

Remote Terminal Unit 

 
 
 

1.3

 

I

NTENDED USE

 

 
The SMART NAVIGATOR is an overhead faulted circuit indicator that is designed and engineered for 
Smart Grid – Distribution Automation applications. The SMART NAVIGATOR is installed on overhead 
distribution circuits and transmits event based fault information in addition to continuous circuit status 
information. The SMART NAVIGATOR is integrated into an existing Smart Grid system and can 
operate in different WAN environments such as cellular, radio, etc. A pole mounted concentrator, 
either the SMART RECEIVER or SMART CONTROLLER acts as WAN access point. 
 

Summary of Contents for SMART NAVIGATOR

Page 1: ...Dipl Ing H Horstmann GmbH Humboldtstra e 2 42579 Heiligenhaus www horstmanngmbh com Instructions for Use SMART NAVIGATOR 14 September 2010...

Page 2: ...ation and Reset 8 2 2 3 Fault Indication and Line Monitoring by Radio Signal 9 2 3 Wireless Communication 9 2 3 1 Priority Events communicate by exception 9 2 3 2 Reports communicate by routine interv...

Page 3: ...ice here _______________________________ You will find all data on the name plate attached to the housing of the instrument The content of this operating manual reflects the current state of the art a...

Page 4: ...INFORMATION FOR CANADA Warning Installation connection and commissioning of the SMART NAVIGATOR must be carried out exclusively by a skilled qualified electrician observing the applicable safety rule...

Page 5: ...VIGATOR Part 4 Technical Data Contains the technical data of the Navigator SMART NAVIGATOR 1 2 ABBREVIATIONS Abbreviation Definition DA Distribution Automation FCI Faulted Circuit Indicator ISM Indust...

Page 6: ...ine section This substantially speeds up the process of restoring the power supply to the utility customers In addition the SMART NAVIGATOR continuously monitors and transmits circuit status informati...

Page 7: ...Instructions for Use Dipl Ing H Horstmann GmbH SMART NAVIGATOR 7 PART 2 FUNCTIONALITY 2 1 DEVICE DESCRIPTION Figure 2 1 NAVIGATOR 2D View Battery Compartments...

Page 8: ...The SMART NAVIGATOR features one ultra bright RED LED that provides fault information LED Status Meaning Off Normal status of FCI 1 RED LED Flashing Fault Indication Fault detection is indicated by a...

Page 9: ...EIVER via low power RF wireless technology using the world wide available 2 4GHz ISM Industrial Scientific Medical frequency band The range between the SMART RECEIVER and a SMART NAVIGATOR can extend...

Page 10: ...TEST with a magnet for 0 2s does test the local indication and radio link It turns the FCI ON and activates a local fault indication LED flashing The unit will be flashing until reset by magnet elapse...

Page 11: ...overhead line The field replaceable battery provides operational power Not only dependent on line current or voltage for its power the fault indicator is constantly armed ready to register switching i...

Page 12: ...Installation should be carried out observing appropriate safety regulations and the use of proper protective equipment such as hot sticks Operators must maintain safe clearance from electrical power...

Page 13: ...r momentary fault information 3 Low battery Whenever a SMART NAVIGATOR detects that its battery is approaching its end of life it sends the Low Battery information 4 Test FCI ON Activating the reed co...

Page 14: ...or pairing with a SMART NAVIGATOR Step 3 Hold the magnet close to the RESET point of the SMART NAVIGATOR until a yellow LED in the SMART NAVIGATOR lights up twice If after a maximum of 10 seconds eith...

Page 15: ...factor 4 times load current 200ms Level delay 60 sec Level memory 72 hours Function test reset by use of permanent magnet Automatic time reset 4 hours Current reset 3 A Power source 1 Lithium Battery...

Page 16: ...Dipl Ing H Horstmann GmbH Instructions for Use 16 SMART NAVIGATOR 4 1 PRODUCT FOTO LABEL INFORMATION Label with FCC ID IC ID...