Dinel, s.r.o. ULM–70
NO ECHO: Current in case of echo loss
DEAD ZONE: Dead zone current
The values can be set in three steps:
3.75 mA, 22 mA and LAST (last measured data).
FAILURE MODE
It
defines the output current
of the level meter when the measured medium level is in the dead zone
("DEAD ZONE") or outside the measurement range in case of echo loss ("NO ECHO").
S E N S I T I V I T Y
T E A C H I N G
M E D I U M T E M P E R A T U R E
F A I L U R E M O D E
H A R T
F A C T O R Y D E F A U L T
R E S E T
F A I L U R E M O D E
N O E C H O : 3 . 7 5 m A
D E A D Z O N E : 2 2 m A
HART
HART
®
mode (point to point, multidrop) and multidrop mode
address setting
. Up to 15 units can be
connected to one two-wired cable in the multidrop mode.
In case of the address "00", the point to point
mode is enabled. The range from "01" to "15" is
reserved for addresses in the multidrop mode.
After you press the button
"RUNNING"
will be displayed for about 3 sec. After the
initial values are set, "DONE" will be appear
on the display.
FACTORY DEFAULT
To
reset the initial values
of the level meter set by the manufacturer, press the button
(see the
Factory default table, p. 24).
RESET
Complete restart
of the level meter. The same effect has also a short-time interruption of the supply
voltage. To enable the resetting, press the button
.
S E N S I T I V I T Y
T E A C H I N G
M E D I U M T E M P E R A T U R E
F A I L U R E M O D E
H A R T
F A C T O R Y D E F A U L T
R E S E T
P O L L I N G A D D R E S S
0 0
F A C T O R Y D E F A U L T
A R E Y O U S U R E ?
F A C T O R Y D E F A U L T
R U N N I N G
F A C T O R Y D E F A U L T
D O N E
P R E S S
E S C
T O E X I T
S E N S I T I V I T Y
T E A C H I N G
M E D I U M T E M P E R A T U R E
F A I L U R E M O D E
H A R T
F A C T O R Y D E F A U L T
R E S E T
S E N S I T I V I T Y
T E A C H I N G
M E D I U M T E M P E R A T U R E
F A I L U R E M O D E
H A R T
F A C T O R Y D E F A U L T
R E S E T
R E S E T
A R E Y O U S U R E ?
During the restart process, "RUNNING" will
be displayed. Then the level meter will be
automatically turned off and on.