Dinel, s.r.o. RFLS–28
4.
Pull the sensor out of the media. Leave possible deposits on the electrode.
5. Switch the SET switch to the OFF position
6. Press the setting button (SETTING). Settings are confirmed by three flashes of the orange
LED.
7. Check the state of the ALARM indicator. If the red LED is not flashing, the sensor is set cor
-
rectly. If it is flashing, the sensor is set incorrectly. Repeat the setting.
b) Setting the c mode (opens when submerged)
1.
Immerse the sensor electrode in the medium to be measured.
2. Switch the SET CH switch to the ON position and the SET switch to the OFF position
3. Press the setting button (SETTING). Settings are confirmed by three flashes of the orange
LED.
4.
Pull the sensor out of the media. Leave possible deposits on the electrode.
5. Switch the SET switch to the ON position
6. Press the setting button (SETTING). Settings are confirmed by three flashes of the orange
LED.
7. Check the state of the ALARM indicator. If the red LED is not flashing, the sensor is set cor
-
rectly. If it is flashing, the sensor is set incorrectly. Repeat the setting.