12
©
Dinel, s.r.o. DLM–35
Setting the lower output value - Indirect
1. Bring the level in the tank to any known (determinable) level, best close to the minimum
measured level.
2. Touch the magnetic pen for
approx. 3 seconds
on the sensitive spot
of the level meter.
After 3 seconds, the LED indicator “STATE” starts to flash slowly and now put away the magnetic
pen from the sensitive spot.
3. At the moment when the LED indicator “STATE” starts flashing slowly, by touching the
magnetic pen on spots
and
it is possible to set the output value by stepping,
which is calculated according to the formula:
- for current output ... I out = 4 + (0.16 x height of level in %) [mA]
- for voltage output ... U out = 0.1 x height of level in % [V]
(If the magnetic pen is kept on the sensitive spot, the setting step gradually increases.)
4. After reaching the lower output value, put away the magnetic pen from sensitive spots and wait
for permanent shine of the orange LED indicator “STATE”.
5. After light up of the orange LED indicator “STATE”, confirm the setting by short touch of the
magnetic pen on the sensitive spot
. After simultaneous light up of both LED indicators
“STATE” and “RUN” it is possible to put away the magnetic pen. The LED indicator “STATE” will
briefly flash 3x to confirm the setting of the limit.
Setting the upper output value - Indirect
1. Bring the level in the tank to a known (determinable) level, best when close to the maximum
measured level.
2. Touch the magnetic pen for
approx. 3 seconds
on the sensitive spot
of the level meter.
After 3 seconds, the LED indicator “STATE” starts to flash rapidly, and now put away the
magnetic pen from the sensitive spot.
3. At the moment when the LED indicator “STATE” starts flashing rapidly, by touching the
magnetic pen on spots
and
it is possible to set the output value by stepping,
which is calculated according to the formula:
- for current output ... I out = 4 + (0.16 x level height in %) [mA]
- for voltage output ... U out = 0.1 x level height in % [V]
(If the magnetic pen is kept on the sensitive spot, the setting step gradually increases.)
4. After reaching the upper output value, put away the magnetic pen from sensitive spots and wait
for permanent shine of the orange LED indicator “STATE”.
5. After light up of the orange LED indicator “STATE”, confirm the setting by short touch of the
magnetic pen on the sensitive spot
. After simultaneous light up of both LED indicators
“STATE” and “RUN” it is possible to put away the magnetic pen. The LED indicator “STATE” will
briefly flash 3x to confirm the setting of the limit.
6. If both LED indicators “STATE” and “RUN” begin flashing in alternating fashion, it means
that the level meter cannot distinguish between the selected levels - it is necessary either to
decrease the level for setting the lower output value or increase the level for setting the upper
output value.