Technical information

WWSP 432 SOL

WWSP 540 SOL

CWWSP 308 SOL CWWSP 411 SOL

Nominal volume

litres

363

448

295

380

Usable capacity

litres

346

427

295

380

Heating water heat exchanger area

3,2

4,0

0,8

1,05

Solar heat exchanger area

1,3

1,6

1,55

1,8

Height

mm

1631

1961

1834

1631

Diameter

mm

700

700

600

700

Packed cylinder weight

kg

182

218

113

133

Connections

Solar flow

SF

1 1/4" internal thread 1 1/4" internal thread

1" external thread

1" external thread

Solar return

SR

1 1/4" internal thread 1 1/4" internal thread

1" external thread

1" external thread

Cold water

CW

1" external thread

1" external thread

1" external thread

1" external thread

Domestic hot water

DHW

1" external thread

1" external thread

1" external thread

1" external thread

Circulation

C

3/4" internal thread

3/4" internal thread

3/4" external thread

3/4" external thread

Heating water flow

HF

1 1/4" internal thread 1 1/4" internal thread

1" external thread

1" external thread

Heating water return

HR

1 1/4" internal thread 1 1/4" internal thread

1" external thread

1" external thread

Flange

DN110

DN110

DN110

DN110

Sensor sleeve

mm

‡

20x2x60

‡

20x2x60

‡

20x2x200

‡

20x2x200

Anode 

‡

33 x length

mm

750

1060

Anode 

‡

26 x length

mm

1100

900

Anode connection thread

1 1/4“

1 1/4“

1“

1“

Permissible  operating  temperature,
heating water

°C

110

110

110

110

Permissible operating overpressure,
heating water

Bar

10

10

10

10

Permissible  operating  temperature,
drinking water

°C

95

95

95

95

Permissible operating overpressure,
drinking water

Bar

10

10

10

10

Permissible  operating  temperature,
solar

°C

110

110

110

110

Permissible operating overpressure,
solar

Bar

10

10

10

10

Summary of Contents for WWSP 432 SOL

Page 1: ...r cylinder 400 litres 361 080 WWSP 432 SOL for heat pumps Solar hot water cylinder 500 litres 361 090 WWSP 540 SOL for heat pumps Solar hot water cylinder 300 litres 361 120 CWWSP 308 SOL for boilers Solar hot water cylinder 400 litres 361 130 CWWSP 411 SOL for boilers Réservoir solaire d eau chaude sanitaire 400 litres 361 080 WWSP 432 SOL pour pompes à chaleur Réservoir solaire d eau chaude sani...

Page 2: ...impact in the cold water network and avoid unnecessary loss of water we recommend installing a fitted expansion vessel with a perfusion device 2 Start up Ensure that the water supply is turned on and the tank is filled before start up The initial filling and start up must be carried out by a qualified specialist company The entire system including all factory assembled components should be inspect...

Page 3: ...rnal thread 1 external thread 1 external thread Circulation C 3 4 internal thread 3 4 internal thread 3 4 external thread 3 4 external thread Heating water flow HF 1 1 4 internal thread 1 1 4 internal thread 1 external thread 1 external thread Heating water return HR 1 1 4 internal thread 1 1 4 internal thread 1 external thread 1 external thread Flange DN110 DN110 DN110 DN110 Sensor sleeve mm 20x2...

Page 4: ...et valve 7 Filter 8 Ventilation and de aeration 9 Shutoff valve with drainage 10 Check valve 11 Load pump 12 Circulation pump intermittent operation 13 Straight valve with return inhibitor 14 Scalding protection according to DIN 806 2 and DVGW W551 15 Return inhibitor Legend CW Cold water C Circulation SF Solar flow SR Solar return T Thermometer HF Heating Flow HR Heating return LUFXODWLRQ RQO LI ...

Reviews: