EN-22 SRX_C_gb · 09/15/B
www.dimplex.de/en
Englis
h
SRX 070ECM, SRX 120ECM, SRX 160ECM
21. Technical data
Glen Dimplex Deutschland GmbH
Am Goldenen Feld 18
D-95326 Kulmbach
Subject to modifications
Phone +49 9221709564
Fax +49 9221 709589
E-Mail: [email protected]
www.glendimplex.de/en
SRX
070
ECM
SRX
120
ECM
SRX
160
ECM
Setting range of
thermostat (°C)
5 - 30
Flow temperature (°C)
in heating mode
> 25
Maximum permissible
flow temperature (°C)
85
Flow temperature (°C)
in cooling mode
< 20
Permissible operating
overpressure (MPa)
1
Pressure drop (kPa)
11,3
13,1
13,7
Air volume flow
(m
3/
h)
3
228
410
540
2
125
225
300
1
60
120
160
Sound pressure level at
1m (dB/A)
3
47
2
38
1
27
Nominal voltage
~100 - 250V, 50/60Hz
Power Consumption
3
10,5
12,5
15,0
2
8,0
8,0
8,0
1
6,0
6,0
6,0
Standby Energy
< 4W
Protection category
IP20
Volume of heat
exchanger (ml)
230
385
555
Dimensions
W x H x D (mm)
503 x
530 x
145
740 x
530 x
145
911 x
530 x
145
Weight (kg)
12
15
17,5