6
Electrical connection
6.1
Nominal voltage / fusing / type
3-/PE 400V (50Hz) / C25A / A
6.2
Control voltage / fusing / type
1-/N/PE 230V (50Hz) / C13A / A
6.3
Degree of protection according to EN 60 529
IP21
6.4
Starting current with soft starter
A
35
6.5
Nominal power consumption
B0 W35 / max. power consumption kW
7.4 / 13.4
6.6
Nominal current
B0 W35 / cos
A
/
---
13.4 / 0.8
6.7
Power consumption of compressor protection (per compressor)
W
70; thermostatically controlled
6.8
Power consumption of pumps
kW
up to 0.5
7
Complies with the European safety regulations
7
8
Additional model features
8.1
Water in device protected against freezing
8
Yes
8.2
max. operating overpressure (heat source/heat sink)
bar
3.0
1. 1-compressor operation
2. 2-compressor operation
3. These data indicate the size and capacity of the system according to EN 14511.
For an analysis of the economic and energy efficiency of the system, the bivalence point and the regulation should be taken into consideration.
These figures are only achieved with clean heat exchangers.
Information on maintenance, commissioning and operation can be found in the respective sections of the installation and operating instructions.
The specified values, e.g. B10 / W55, have the following meaning: Heat source temperature 10 °C and heating water flow temperature 55 °C.
4. The coefficients of performance are valid with the circulating pumps included in the scope of supply
5. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35° C.
The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A) depending on the installation location.
6. Please note that additional space is required for pipe connections, operation and maintenance
7. see CE declaration of conformity
8. The heat circulating pump and the heat pump manager must always be ready for operation.