9 Maintenance and 

Cleaning 

9.1 Maintenance

The heat pump is maintenance-free. To prevent faults due to
sediment in the heat exchangers, care must be taken to ensure
that no impurities can enter either the heat source system or the
heating system. In the event that operating malfunctions due to
contamination occur nevertheless, the system should be cleaned
as described below. 

9.2 Cleaning the Heating System

The ingress of oxygen into the heating water circuit may result in
the formation of oxidation products (rust), particularly if steel
components are used. These products enter the heating system
via the valves, the circulating pumps and/or plastic pipes. It is
therefore essential - in particular with respect to the piping of un-
derfloor heating systems - that only diffusion-proof materials are
used.

ATTENTION!

We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump.

Residue from lubricants and sealants may also contaminate the
heating water.
In the case of severe contamination leading to a reduction in the
performance of the liquifier in the heat pump, the system must be
cleaned by a heating technician.
According to today’s state of knowledge, we recommend using a
5% phosphoric acid solution for cleaning purposes. However, if
cleaning needs to be performed more frequently, a 5 % formic
acid solution should be used.
In either case, the cleaning fluid should be at room temperature.
We recommend flushing the heat exchanger in the direction op-
posite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating sys-
tem circuit, we recommend connecting the flushing device di-
rectly to the flow and return flow of the liquifier. It is important that
the system be thoroughly flushed using appropriate neutralising
agents to prevent any damage from being caused by cleaning
agent residue remaining in the system.
Acids must be used with great care and all relevant regulations of
the employers’ liability insurance associations must be adhered
to.
If in doubt, contact the manufacturer of the chemicals!

9.3 Cleaning the Heat Source 

System

ATTENTION!

The supplied dirt trap must be inserted in the heat source inlet of the heat
pump to protect the evaporator against the ingress of impurities.

Clean the dirt trap’s filter screen one day after start-up and sub-
sequently in weekly intervals. If no more signs of contamination
are evident, the filter can be removed to reduce pressure drops.

10 Faults / Trouble-

Shooting

This heat pump is a quality product and is designed for trouble-
free operation. In the event that a fault should occur, it will be
shown on the heat pump manager display. Simply consult the
Faults and Trouble-shooting page in the operating instructions of
the heat pump manager.
If you cannot correct the fault yourself, please contact your after-
sales service technician.

ATTENTION!

Any work on the heat pump may only be performed by authorised and
qualified after-sales service technicians.

ATTENTION!

Disconnect all electrical circuits from the power source prior to opening
the device.

11 Decommissioning / 

Disposal

Before removing the heat pump, disconnect it from the power
source and close all valves. Observe all environmentally-relevant
requirements regarding the recovery, recycling and disposal of
materials and components in accordance with all applicable
standards. Particular attention should be paid to the proper dis-
posal of refrigerants and refrigeration oils.

Summary of Contents for SI 11USR

Page 1: ...ater Heat Pump for Indoor Installation Pompe chaleur eau glycol e eau pour installation int rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation...

Page 2: ......

Page 3: ...ufstellung D 4 6 1 Allgemeine Hinweise D 4 6 2 Schallemissionen D 4 7 Montage D 4 7 1 Allgemein D 4 7 2 Heizungsseitiger Anschluss D 4 7 3 W rmequellenseitiger Anschluss D 4 7 4 Elektrischer Anschluss...

Page 4: ...orgf ltige Bemessung der Heizungs bzw K hlungsanlage und der W rmequelle sehr wichtig Dabei ist im Heizbetrieb besonde res Augenmerk auf m glichst niedrige Wasservorlauftemperatu ren zu richten Darum...

Page 5: ...ssiger 2 Schaltblech 3 Verdichter 4 Verdampfer 4 Zubeh r 4 1 Soleverteiler Der Soleverteiler vereinigt die Kollektorschleifen der W rmequel lenanlage zu einer Hauptleitung welche an die W rmepumpe an...

Page 6: ...er Installation ist die Heizungsan lage zu f llen zu entl ften und abzudr cken Die im Schaltkasten angeschlossenen und lose eingelegten F h ler m ssen wie im Prinzipschema dargestellt angebracht und i...

Page 7: ...zu erfolgen 8 2 Vorbereitung Vor der Inbetriebnahme m ssen folgende Punkte gepr ft wer den Alle Anschl sse der W rmepumpe m ssen wie in Kapitel 7 beschrieben montiert sein Die W rmequellenanlage und d...

Page 8: ...sigers anzuschlie en Danach muss mit geeigneten neutralisierenden Mitteln gr ndlich nachgesp lt werden um Besch digungen durch even tuell im System verbliebene Reinigungsmittelreste zu verhin dern Die...

Page 9: ...0 4 5 9 9 4 6 11 4 4 6 14 1 5 0 bei B20 W18 kW 6 6 5 3 8 6 5 3 12 0 5 4 14 1 5 3 17 4 5 9 bei B10 W8 kW 5 4 5 6 7 0 5 5 9 9 5 6 11 6 5 7 14 7 6 4 bei B10 W18 kW 6 8 6 7 8 8 6 6 12 4 6 7 14 1 6 5 17 4...

Page 10: ...e Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf hren sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die Nach besse...

Page 11: ...3 6 Set up E 4 6 1 General Information E 4 6 2 Acoustic Emissions E 4 7 Installation E 4 7 1 General Information E 4 7 2 Heating System Connection E 4 7 3 Heat Source Connection E 4 7 4 Electrical Co...

Page 12: ...or cooling system and the heat source must be properly designed and dimensioned to ensure efficient operation It is particularly important to keep water flow tempera tures as low as possible in heati...

Page 13: ...cir cuit manifold 1 Liquifier 2 Control panel 3 Compressor 4 Evaporator 4 Accessories 4 1 Brine Circuit Manifold The brine circuit manifold merges the individual collector loops of the heat source sy...

Page 14: ...ed and insulated accord ing to the block diagram Minimum heating water flow rate The minimum heating water flow rate through the heat pump must be assured in all operating states of the heating system...

Page 15: ...ating operation 8 2 Preparation The following items need to be checked prior to start up The heat pump must be fully connected as described in Chapter 7 The heat source system and the heating circuit...

Page 16: ...circuit we recommend connecting the flushing device di rectly to the flow and return flow of the liquifier It is important that the system be thoroughly flushed using appropriate neutralising agents...

Page 17: ...8 kW 6 6 5 3 8 6 5 3 12 0 5 4 14 1 5 3 17 4 5 9 at B10 W8 kW 5 4 5 6 7 0 5 5 9 9 5 6 11 6 5 7 14 7 6 4 at B10 W18 kW 6 8 6 7 8 8 6 6 12 4 6 7 14 1 6 5 17 4 7 1 3 5 Sound power level dB A 54 55 56 56 5...

Page 18: ...E 8 English 12...

Page 19: ...F 4 6 1 G n ralit s F 4 6 2 Emissions sonores F 4 7 Montage F 5 7 1 Remarques d ordre g n ral F 5 7 2 Branchement c t installation de chauffage F 5 7 3 Raccordement c t source de chaleur F 5 7 4 Branc...

Page 20: ...s uniquement par des techniciens qualifi s et agr s ATTENTION Avant d ouvrir l appareil assurez vous que tous les circuits lectriques sont bien hors tension 1 2 Dispositions l gales et directives La p...

Page 21: ...si l eau de chauffage chauffe et atteint des temp ratures pouvant atteindre en fonction du point de fonctionnement jusqu 60 C Rafra chissement En mode rafra chissement les modes de fonctionnement de l...

Page 22: ...billage Pour vous aider porter l appareil un tube quelconque fera l affaire ATTENTION Ne pas soulever l appareil en utilisant les orifices de l habillage 6 Installation 6 1 G n ralit s En r gle g n ra...

Page 23: ...e la source de chaleur afin de prot ger l vaporateur des salissures Un s parateur d air doit en plus tre mont au point le plus haut de l installation de source de chaleur Pr parer l eau glycol e avant...

Page 24: ...al en eau de chauffage est assur par une vanne de trop plein il faut l adapter l installation de chauffage Un mauvais r glage pourrait conduire divers messages d er reur et une augmentation du besoin...

Page 25: ...ment sur le d part et le retour du condenseur Il faut ensuite soigneusement rincer l aide de produits neutralisants ad quats afin d viter tous dom mages provoqu s par d ventuels restes de produits de...

Page 26: ...ssance pour B20 W8 kW 5 4 4 6 7 0 4 5 9 9 4 6 11 4 4 6 14 1 5 0 pour B20 W18 kW 6 6 5 3 8 6 5 3 12 0 5 4 14 1 5 3 17 4 5 9 pour B10 W8 kW 5 4 5 6 7 0 5 5 9 9 5 6 11 6 5 7 14 7 6 4 pour B10 W18 kW 6 8...

Page 27: ...ode chauffage SI 14USR A XI 2 10 K hlbetrieb Cooling Operation Mode rafra chissement SI 14USR A XII 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques A XIII 3 1 Steuerung Standardregler Control for...

Page 28: ...3 X HQJHZLQGH HDW VRXUFH HDW SXPS RXWOHW H WHUQDO WKUHDG 6RXUFH GH FKDOHXU 6RUWLH GH OD 3 LOHWDJH H WpULHXU HL XQJVYRUODXI XVJDQJ DXV 3 X HQJHZLQGH HDWLQJ ZDWHU IORZ HDW SXPS RXWOHW H WHUQDO WKUHDG O...

Page 29: ...FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH L...

Page 30: ...V SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SR...

Page 31: ...RQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW W...

Page 32: ...V SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SR...

Page 33: ...FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW...

Page 34: ...LV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO S...

Page 35: ...FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW...

Page 36: ...V SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SR...

Page 37: ...FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW...

Page 38: ...ULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO...

Page 39: ...Commande r gulateur standard FKWXQJ ELV VRZLH XQG OLHJHQ DQ 9 V GDUI NHLQH 1HW VSDQQXQJ DQJHOHJW ZHUGHQ DUQLQJ WR DV ZHOO DV DQG DUH FRQQHFWHG WR 9 R QRW FRQQHFW WR PDLQV YROWDJH WWHQWLRQ j DLQVL TXH...

Page 40: ...ra chissement FKWXQJ ELV XQG VRZLH XQG OLHJHQ DQ 9 V GDUI NHLQH 1HW VSDQQXQJ DQJHOHJW ZHUGHQ DUQLQJ WR DQG DV ZHOO DV DQG DUH FRQQHFWHG WR 9 R QRW FRQQHFW WR PDLQV YROWDJH WWHQWLRQ j HW DLQVL TXH HW V...

Page 41: ...9RU GHP LQNOHPPHQ GHV 0 0RWRUVFKXW HV GLH UDKWEU FNH HQWIHUQHQ LVW GLH U FNH 6W UXQJ 0 7KH ZLUH MXPSHU PXVW EH UHPRYHG EHIRUH FRQQHFWLQJ WKH 0 PRWRU SURWHFWLRQ LV WKH 0 IDXOW MXPSHU 5HWLUHU OH FDYDOL...

Page 42: ...SDU OH FOLHQW RQWDNW RIIHQ 3 JHVSHUUW RQWDFW RSHQ 3 GLVDEOHG RQWDFW RXYHUW 3 EORTXpH LH XQNWLRQ YRQ LVW ZlKOEDU 7KH IXQFWLRQ RI FDQ EH VHOHFWHG D IRQFWLRQ GX SHXW rWUH VpOHFWLRQQpH WHU 6SHUUHLQJDQJ R...

Page 43: ...HQVLRQ VHFWHXU ZHUNVVHLWLJ YHUGUDKWHW LUHG UHDG IRU XVH kEOp HQ XVLQH EDXVHLWV EHL HGDUI DQ XVFKOLH HQ 7R EH FRQQHFWHG E WKH FXVWRPHU DV UHTXLUHG UDFFRUGHU VL QpFHVVDLUH SDU OH FOLHQW 7HPSHU 7HPS 7HPS...

Page 44: ...Compresseur M11 Prim rpumpe PUP Primary pump PUP Pompe primaire PUP M13 Heizungsumw lzpumpe Heat circulating pump Circulateur de chauffage M14 Heizungsumw lzpumpe 1 Heizkreis Heat circulating pump of...

Page 45: ...www dimplex de A XIX Anhang Appendix Annexes 4 1 4 Hydraulisches Prinzipschema Hydraulic Plumbing Diagram Sch ma hydraulique 4 1 Darstellung Schematic View Repr sentation...

Page 46: ...tor 2e g n rateur de chaleur M11 Soleumw lzpumpe Brine circulating pump Circulateur d eau glycol e M13 Heizungsumw lzpumpe Heat circulating pump Circulateur de chauffage M14 Umw lzpumpe f r Heiz und K...

Page 47: ...www dimplex de A XXI Anhang Appendix Annexes 5 5 Konformit tserkl rung Declaration of Conformity D claration de conformit...

Page 48: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Reviews: