Dimplex SI 11USR Installation And Operating Instructions Manual Download Page 15

www.dimplex.de

E-5

English

8.3

7.4 Electrical Connection

The following electrical connections must be established on the
heat pump:

„

Connection of the control line to the control panel of the heat
pump via terminal X1: L/N/PE.

„

Connection of the mains cable to the control panel of the
heat pump via terminal X6: L1/L2/L3/PE.

„

Connection of the brine circulating pump (to be provided by
the customer) to the control panel of the heat pump via ter-
minal X1: PE and pump contactor K5: 2/4/6.

All electrical components required for the operation of the heat
pump are located on the control panel.
For detailed instructions on how to connect the heat pump con-
troller and how it functions (e.g. external wall sensor included in
the scope of supply), please refer to the operating manual sup-
plied with the controller.
An all-pole disconnecting device with a contact gap of at least 3
mm (e.g. utility blocking contactor or power contactor) as well as
a 3-pole circuit breaker with common tripping for all external con-
ductors have to be provided by the customer. 
The required conductor cross section is to be selected according
to the power consumption of the heat pump, the technical con-
nection requirements of the respective utility company as well as
all applicable regulations. Details on the power consumption of
the heat pump are listed on both the product information sheet
and the type plate. The connection terminals are designed for a
max. conductor cross section of 10 mm².

ATTENTION!

Observe the clockwise rotating field when connecting the mains cable (if
rotating field is not clockwise, the heat pump will not work properly and
will be very noisy).

8 Commissioning

8.1 General Information

To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorised by the
manufacturer. This may be a condition for extending the guaran-
tee (see Warranty Service). Start-up should be carried out in
heating operation.

8.2 Preparation

The following items need to be checked prior to start-up:

„

The heat pump must be fully connected, as described in
Chapter 7.

„

The heat source system and the heating circuit must have
been filled and checked.

„

The dirt trap must be inserted in the brine inlet of the heat
pump.

„

All valves that could impair proper flow in the brine and heat-
ing circuits must be open.

„

The heat pump controller must be adapted to the heating
system in accordance with the controller’s operating instruc-
tions.

8.3 Start-up Procedure

The heat pump is started up via the heat pump controller.

ATTENTION!

The heat pump must be started up in accordance with the installation and
operating instructions of the heat pump controller.

If an overflow valve is fitted to assure the minimum heating water
flow rate, the valve must be set in accordance with the require-
ments of the respective heating system. Incorrect adjustment
can lead to faulty operation and increased energy consumption.
We recommend carrying out the following procedure to correctly
adjust the overflow valve:
Close all of the heating circuits that may also be closed during
operation (depending on the type of heat pump usage) so that
the most unfavourable operating state - with respect to the water
flow rate - is achieved. This normally means the heating circuits
of the rooms on the south and west sides of the building. At least
one heating circuit must remain open (e.g. bathroom).
The overflow valve should be opened far enough to produce the
maximum temperature spread between the heating flow and re-
turn flow listed in the table below for the current heat source tem-
perature. The temperature spread should be measured as close
as possible to the heat pump. The heating element of mono en-
ergy systems should be disconnected.

Any faults occurring during operation are displayed on the heat
pump controller and can be corrected as described in the operat-
ing manual of the heat pump controller.

Heat source
temperature

Max. temperature spread 

between heating flow and return 

flow

From

To

-5° C

0° C

10 K

1° C

5° C

11 K

6° C

9° C

12 K

10° C

14° C

13 K

15° C

20° C

14 K

21° C

25° C

15 K

Summary of Contents for SI 11USR

Page 1: ...ater Heat Pump for Indoor Installation Pompe chaleur eau glycol e eau pour installation int rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation...

Page 2: ......

Page 3: ...ufstellung D 4 6 1 Allgemeine Hinweise D 4 6 2 Schallemissionen D 4 7 Montage D 4 7 1 Allgemein D 4 7 2 Heizungsseitiger Anschluss D 4 7 3 W rmequellenseitiger Anschluss D 4 7 4 Elektrischer Anschluss...

Page 4: ...orgf ltige Bemessung der Heizungs bzw K hlungsanlage und der W rmequelle sehr wichtig Dabei ist im Heizbetrieb besonde res Augenmerk auf m glichst niedrige Wasservorlauftemperatu ren zu richten Darum...

Page 5: ...ssiger 2 Schaltblech 3 Verdichter 4 Verdampfer 4 Zubeh r 4 1 Soleverteiler Der Soleverteiler vereinigt die Kollektorschleifen der W rmequel lenanlage zu einer Hauptleitung welche an die W rmepumpe an...

Page 6: ...er Installation ist die Heizungsan lage zu f llen zu entl ften und abzudr cken Die im Schaltkasten angeschlossenen und lose eingelegten F h ler m ssen wie im Prinzipschema dargestellt angebracht und i...

Page 7: ...zu erfolgen 8 2 Vorbereitung Vor der Inbetriebnahme m ssen folgende Punkte gepr ft wer den Alle Anschl sse der W rmepumpe m ssen wie in Kapitel 7 beschrieben montiert sein Die W rmequellenanlage und d...

Page 8: ...sigers anzuschlie en Danach muss mit geeigneten neutralisierenden Mitteln gr ndlich nachgesp lt werden um Besch digungen durch even tuell im System verbliebene Reinigungsmittelreste zu verhin dern Die...

Page 9: ...0 4 5 9 9 4 6 11 4 4 6 14 1 5 0 bei B20 W18 kW 6 6 5 3 8 6 5 3 12 0 5 4 14 1 5 3 17 4 5 9 bei B10 W8 kW 5 4 5 6 7 0 5 5 9 9 5 6 11 6 5 7 14 7 6 4 bei B10 W18 kW 6 8 6 7 8 8 6 6 12 4 6 7 14 1 6 5 17 4...

Page 10: ...e Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf hren sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die Nach besse...

Page 11: ...3 6 Set up E 4 6 1 General Information E 4 6 2 Acoustic Emissions E 4 7 Installation E 4 7 1 General Information E 4 7 2 Heating System Connection E 4 7 3 Heat Source Connection E 4 7 4 Electrical Co...

Page 12: ...or cooling system and the heat source must be properly designed and dimensioned to ensure efficient operation It is particularly important to keep water flow tempera tures as low as possible in heati...

Page 13: ...cir cuit manifold 1 Liquifier 2 Control panel 3 Compressor 4 Evaporator 4 Accessories 4 1 Brine Circuit Manifold The brine circuit manifold merges the individual collector loops of the heat source sy...

Page 14: ...ed and insulated accord ing to the block diagram Minimum heating water flow rate The minimum heating water flow rate through the heat pump must be assured in all operating states of the heating system...

Page 15: ...ating operation 8 2 Preparation The following items need to be checked prior to start up The heat pump must be fully connected as described in Chapter 7 The heat source system and the heating circuit...

Page 16: ...circuit we recommend connecting the flushing device di rectly to the flow and return flow of the liquifier It is important that the system be thoroughly flushed using appropriate neutralising agents...

Page 17: ...8 kW 6 6 5 3 8 6 5 3 12 0 5 4 14 1 5 3 17 4 5 9 at B10 W8 kW 5 4 5 6 7 0 5 5 9 9 5 6 11 6 5 7 14 7 6 4 at B10 W18 kW 6 8 6 7 8 8 6 6 12 4 6 7 14 1 6 5 17 4 7 1 3 5 Sound power level dB A 54 55 56 56 5...

Page 18: ...E 8 English 12...

Page 19: ...F 4 6 1 G n ralit s F 4 6 2 Emissions sonores F 4 7 Montage F 5 7 1 Remarques d ordre g n ral F 5 7 2 Branchement c t installation de chauffage F 5 7 3 Raccordement c t source de chaleur F 5 7 4 Branc...

Page 20: ...s uniquement par des techniciens qualifi s et agr s ATTENTION Avant d ouvrir l appareil assurez vous que tous les circuits lectriques sont bien hors tension 1 2 Dispositions l gales et directives La p...

Page 21: ...si l eau de chauffage chauffe et atteint des temp ratures pouvant atteindre en fonction du point de fonctionnement jusqu 60 C Rafra chissement En mode rafra chissement les modes de fonctionnement de l...

Page 22: ...billage Pour vous aider porter l appareil un tube quelconque fera l affaire ATTENTION Ne pas soulever l appareil en utilisant les orifices de l habillage 6 Installation 6 1 G n ralit s En r gle g n ra...

Page 23: ...e la source de chaleur afin de prot ger l vaporateur des salissures Un s parateur d air doit en plus tre mont au point le plus haut de l installation de source de chaleur Pr parer l eau glycol e avant...

Page 24: ...al en eau de chauffage est assur par une vanne de trop plein il faut l adapter l installation de chauffage Un mauvais r glage pourrait conduire divers messages d er reur et une augmentation du besoin...

Page 25: ...ment sur le d part et le retour du condenseur Il faut ensuite soigneusement rincer l aide de produits neutralisants ad quats afin d viter tous dom mages provoqu s par d ventuels restes de produits de...

Page 26: ...ssance pour B20 W8 kW 5 4 4 6 7 0 4 5 9 9 4 6 11 4 4 6 14 1 5 0 pour B20 W18 kW 6 6 5 3 8 6 5 3 12 0 5 4 14 1 5 3 17 4 5 9 pour B10 W8 kW 5 4 5 6 7 0 5 5 9 9 5 6 11 6 5 7 14 7 6 4 pour B10 W18 kW 6 8...

Page 27: ...ode chauffage SI 14USR A XI 2 10 K hlbetrieb Cooling Operation Mode rafra chissement SI 14USR A XII 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques A XIII 3 1 Steuerung Standardregler Control for...

Page 28: ...3 X HQJHZLQGH HDW VRXUFH HDW SXPS RXWOHW H WHUQDO WKUHDG 6RXUFH GH FKDOHXU 6RUWLH GH OD 3 LOHWDJH H WpULHXU HL XQJVYRUODXI XVJDQJ DXV 3 X HQJHZLQGH HDWLQJ ZDWHU IORZ HDW SXPS RXWOHW H WHUQDO WKUHDG O...

Page 29: ...FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH L...

Page 30: ...V SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SR...

Page 31: ...RQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW W...

Page 32: ...V SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SR...

Page 33: ...FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW...

Page 34: ...LV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO S...

Page 35: ...FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW...

Page 36: ...V SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SR...

Page 37: ...FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW...

Page 38: ...ULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO...

Page 39: ...Commande r gulateur standard FKWXQJ ELV VRZLH XQG OLHJHQ DQ 9 V GDUI NHLQH 1HW VSDQQXQJ DQJHOHJW ZHUGHQ DUQLQJ WR DV ZHOO DV DQG DUH FRQQHFWHG WR 9 R QRW FRQQHFW WR PDLQV YROWDJH WWHQWLRQ j DLQVL TXH...

Page 40: ...ra chissement FKWXQJ ELV XQG VRZLH XQG OLHJHQ DQ 9 V GDUI NHLQH 1HW VSDQQXQJ DQJHOHJW ZHUGHQ DUQLQJ WR DQG DV ZHOO DV DQG DUH FRQQHFWHG WR 9 R QRW FRQQHFW WR PDLQV YROWDJH WWHQWLRQ j HW DLQVL TXH HW V...

Page 41: ...9RU GHP LQNOHPPHQ GHV 0 0RWRUVFKXW HV GLH UDKWEU FNH HQWIHUQHQ LVW GLH U FNH 6W UXQJ 0 7KH ZLUH MXPSHU PXVW EH UHPRYHG EHIRUH FRQQHFWLQJ WKH 0 PRWRU SURWHFWLRQ LV WKH 0 IDXOW MXPSHU 5HWLUHU OH FDYDOL...

Page 42: ...SDU OH FOLHQW RQWDNW RIIHQ 3 JHVSHUUW RQWDFW RSHQ 3 GLVDEOHG RQWDFW RXYHUW 3 EORTXpH LH XQNWLRQ YRQ LVW ZlKOEDU 7KH IXQFWLRQ RI FDQ EH VHOHFWHG D IRQFWLRQ GX SHXW rWUH VpOHFWLRQQpH WHU 6SHUUHLQJDQJ R...

Page 43: ...HQVLRQ VHFWHXU ZHUNVVHLWLJ YHUGUDKWHW LUHG UHDG IRU XVH kEOp HQ XVLQH EDXVHLWV EHL HGDUI DQ XVFKOLH HQ 7R EH FRQQHFWHG E WKH FXVWRPHU DV UHTXLUHG UDFFRUGHU VL QpFHVVDLUH SDU OH FOLHQW 7HPSHU 7HPS 7HPS...

Page 44: ...Compresseur M11 Prim rpumpe PUP Primary pump PUP Pompe primaire PUP M13 Heizungsumw lzpumpe Heat circulating pump Circulateur de chauffage M14 Heizungsumw lzpumpe 1 Heizkreis Heat circulating pump of...

Page 45: ...www dimplex de A XIX Anhang Appendix Annexes 4 1 4 Hydraulisches Prinzipschema Hydraulic Plumbing Diagram Sch ma hydraulique 4 1 Darstellung Schematic View Repr sentation...

Page 46: ...tor 2e g n rateur de chaleur M11 Soleumw lzpumpe Brine circulating pump Circulateur d eau glycol e M13 Heizungsumw lzpumpe Heat circulating pump Circulateur de chauffage M14 Umw lzpumpe f r Heiz und K...

Page 47: ...www dimplex de A XXI Anhang Appendix Annexes 5 5 Konformit tserkl rung Declaration of Conformity D claration de conformit...

Page 48: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Reviews: