Dimplex SCx175sd Installation And Operation Manual Download Page 6

 

6

4.7. Pipework connections 

 

All Pipework connections to the cylinder 

MUST

 be made in accordance 

with Fig 4.1, the secondary return being optional. 
 
4.7.1 The 

 SCX Solar

 unvented cylinder must be installed by a competent person with appropriate 

qualifications and registration for the installation of unvented water storage heaters.  

4.7.2  The cold water feed to the cylinder must be fed through the pressure reducing valve, take care 

to install this in the correct direction (see arrow on side of valve) and then the pressure relief  
valve, with the expansion vessel Tee’d off between the pressure relief valve and the cylinder. 

4.7.3  For the single coil cylinder the immersion must be connected and suitably controlled to bring 

the temperature of water to 60

o

C following heating by the solar source. 

 

 

4.8   Hard Water Areas – 

In hard water areas it is advisable to use a water softening device to 

minimise scale build-up. Periodically the immersion should be removed and scale scraped way from 
the bottom of the cylinder to avoid scale surrounding the immersion and causing failure. 

  

 
 

5. Primary circuit installation 

 

5.1.

 Dimplex Solar cylinders are suitable for connecting to a solar collector system and where a twin 

coil is present, to a gas or oil central heating boiler. 
 

! Solid fuel or wood burning boilers, and gravity circulation systems MUST NOT be used on 
the primary circuit of an unvented hot water system!  

 

5.2. Systems design –

 The cylinder must be installed in accordance with the solar installation 

instructions for connection to the primary flow and return.  

 

5.3  Two-port Motorised valves – 

The  SCx Solar range of cylinders must only be connected to solar 

installations containing a hydraulic station with two non return valves (one in the flow to the collector 
and one in the return), that will prevent thermal siphoning of the heat transfer fluid when the pump is 
switched off.  Where two non-return valves are not present or a hydraulic station is not used a second 
twin port valve must be installed into the flow of the solar coil and wired to the lower twin-port valve. 
The  SCx cylinder comes with one two-port motorised valve, which should be connected in the flow to 
the auxiliary coil and wired to the upper twin thermostat of the cylinder. 
 

5.4 Solar Pump

 – The lower twin thermostat should be connected in-line with the solar pump power 

supply. 
 

 
 

6. Secondary circuit installation

 

6.1. Connections

. Secondary circuit

 

connections 

MUST

 be made to the cylinder in accordance with 

Fig 4.1/4.2. A drain cock (not supplied) should be fitted in the cold water inlet to facilitate draining of 
the cylinder. 
 

6.2

Cold water supply –

 Where possible, for best results, the cylinder should be fed by an 

uninterrupted 22mm supply pipe into the pressure reducing valve (PR valve) with a supply pressure of 
between 3 and 12bar maximum. The cylinder should not be used on any system with a supply 
pressure below 1.5 bar and a flow rate of less than 20litres per minute. 
 

6.3. Temperature and pressure relief valve 

– The temperature and pressure relief valve (T&P 

valve) is supplied factory fitted to the cylinder. The TPV must not be removed from the cylinder or 

Summary of Contents for SCx175sd

Page 1: ...SOLAR UNVENTED WATER HEATERS Installation and Operation Manual Important This Manual Should Be Left With The Cylinder After Installation...

Page 2: ...quirements 5 5 Primary circuit installation 6 6 Secondary circuit installation 6 7 Discharge arrangement 8 8 Electrical installation 10 9 Filling and commissioning 11 10 Servicing and maintenance 12 1...

Page 3: ...42 542 542 542 542 542 Solar Return mm 380 380 380 380 380 380 380 380 Cold Inlet mm 300 300 300 300 300 300 300 300 solar Coil size sqm 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Aux Coil size sqm 0 75 0 75 0 7...

Page 4: ...4 2 2 Connection 2 2 1 SOLAR Indirect 2 2 2 Single Coil Direct Electric...

Page 5: ...it to function but flow from the outlets will be low if several outlets are used simultaneously Correct performance is achieved with supplies between 3bar and 12bar The cylinder control equipment is f...

Page 6: ...nce with the solar installation instructions for connection to the primary flow and return 5 3 Two port Motorised valves The SCx Solar range of cylinders must only be connected to solar installations...

Page 7: ...ve should be connected to the secondary return of the cylinder See fig 4 1 4 2 IMPORTANT If a secondary circulation circuit is installed then a larger expansion vessel may be required to handle the in...

Page 8: ...lity at one or other of these locations Examples of acceptable discharge arrangements are Ideally below a fixed grating and above the water seal in a trapped gully Downward discharge at low level i e...

Page 9: ...diameter temperature relief valve with a discharge pipe D2 having 4 elbows and a length of 7m from the tundish to the point of discharge From the table above the maximum resistance allowed for a strai...

Page 10: ...the following should also be observed 8 2 1 Ensure the mains voltage corresponds to the voltage rating of the immersion heater as shown on the rating label on the terminal cover 8 2 2 Insert the imme...

Page 11: ...3 8 4 The Power Supply to the pump station should be connected via the lower 9 Filling and commissioning 9 1 Check that the expansion vessel charge pressure is 3bar 9 2 Check that all connections are...

Page 12: ...k that the immersion or boiler switches off when the cylinder reaches the desired temperature 10 Servicing and maintenance 10 1 Servicing and maintenance must only be carried out by a competent unvent...

Page 13: ...ked 3 Pressure reducing valve PRV fitted the wrong way 1 Open stopcock 2 Turn water supply off remove strainer and clean see 10 6 3 Re fit with arrow pointing in direction of flow Water from hot taps...

Page 14: ...ntrols supplied with the cylinder excluding the immersion for a period of 5 years from the date of purchase provided that they have been installed for their intended use by a competent person and have...

Page 15: ...m straight tundish SC06004 3kW Immersion heater SC070011 or SC070012 22mm Pressure reducing valve kit SC07015 22mm 2 port motorised valve SC06005 Twin Cylinder Thermostat SC06006 For assistance please...

Page 16: ...f practice It is recommended that your hot water system is serviced regularly and that your service engineer completes the appropriate Service Interval Record below SERVICE 1 DATE SERVICE 2 DATE ENGIN...

Reviews: