3. INSTALLATION

3.1  Where to install
The unit can be installed anywhere in your home and enables the
remote control of all heaters connected to the system from the
central programmer.

3.2  Fixing
To wall-mount the unit, it is necessary to remove the base.
To do this, remove the single screw from underneath the unit as
shown in Fig.1.
Once separated from the unit, the base should be fixed to the
wall using screws/plugs or to a connection box (60mm fixing
centres) using the holes      provided.
Recessed gaps are provided to let the connection wires through
     for the connection box,     for surface mounting.

50 Hz

Fréquence
porteuse

Réseau EDF 230V

Transmitter

Receiver

2

3

Fig 1

RX010007
Two-Zone Wall Mounted Programmer
 – Mains Borne Signalling

1.  SPECIFICATION

230V, +/-10%, 50Hz power supply

Clock back-up in case of power cut:
4 hrs approx. (by capacitor)

Consumption: 4 VA

Class II insulation

Function mode selection switch

Choice of four permanent modes
(Frost-protection, Setback, Comfort,
Off) and one customisable programme
per day, per zone

Automatic override by zone until next
programme change

Programmable frost-protection
adjustable for 1 to 99 days

2. GENERAL PRINCIPLE
The main principle of “MBS” transmissions is
to superimpose a coded signal with a higher
frequency and lower amplitude on the 50Hz
mains frequency, between the live and
neutral wires.

Appliance conforms to the requirements of

directives CEE 89/336 (Electromagnetic

Accountability) and CEE 73/23 modified

CEE 93/68 (Low tension safety).

Guarantee

Your product is guaranteed for one year from

the date of purchase. We undertake to repair

or exchange free of charge within the

guarantee period any part found to be

defective. Your rights under the guarantee

are additional to your statutory rights, which

in turn are unaffected by this guarantee.

If the programmer is not working correctly,

please contact our Customer Helpline on

0870 727 0101.

This guarantee only applies in the United

Kingdom.

Installation and Operating Instructions

Glen Dimplex UK Ltd

Millbrook House, Grange Drive

Hedge End, Southampton

SO30 2DF

Customer Helpline

T el:

 0870 727 0101

8am-6pm Mon-Fri

8:30am-1pm Sat

Fax: 0870 727 0102

Republic of Ireland: 01 842 4833

Fig 3

Fig 2

1

1

T0203/05/A

3

1

2

2

3

3

Emission frequency: 132.45kHz

Emission power conforms to standard
CENELEC EN 50065-1

Internal resistance: 5

Reception sensitivity: 2.5mV

“House” addressing: 65000 factory-
coded combinations

Digital display

Control panel: 128 x 85 x 43 mm

Wall fixing to connection box or surface-
mount

Protection index: IP 30

In the case of a three-phase installation, you should use a phase
coupler to transmit over the 3 phases simultaneously.

Signal

230V mains

circuit

50Hz

3.3  Connection
The electrical installation must be carried
out by a competent electrician and be in
strict accordance with the current IEE
regulations for Electrical Equipment in
Buildings.
Before doing anything, switch off the
power supply.
Pull off the termnal block      (Fig 2) from the
pins on the board. Connect the two supply
wires to the terminals and replace the block
on the pins.
Position the unit on the base, first hooking
the two recesses in the inside top over the
hooks on the base, then swing the unit down
into position.  Ensure the wires are not
trapped behind transformer      . Secure with
the fixing screw as shown in Fig 1.

Programmer

Z1

Day zone

Z2

Night zone

5.  START-UP
This procedure sets up the communication between the programmer and the heaters in
the system.

1. Go into the service mode by turning the switch to 

 .

The display will show  “PArA”.

2. Press and hold down the + and – buttons together for

approx. 5 seconds.
The display will show FP4 and markings for zone 1.
Press OK twice.
If display shows FP6, press the + or – key to reset the
display to FP4.

3. Press OK. The display will show “ENET”. Press OK

again.

4. Display shows “ENET” and markings next to zone 1.

The code for zone 1 is now being transmitted.

5. Insert a receiver cassette into each heater, as per the

cassette instructions. Ensure heater is set to the 
position.

6. On each heater for zone 1, press and hold down the

button on the receiver cassettefor approx. 10
seconds until the LED indicator starts to flash.

Release the button, then press again to confirm; the
LED will light continuously.

7. Press OK on the programmer and repeat steps 2-5

for all the heaters in zone 2.

8. Press OK when completed and before changing the

switch position - see over.

N

Ph1 Ph2 Ph3

Coupleur de phases

Phase coupler