1
Type and order code
LIK 8TE
2
Design
2.1
Model
Compact
2.2
Degree of protection according to EN 60 529 for compact devices
and heating components
IP 20
2.3
Installation location
Indoors
3
Performance data
3.1
Operating temperature limits:
Heating water flow/return flow
°C / °C
Up to 58 / above 18
Air
°C
-25 to +35
3.2
Temperature spread of heating water (flow/return flow) at A7 / W35
10.0
5.0
3.3
Heat output / COP
at A-7 / W35
1
kW / ---
1. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, the defrosting
capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning: External temperature 2 °C
and heating water flow temperature 55 °C.
5.8 / 2.7
5.5 / 2.6
at A-7 / W45
1
kW / ---
5.4 / 2.1
at A2 / W35
1
kW / ---
7.5 / 3.3
7.4 / 3.2
at A7 / W35
1
kW / ---
9.3 / 3.9
9.2 / 3.8
at A7 / W45
1
kW / ---
8.8 / 3.2
at A10 / W35
1
kW / ---
9.8 / 4.1
9.7 / 4.0
3.4
Sound power level device / outdoors
dB(A)
53 / 60
3.5
Sound pressure level at a distance of 1 m (indoors)
dB(A)
48.0
3.6
Heating water flow
with an internal pressure differential of
2
m³/h / Pa
2. The heat circulating pump is integrated.
0.8 / 2700
1.6 / 11900
3.7
Free pressure, heating circulating pump (max. stage)
Pa
45000.0
3.8
Air flow rate
with an external static pressure differential of
m³/h / Pa
2500 / 20
3.9
Refrigerant; total filling weight
type / kg
R404A / 2.0
3.10 Lubricant; total filling weight
type / litres
Polyolester (POE) / 1.5
3.11 Output of electric heating element
(second heat generator)
kW
2.0
4
Dimensions, connections and weight
4.1
Device dimensions
H x W x L cm
190 x 75 x 68
4.2
Device connections to heating system
Inch
G 1'' external
4.3
Air duct inlet and outlet (min. internal dimensions)
L x W cm
44 x 44
4.4
Weight of the transportable unit(s) incl. packing
kg
264
4.5
Buffer tank volume
l
50
4.6
Buffer tank pressure rating
bar
6
5
Electrical Connection
5.1
Nominal voltage; fuse protection
V / A
400 / 25
5.2
Nominal power consumption
1
A2 W35
kW
2.27
2.33
5.3
Starting current with soft starter
A
19.5
5.4
Nominal current A2 W35 / cos
ϕ
A / ---
4.1 / 0.8
4.2 / 0.8
6
Complies with the European safety regulations
3
3. See CE declaration of conformity
7
Additional model features
7.1
Defrosting
Automatic
Type of defrosting
Reverse cycle
Defrosting tray included
Yes (heated)
7.2
Heating water in device protected against freezing
4
4. The heat circulating pump and the heat pump manager must always be ready for operation.
Yes
7.3
Performance levels
1
7.4
Controller internal/external
Internal
Summary of Contents for LIK 8TE
Page 2: ......
Page 16: ...DE 14 Deutsch 13 ...
Page 42: ...FR 14 Français 12 ...
Page 55: ...www dimplex de A XIII Anhang Appendix Annexes 5 ...
Page 56: ...A XIV Anhang Appendix Annexes 5 ...
Page 57: ...www dimplex de A XV Anhang Appendix Annexes 5 ...
Page 58: ...A XVI Anhang Appendix Annexes 5 ...
Page 59: ...www dimplex de A XVII Anhang Appendix Annexes 5 ...