12 Device Information
1
Type and order code
LI 9TEL
2
Design
2.1
Degree of protection according to EN 60 529 for compact devices
and heating components
IP 21
2.2
Installation location
Indoors
3
Performance data
3.1
Operating temperature limits:
Heating water flow/return flow
°C / °C
Up to 58 / above 18
Air
°C
-25 to +35
3.2
Temperature spread of heating water
(flow/return flow)
at A7 / W35
K
10,0
5,0
3.3
Heat output / COP
at A-7 / W35
1
kW / ---
1. This data indicates the size and capacity of the system according to EN 255 or EN 14511. For an analysis of the economic and energy efficiency of the system, other parameters,
in particular the defrosting capacity, the bivalence point and regulation, should also be taken into consideration. The specified values have the following meaning, e.g. A2 / W35:
2 °C external air temperature and 35 °C heating water flow temperature.
5,8 / 2,7
5,5 / 2,6
at A-7 / W45
1
kW / ---
5,4 / 2,1
at A2 / W35
1
kW / ---
7,5 / 3,3
7,4 / 3,2
at A7 / W35
1
kW / ---
9,3 / 3,9
9,2 / 3,8
at A7 / W45
1
kW / ---
8,8 / 3,2
at A10 / W35
1
kW / ---
9,8 / 4,1
9,7 / 4,0
3.4
Sound power level device / outdoors
dB(A)
53 / 60
3.5
Sound pressure level at a distance of 1 m (indoors)
2
dB(A)
2. The specified sound pressure level represents the free field level. The measured value can be up to 16 dB(A) higher, depending on the installation location. This value corresponds
to the operating noise of the heat pump in heating operation with a flow temperature of 35 °C.
48,0
3.6
Heating water flow with an internal pressure differential of m³/h / Pa
0,8 / 2700
1,6 / 11900
3.7
Air flow rate with an external static pressure differential of m³/h / Pa
2500 / 20
3.8
Refrigerant; total filling weight
type / kg
R404A / 1,9
3.9
Lubricant; total filling weight
type / litres
Polyolester (POE) / 1.5
3.10 Max. output of electric heating element
(2nd heat generator)
kW
6,0
4
Dimensions, connections and weight
4.1
Device dimensions
H x W x L cm
125 x 85 x 68
4.2
Device connections to heating system
Inch
G 1'' external
4.3
Air duct inlet and outlet (min. internal dimensions)
L x W cm
44 x 44
4.4
Weight of the transportable unit(s) incl. packing
kg
186
5
Electrical Connection
5.1
Nominal voltage; fuse protection
(combined infeed HP and HG2)
V / A
400 / 25
5.2
Fuse protection for separate infeed: HP / HG2
16 / 10
5.3
Nominal power consumption
1
A2 W35
kW
2,27
2,33
5.4
Starting current with soft starter
A
19,5
5.5
Nominal current A2 W35 / cos
ϕ
A / ---
4,1 / 0,8
4,2 / 0,8
6
Complies with the European safety regulations
3
3. See CE declaration of conformity
7
Additional model features
7.1
Defrosting
Automatic
Type of defrosting
Reverse cycle
Defrosting tray included
Yes (heated)
7.2
Heating water in device protected against icing
4
4. The heat circulating pump and the heat pump manager must always be ready for operation.
Yes
7.3
Performance levels
1
7.4
Controller internal/external