www.dimplex.de 452163.66.09 · FD 9312
EN-9
English
LA 9TU - LA 12TU
11 Device information
1
Type and order code
LA 9TU
LA 12TU
2
Design
2.1
Controller
External
External
2.2
Thermal energy metering
Integrated
Integrated
2.3
Installation location / degree of protection according to EN 60529
Outdoor / IP24
Outdoor / IP24
2.4
Antifreeze condensate tray / heating water
Heated / yes
1
1. The heat circulating pump and the heat pump controller must always be ready for operation.
Heated / yes
2.5
Performance levels
1
1
3
Operating limits
3.1
Heating water flow / return
°C
up to 58 ± 2 / from 18
up to 58 ± 2 / from 18
3.2
Air (heat source)
°C
-20 to +35
-25 to +35
4
Performance data / flow rate
2
2. These data indicate the size and capacity of the system according to EN 14511 (5K at A7). For an analysis of the economic and energy efficiency of the system, other parameters,
in particular the defrosting capacity, the bivalence point and the regulation, should also be taken into consideration. These specifications can only be achieved with clean heat
exchangers. Information on the maintenance, start-up and operation can be found in the respective sections of the installation and operating instructions. The specified values
have the following meaning, e.g. A7 / W35: External air temperature 7 °C and heating water flow temperature 35 °C.
4.1
Heating water flow rate /
internal pressure differential
maximum
m³/h / Pa
1.6 / 7300
2.0 / 2900
minimum
m³/h / Pa
0.7 / 1600
0.9 / 600
4.2
Heat output / COP
3
3. With maximum heating flow rate
EN 14511
EN 14511
at A-7 / W35
kW / ---
5.5 / 2.8
7.6 / 3,0
at A2 / W35
kW / ---
7.5 / 3.7
9.6 / 3.7
at A7 / W35
kW / ---
9.2 / 4.2
11.4 / 4.3
at A7 / W55
kW / ---
7.1 / 2.7
9.8 / 2.5
at A10 / W35
kW / ---
10.2 / 4.5
11.7 / 4.6
4.3
Sound power level according to EN 12102
Normal operation/reduced operation.
4
dB(A)
4. The heat output is reduced by approx. 9 % in lower operation
60 / 55
61 / -
4.4
Sound pressure level at a distance of 10 m (air outlet side)
5
Normal operation/reduced operation.
dB(A)
5. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35 °C.
30 / 25
32 / -
4.5
Air flow
m³/h
2500
4100
5
Dimensions, weight and filling quantities
5.1
Device dimensions without connections
H x W x L mm
1460 x 910 x 750
1810 x 1250 x 750
5.2
Device connections for heating system
Inches
Thread 1 1/4" flat sealing
Thread 1 1/4" flat sealing
5.3
Weight of the transport unit(s) incl. packaging
kg
208
280
5.4
Refrigerant / total filling weight
type / kg
R404A / 3.4
R404A / 4.2
5.5
Lubricant / total filling quantity
type / litres
Polyolester (POE) / 1.3
Polyolester (POE) / 1.45
6
Electrical connection
6.1
Supply voltage / fuse protection
3~/ PE 400 V (50 Hz) / C16 A
3~/ PE 400 V (50 Hz) / C16 A
6.2
Control voltage / fuse protection
- / -
- / -
6.3
Starting current with soft starter
A
17
18
6.4
Nominal power consumption at A2/W35 /
max. power consumption
2.04 / 3.5
2.52 / 3.8
6.5
Power consumption ventilator
W
up to 140
up to 180
6.6
Nominal current at A2/W35 / cos
A / ---
3.68 / 0.8
4.55 / 0.8
6.7
Max. power consumption of compressor protection
(per compressor)
W
---
70; thermostatically controlled
7
Complies with the European safety regulations
6
6. See CE declaration of conformity
8
Additional model features
8.1
Type of defrosting (according to need)
Reverse circulation
Reverse circulation
8.2
Max. operating overpressure (heat sink)
bar
3,0
3,0
Summary of Contents for LA 12TU
Page 2: ......
Page 14: ...DE 12 452163 66 09 FD 9312 www dimplex de Deutsch LA 9TU LA 12TU...
Page 24: ...EN 10 452163 66 09 FD 9312 www dimplex de English LA 9TU LA 12TU...
Page 54: ...A XX 452163 66 09 FD 9312 www dimplex de Anhang Appendix Annexes LA 9TU LA 12TU...
Page 55: ...www dimplex de 452163 66 09 FD 9312 A XXI Anhang Appendix Annexes LA 9TU LA 12TU...