English

6.3

Antifreeze

Manual drainage should be provided for heat pumps which are
exposed to frost. The antifreeze function of the heat pump con-
troller is active whenever the controller and the heat circulating
pump are ready for operation. If the heat pump is taken out of
service or in the event of a power failure, the system has to be
drained, and if required, blown out, at three locations (see illus-
tration). The heating circuit should be operated with a suitable
antifreeze if heat pump systems are implemented in buildings
where a power failure can not be detected (holiday home).

6.3 Electrical Connection

A standard four-core cable is used for connecting the heat pump
to the power supply.
The power supply and the control line are normally installed in
the ground (in ductwork with a suitable size and resistance) and
routed from the heat pump to the building. This ductwork must
extend into the heat pump by approx. 22 mm and be installed
with a continuous downward slope in order to comply with Sec-
tion 42 of the VDE 0100 regulations. Instead of 90° bends, two
45° bends must be used as pipe bends. The control line and the
cable for the power supply are drawn into this ductwork.
The cable (power supply) must be provided by the customer. The
conductor cross section is selected in accordance with the power
consumption of the heat pump (see Appendix Device Informa-
tion) and the applicable VDE (EN) and VNB regulations.
The power supply line on the heat pump must be fed through the
provided cable feedthrough into the switch box. The line must be
firmly screwed to its feedthrough (vapour sealed pipe union).
An all-pole disconnecting device with a contact gap of at least
3 mm (e.g. utility blocking contactor or power contactor) as well
as a 3-pole circuit breaker with common tripping for all external
conductors must be installed in the power supply (tripping current
in compliance with the Device Information). Ensure that the in-
coming supply has a clockwise rotating field when connecting
multiphase devices.
Phase sequence: L1, L2, L3.

ATTENTION!

Ensure that there is a clockwise rotating field: Operating the compressor
in the wrong rotational direction could cause damage to the compressor.

The control voltage is supplied via the heat pump controller.
The heat pump controller has a 230 V AC-50 Hz power supply.
Connect the controller in compliance with its own operating in-
structions (16 A fuse).

The control line (not included in scope of supply) is connected to
the heat pump controller using the two rectangular plug connec-
tors and the single-core wire. The plug connector is located on
the bottom side of the switch box inside the heat pump. More de-
tailed information can be found in the operating instructions of
the heat pump controller.
For detailed information, see Circuit Diagrams in the Appendix.

7 Start-up

7.1 General Information

To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorised by the
manufacturer. This may be a condition for extending the guaran-
tee (see Warranty).

7.2 Preparation

The following items need to be checked prior to start-up:

„

The heat pump must be fully connected, as described in
Chapter 6.

„

All valves that could impair the proper flow of the heating
water in the heating circuit must be open.

„

The air intake and air outlet paths must be clear.

„

The ventilator must turn in the direction indicated by the ar-
row.

„

The settings of the heat pump controller must be adapted to
the heating system in accordance with the controller’s oper-
ating instructions.

„

Ensure the condensate outflow functions properly.

7.3 Procedure

The heat pump is started up via the heat pump controller. Adjust-
ments should be made in compliance with the instructions.
If an overflow valve is fitted to assure the minimum heating water
flow rate, the valve must be set in accordance with the require-
ments of the respective heating system. Incorrect adjustment
can lead to faulty operation and increased energy consumption.
We recommend carrying out the following procedure to correctly
adjust the overflow valve:
Close all of the heating circuits that may also be closed during
operation (depending on the type of heat pump usage) so that
the most unfavourable operating state - with respect to the water
flow rate - is achieved. This normally means the heating circuits
of the rooms on the south and west sides of the building. At least
one heating circuit must remain open (e.g. bathroom).
The overflow valve should be opened far enough to produce the
maximum temperature spread between the heating flow and re-
turn flow listed in the following table for the current heat source
temperature. The temperature spread should be measured as
close as possible to the heat pump. The heating element of mono
energy systems should be disconnected.

Summary of Contents for LA 12 PS

Page 1: ...eat Pump for Outdoor Installation Pompe à chaleur air eau pour installation extérieure Montage und Gebrauchsanweisung Deutsch English Français Instructions d installation et d utilisation Installation and Operating Instructions Bestell Nr Order no No de commande 452149 66 19 FD 8703 ...

Page 2: ......

Page 3: ...4 3 3 Wärmepumpenregler D 4 4 Transport D 4 5 Aufstellung D 5 5 1 Allgemein D 5 5 2 Kondensatleitung D 5 6 Montage D 5 6 1 Allgemein D 5 6 2 Heizungsseitiger Anschluss D 5 6 3 Elektrischer Anschluss D 6 7 Inbetriebnahme D 7 7 1 Allgemein D 7 7 2 Vorbereitung D 7 7 3 Vorgehensweise D 7 8 Reinigung Pflege D 8 8 1 Pflege D 8 8 2 Reinigung Heizungsseite D 8 8 3 Reinigung Luftseite D 8 9 Störungen Fehl...

Page 4: ...n einzuhalten ACHTUNG Arbeiten an der Wärmepumpe dürfen nur vom autorisierten und sachkundigen Kundendienst durchgeführt werden Personen insbesondere Kinder die aufgrund ihrer physischen sensorischen oder geistigen Fähigkeiten oder ihrer Unerfahren heit oder Unkenntnis nicht in der Lage sind das Gerät sicher zu benutzen sollten dieses Gerät nicht ohne Aufsicht oder Anwei sung durch eine verantwort...

Page 5: ...hr Wärme Die gewonnene Wärme wird im Verdampfer auf das Arbeitsmedium Kältemittel übertragen Mit Hilfe der elektrisch angetriebenen Verdichter wird die aufge nommene Wärme durch Druckerhöhung auf ein höheres Tempe raturniveau gepumpt und über den Verflüssiger Wärmeaus tauscher an das Heizwasser abgegeben Dabei wird die elektrische Energie eingesetzt um die Wärme der Umwelt auf ein höheres Temperat...

Page 6: ...g bei Funktionsweise und Handhabung des Wärmepumpenreglers sind in der dazu beiliegenden Gebrauchsanweisung beschrie ben 4 Transport ACHTUNG Das Gerät sollte nur in Räumen ohne dauernde Zündquellen aufbewahrt werden ACHTUNG Die Wärmepumpe darf beim Transport nur bis zu einer Neigung von 45 in jeder Richtung gekippt werden Der Transport der Wärmepumpe zum endgültigen Aufstellungs ort sollte im verp...

Page 7: ...e heizungsseitigen Anschlüsse an der Wärmepumpe sind mit 1 Außengewinde versehen Die anzuschließenden Schläuche werden nach unten aus dem Gerät geführt Beim Anschluss an die Wärmepumpe muss an den Übergängen mit einem Schlüssel gegengehalten werden Leerrohre sind nach der Montage an der Wärmepumpe gasdicht zu verschließen Bevor die heizwasserseitigen Anschlüsse der Wärmepumpe er folgen muss die He...

Page 8: ...e pumpe siehe Anhang Geräteinformation sowie der einschlägi gen VDE EN und VNB Vorschriften zu wählen An der Wärmepumpe muss die Leistungszuleitung durch die dafür vorgesehene frei Kabelverschraubung in den Schaltkasten geführt werden Die Leitung ist in ihrer Durchführung fest zu ver schrauben schwadendichte Verschraubung In der Leistungsversorgung für die Wärmepumpe ist eine allpo lige Abschaltun...

Page 9: ...ücklauf ergibt Die Temperaturspreizung ist möglichst nahe an der Wärmepumpe zu messen Bei monoener getischen Anlagen ist der Heizstab zu deaktivieren Störungen während des Betriebes werden ebenfalls am Wärme pumpenregler angezeigt und können wie in der Gebrauchsan weisung des Wärmepumpenreglers beschrieben behoben wer den Bei Außentemperaturen kleiner 10 C und Heizwassertempera turen kleiner als 1...

Page 10: ... um Beschädigungen durch eventuell im System verbliebene Reinigungsmittelreste zu verhindern Die Säuren sind mit Vorsicht anzuwenden und es sind die Vor schriften der Berufsgenossenschaften einzuhalten Im Zweifelsfall ist mit dem Hersteller des Reinigungsmittels Rücksprache zu halten 8 3 Reinigung Luftseite Verdampfer Lüfter und Kondensatablauf sind vor der Heizperi ode von Verunreinigungen Blätte...

Page 11: ...0 W35 2 kW 9 6 4 0 12 1 4 0 18 3 3 7 3 3 Schall Leistungspegel dB A 62 65 74 3 4 Heizwasserdurchfluss bei interner Druckdifferenz m h Pa 1 2 9000 1 4 9000 1 6 9000 3 5 Luftdurchsatz m h Pa 2000 2000 4000 3 6 Kältemittel Gesamt Füllgewicht Typ kg R290 1 0 R290 1 4 R290 2 0 4 Abmessungen Anschlüsse und Gewicht 4 1 Geräteabmessungen H x B x L cm 132 x 77 x 66 113 x 80 x 159 113 x 80 x 199 4 2 Gerätea...

Page 12: ...gene Teile und Geräte Anlagenmängel die auf nicht vom Lieferer bezogene Teile zurückzuführen sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die Nach besserung von uns abgelehnt oder unzumutbar verzögert wird wird der Hersteller entweder kostenfreien Ersatz liefern oder den Minderwert vergüten Im Falle einer Ersatzlieferung behalten wir uns die Gelte...

Page 13: ... Pump Controller E 4 4 Transport E 4 5 Set up E 5 5 1 General Information E 5 5 2 Condensed Water Pipe E 5 6 Installation E 5 6 1 General Information E 5 6 2 Heating System Connection E 5 6 3 Electrical Connection E 6 7 Start up E 6 7 1 General Information E 6 7 2 Preparation E 6 7 3 Procedure E 6 8 Maintenance Cleaning E 7 8 1 Maintenance E 7 8 2 Cleaning the Heating System E 7 8 3 Cleaning the A...

Page 14: ...necting the heating system all applicable regulations must also be adhered to ATTENTION Any work on the heat pump may only be performed by authorised and qualified after sales service technicians Persons especially children who are not capable of operating the device safely due to their physical sensory or mental abilities or their inexperience or lack of knowledge must not operate this device wit...

Page 15: ...at from it This extracted heat is then transferred to the working medium refrigerant in the evaporator The heat is pumped to a higher temperature level by increasing its pressure with the aid of electrically driven compressors It is then transferred to the heating water via the liquifier heat ex changer Electrical energy is used to raise the temperature of the heat in the environment to a higher l...

Page 16: ... together with the neces sary fixing accessories The operating instructions included in the scope of supply of the heat pump controller describe its function and use 4 Transport ATTENTION Never install the device in rooms in which there are any permanent ignition sources ATTENTION When transporting the heat pump ensure that it is not tilted more than 45 in any direction The heat pump should be tra...

Page 17: ...eating System Connection The heating system connections on the heat pump have a 1 ex ternal thread Route the connection hoses out of the device in a downwards di rection Use a spanner to firmly grip the transitions when con necting the heat pump After the heat pump has been installed the ductwork must be sealed so that the connection is gastight Before connecting the heating water system to the he...

Page 18: ...z power supply Connect the controller in compliance with its own operating in structions 16 A fuse The control line not included in scope of supply is connected to the heat pump controller using the two rectangular plug connec tors and the single core wire The plug connector is located on the bottom side of the switch box inside the heat pump More de tailed information can be found in the operatin...

Page 19: ...em cannot be contaminated In the event that operating malfunctions due to contamination still occur the system should be cleaned as described below The device may only be cleaned according to the following instructions from the manufacturer 8 2 Cleaning the Heating System The ingress of oxygen into the heating water circuit may result in the formation of oxidation products rust particularly if ste...

Page 20: ...9 Faults Trouble Shooting This heat pump is a quality product and is designed for trouble free and maintenance free operation In the event that a fault should occur it will be indicated on the heat pump manager dis play Simply consult the Faults and Trouble shooting page in the operating instructions of the heat pump manager If you cannot correct the fault yourself please contact your after sales ...

Page 21: ... 1 3 8 15 8 3 3 at A10 W35 2 kW 9 6 4 0 12 1 4 0 18 3 3 7 3 3 Sound power level dB A 62 65 74 3 4 Heating water flow with an internal pressure differential of m h Pa 1 2 9000 1 4 9000 1 6 9000 3 5 Air flow rate m h Pa 2000 2000 4000 3 6 Refrigerant total filling weight type kg R290 1 0 R290 1 4 R290 2 0 4 Dimensions connections and weight 4 1 Device dimensions H x W x L cm 132 x 77 x 66 113 x 80 x...

Page 22: ...aleur F 4 4 Transport F 4 5 Installation F 5 5 1 Remarques d ordre général F 5 5 2 Ecoulement des condensats F 5 6 Montage F 5 6 1 Remarques d ordre général F 5 6 2 Branchement côté installation de chauffage F 5 6 3 Branchements électriques F 6 7 Mise en service F 6 7 1 Remarques d ordre général F 6 7 2 Préparation F 6 7 3 Procédures à suivre F 6 8 Nettoyage entretien F 7 8 1 Entretien F 7 8 2 Net...

Page 23: ...a pompe à chaleur doivent être effectués uniquement par des techniciens qualifiés et agréés Les personnes en particulier les enfants qui compte tenu de leurs capacités physiques sensorielles ou intellectuelles ou de leur manque d expérience ou de connaissances ne sont pas en mesure d utiliser l appareil en toute sûreté ne devraient pas le faire en l absence ou sans instructions d une personne resp...

Page 24: ... air par extraction de chaleur La chaleur ainsi obtenue est trans mise au fluide utilisé fluide frigorigène dans l évaporateur A l aide d un compresseur à commande électrique la chaleur ab sorbée est pompée à un niveau de température plus élevé par augmentation de pression puis rendue via le condenseur échangeur thermique à l eau de chauffage Il est fait appel à l énergie électrique pour faire pas...

Page 25: ...ces instructions Mode de fonctionnement et utilisation du régulateur de pompe à chaleur sont décrits dans les instructions d utilisation livrées avec l appareil 4 Transport ATTENTION L appareil ne devrait être installé que dans des pièces dépourvues de sources d ignition permanentes ATTENTION Lors du transport l angle d inclinaison de la pompe à chaleur ne doit pas dépasser 45 quel que soit le sen...

Page 26: ...e obturés pour être étanches aux gaz après le montage sur la pompe à chaleur Avant de procéder au raccordement de la pompe à chaleur côté eau de chauffage l installation de chauffage doit être rincée pour éliminer d éventuelles impuretés des restes potentiels de maté riau d étanchéité ou autres et pour empêcher l accumulation de dépôts divers dans le condenseur Un condenseur pollué de cette manièr...

Page 27: ...partie inférieure du boîtier électrique Des instructions plus précises se trouvent dans les instructions d utilisation du ré gulateur de pompe à chaleur Pour des informations plus détaillées cf schémas électriques en annexe 7 Mise en service 7 1 Remarques d ordre général Pour garantir une mise en service en règle cette dernière doit être effectuée par un service après vente agréé par le construc t...

Page 28: ...nctionnements dus à des dépôts dans l échangeur thermique de la pompe à chaleur il faut veiller à ce que l échangeur de chaleur dans l installation de chauffage ne puisse pas s encrasser Si des dysfonctionnements dus à des impuretés devaient se produire malgré cette mesure l installa tion devra être nettoyée comme indiqué ci après Le nettoyage doit être réalisé uniquement suivant les indications d...

Page 29: ...nts Si un dysfonctionnement devait quand même survenir celui ci sera affiché sur l écran du gestionnaire de pompe à chaleur Référez vous pour cela à la page Dysfonctionnements et recherche de pannes dans les ins tructions d utilisation du gestionnaire de pompe à chaleur Si vous n êtes pas en mesure de remédier vous même au dysfonc tionnement veuillez vous adresser au service après vente com pétent...

Page 30: ... 12 1 4 0 18 3 3 7 3 3 Niveau de puissance sonore dB A 62 65 74 3 4 Débit d eau de chauffage avec pression diff int m h Pa 1 2 9000 1 4 9000 1 6 9000 3 5 Débit d air m h Pa 2000 2000 4000 3 6 Fluide frigorigène poids au remplissage total type kg R290 1 0 R290 1 4 R290 2 0 4 Dimensions raccordements et poids 4 1 Dimensions de l appareil H x l x L cm 132 x 77 x 66 113 x 80 x 159 113 x 80 x 199 4 2 R...

Page 31: ... 4 Legende Legend Légende LA 9PS A XI 3 5 Steuerung Control Commande LA 12PS A XII 3 6 Last Load Charge LA 12PS A XIII 3 7 Anschlussplan Circuit Diagram Schéma électrique LA 12PS A XIV 3 8 Legende Legend Légende LA 12PS A XV 3 9 Steuerung Control Commande LA 18PS A XVI 3 10 Last Load Charge LA 18PS A XVII 3 11 Anschlussplan Circuit Diagram Schéma électrique LA 18PS A XVIII 3 12 Legende Legend Lége...

Page 32: ... QVFKOXVV X HQJHZLQGH LU LQOHW LU RXWOHW DEHOOLQJ VWULS 6ZLWFK ER RQGHQVDWH RXWIORZ LQWHUQDO PP HDW IORZ RXWOHW IURP 3 Ö ZDWHU RXWOHW RQQHFWLRQ H WHUQDO WKUHDG QIHHG SRZHU VXSSO 9 3 DQG FRQWURO OLQH HDW UHWXUQ IORZ LQOHW LQ 3 Ö ZDWHU LQOHW RQQHFWLRQ H WHUQDO WKUHDG QWUpH G DLU 6RUWLH G DLU DQGHV GH PDUTXDJH RvWLHU pOHFWULTXH FRXOHPHQW GHV FRQGHQVDWV LQW PP LUFXLW DOOHU GH FKDXIIDJH VRUWLH GH 3 Ö V...

Page 33: ...WHUQDO WKUHDG DEHOOLQJ VWULS 6ZLWFK ER DUHD IRU WKH HOHFWULF FRQQHFWLRQV HDW IORZ RXWOHW IURP 3 RQQHFWLRQ H WHUQDO WKUHDG QIHHG RU IHHGWKURXJK DUHD IRU ZDWHU FRQQHFWLRQ SLSHV KRVHV DQG HOHFWULF VXSSO OHDGV RQGHQVDWH RXWIORZ HYLFH IUDPH VXSSRUWLQJ VXUIDFH IUDPH ZLGWK PP RQ DOO VLGHV 6RUWLH G DLU QWUpH G DLU 2ULILFHV SRXU WXEHV GH WUDQVSRUW LUFXLW UHWRXU GH FKDXIIDJH HQWUpH GDQV 3 5DFFRUG ILOHW H W ...

Page 34: ...WHUQDO WKUHDG DEHOOLQJ VWULS 6ZLWFK ER DUHD IRU WKH HOHFWULF FRQQHFWLRQV HDW IORZ RXWOHW IURP 3 RQQHFWLRQ H WHUQDO WKUHDG QIHHG RU IHHGWKURXJK DUHD IRU ZDWHU FRQQHFWLRQ SLSHV KRVHV DQG HOHFWULF VXSSO OHDGV RQGHQVDWH RXWIORZ HYLFH IUDPH VXSSRUWLQJ VXUIDFH IUDPH ZLGWK PP RQ DOO VLGHV 6RUWLH G DLU QWUpH G DLU 2ULILFHV SRXU WXEHV GH WUDQVSRUW LUFXLW UHWRXU GH FKDXIIDJH HQWUpH GDQV 3 5DFFRUG ILOHW H W ...

Page 35: ...PDWLRQ GH SXLVVDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH ...

Page 36: ...DQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH...

Page 37: ...VDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW G...

Page 38: ...WWH PP OO FURVV VHFWLRQV PP 7RXWHV OHV VHFWLRQV PP 6WHXHUOHLWXQJ PP RQWURO OHDG PP LJQH GH FRPPDQGH PP SRO SROH S OHV lUPHSXPSHQUHJOHU 1 HDW SXPS FRQWUROOHU 1 5pJXODWHXU GH SRPSH j FKDOHXU 1 NHLQH XQNWLRQ EHL 35 HWULHE QR IXQFWLRQ LQ 3 FRQWUROOHU PRGH VDQV IRQFWLRQ HQ FDV GH IRQFWLRQQHPHQW DYHF UpJXODWHXU GH SRPSH j FKDOHXU SRO SROH S OHV ...

Page 39: ...A IX Anhang Appendix Annexes 3 2 3 2 Last Load Charge LA 9PS 1HW 0DLQV 5pVHDX 3 9HUWHLOHU 3 GLVWULEXWRU LVWULEXWHXU 3 ...

Page 40: ...UPHSXPSHQUHJOHU 1 HDW SXPS FRQWUROOHU 1 5pJXODWHXU GH SRPSH D FKDOHXU 1 GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV 9RUVLFKW OHLQVSDQQXQJ DXWLRQ WUD ORZ YROWDJH WWHQWLRQ 7HQVLRQ IDLEOH GHU 1U LVW VWURPORV XQG RKQH XQNWLRQ RUH QR LV GH...

Page 41: ...r Contacteur ventilateur M1 Verdichter Compressor Compresseur M2 Ventilator Ventilator Ventilateur N1 Wärmepumpenregler Heat pump controller Régulateur de pompe à chaleur N7 Sanftanlaufsteuerung Soft start control Commande de démarrage progressif R9 Frostschutzfühler Heizwasser Flow sensor heating water Sonde antigel eau de chauffage X1 Klemmenleiste Lasteinspeisung Terminal strip Incoming supply ...

Page 42: ...P 7RXWHV OHV VHFWLRQV PP 6WHXHUOHLWXQJ PP RQWURO OHDG PP LJQH GH FRPPDQGH PP SRO SROH S OHV lUPHSXPSHQUHJOHU 1 HDW SXPS FRQWUROOHU 1 5pJXODWHXU GH SRPSH j FKDOHXU 1 NHLQH XQNWLRQ EHL 35 HWULHE QR IXQFWLRQ LQ 3 FRQWUROOHU PRGH VDQV IRQFWLRQ HQ FDV GH IRQFWLRQQHPHQW DYHF UpJXODWHXU GH SRPSH j FKDOHXU SRO SROH S OHV ...

Page 43: ...A XIII Anhang Appendix Annexes 3 6 3 6 Last Load Charge LA 12PS 1HW 0DLQV 5pVHDX 3 9HUWHLOHU 3 GLVWULEXWRU LVWULEXWHXU 3 ...

Page 44: ...lUPHSXPSHQUHJOHU 1 HDW SXPS FRQWUROOHU 1 5pJXODWHXU GH SRPSH D FKDOHXU 1 GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV 9RUVLFKW OHLQVSDQQXQJ DXWLRQ WUD ORZ YROWDJH WWHQWLRQ 7HQVLRQ IDLEOH GHU 1U LVW VWURPORV XQG RKQH XQNWLRQ RUH QR LV G...

Page 45: ... Compresseur M2 Ventilator Ventilator Ventilateur N1 Wärmepumpenregler Heat pump controller Régulateur de pompe à chaleur N7 Sanftanlaufsteuerung Soft start control Commande de démarrage progressif R9 Frostschutzfühler Heizwasser Flow sensor heating water Sonde antigel eau de chauffage X1 Klemmenleiste Lasteinspeisung Terminal strip Incoming supply to the load Bornier alimentation de charge X2 Kle...

Page 46: ...P 7RXWHV OHV VHFWLRQV PP 6WHXHUOHLWXQJ PP RQWURO OHDG PP LJQH GH FRPPDQGH PP SRO SROH S OHV lUPHSXPSHQUHJOHU 1 HDW SXPS FRQWUROOHU 1 5pJXODWHXU GH SRPSH j FKDOHXU 1 NHLQH XQNWLRQ EHL 35 HWULHE QR IXQFWLRQ LQ 3 FRQWUROOHU PRGH VDQV IRQFWLRQ HQ FDV GH IRQFWLRQQHPHQW DYHF UpJXODWHXU GH SRPSH j FKDOHXU SRO SROH S OHV ...

Page 47: ...A XVII Anhang Appendix Annexes 3 10 3 10 Last Load Charge LA 18PS 1HW 0DLQV 5pVHDX 3 9HUWHLOHU 3 GLVWULEXWRU LVWULEXWHXU 3 ...

Page 48: ...OHU 1 HDW SXPS FRQWUROOHU 1 5pJXODWHXU GH SRPSH D FKDOHXU 1 lUPHSXPSHQUHJOHU 1 HDW SXPS FRQWUROOHU 1 5pJXODWHXU GH SRPSH D FKDOHXU 1 GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV 9RUVLFKW OHLQVSDQQXQJ DXWLRQ WUD ORZ YROWDJH WWHQWLRQ 7HQ...

Page 49: ...ctor for soft starter Contacteur démarrage progressif K1 2 Zeitrelais Sanftanlauf Time relay for soft starter Relais temporisé démarrage progressif K2 Schütz Ventilatoren Contactor for ventilators Contacteur ventilateurs M1 Verdichter Compressor Compresseur M2 Ventilator 1 Ventilator 1 Ventilateur 1 M4 Ventilator 2 Ventilator 2 Ventilateur 2 N1 Wärmepumpenregler Heat pump controller Régulateur de ...

Page 50: ...A XX Anhang Appendix Annexes 4 4 Hydraulische Prinzipschemen Hydraulic Plumbing Diagram Schéma hydraulique 4 1 Monoenergetische Anlage Mono Energy System Installation monoénergétique ...

Page 51: ...A XXI Anhang Appendix Annexes 4 2 4 2 Monoenergetische Anlage und Warmwasserbereitung Mono Energy System and Domestic Hot Water Preparation Installation monoénergétique et production d eau chaude ...

Page 52: ...A XXII Anhang Appendix Annexes 4 3 4 3 Bivalente Anlage Bivalent System Installation bivalente ...

Page 53: ...rd flexible Wärmepumpe Heat pump Pompe à chaleur Pufferspeicher Buffer tank Réservoir tampon Wärmepumpenregler Heat pump controller Régulateur de pompe à chaleur Elektroverteilung Electrical distribution system Distributeur de courant électrique Warmwasserspeicher Hot water cylinder Réservoir d eau chaude Heizkessel Boiler Chaudière E8 Zusatzheizung Supplementary heating Chauffage d appoint M13 He...

Page 54: ...A XXIV Anhang Appendix Annexes 5 5 Konformitätserklärung Declaration of Conformity Déclaration de conformité ...

Page 55: ...A XXV Anhang Appendix Annexes 5 ...

Page 56: ...tschland GmbH Geschäftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrtümer und Änderungen vorbehalten Subject to alterations and errors Sous réserve d erreurs et modifications 49 0 9221 709 565 www dimplex de ...

Reviews: