IRM – Infrared heaters
Installation on wooden walls is permissible.
The heating device must be installed on a vertical wall
(see illustration). The minimum clearances must be
observed. In addition, a clearance of 400 mm is to be
maintained in front of the unit. All dimensions in mm.
Mark, drill and plug the fixing holes.
Fix the screws with washers into the wall. Allow for
a clearance of up to 4 mm to mount the wall
bracket.
Align the wall bracket as depicted in the illustra
-
tion and mount the heating device in the bracket.
Turn two of the wall brackets by approx. 180° to
act as safety catches.
Tighten the fastening screws on the heating de
-
vice (width across flats 8 mm) and the fastening
screws on the wall (width across flats 10 mm).
Ceiling mounting
The heating device must be installed on a horizontal
ceiling (see illustration). Dimensions x and h are rec
-
ommendations for ensuring a pleasant distribution of
heat and can be adjusted if required (observe the min
-
imum clearances).
3. Electrical connection
The voltage specified on the type plate must match
the line voltage.
It is recommended that a separate electric circuit be
provided for the power supply.
The heating device is designed for fixed connection to
a wall socket. When mounting on a wall, route the de
-
vice connection cable downwards.
The device must only be installed and repaired by a
qualified electrician in accordance with the applicable
safety regulations.
Connection may only take place on securely routed
cables!
A disconnecting device with a contact opening of at
least 3 mm at each pole (e.g. circuit breaker) must be
provided in the installed wiring.
4. Heating operation
NOTE
i
Only use the device for room heating within enclosed
rooms.
Operation of the heating device is only permissible if it
is in conjunction with an external room thermostat
with the following functions:
electronically controlled week programme,
adaptive control of the heating start,
further energy-saving functions.
Please observe the operating instructions for the
room thermostat.
Recommended room thermostat: Dimplex DTB 2R.
200
200
200
200
400
x
h
IRM 320/650 W:
x > 0,6 m, h > 2,5 m
IRM 800/1000 W:
:
x > 1,0 m, h > 3,0 m