www.dimplex.de                                       452168.66.05 · FD 9512

EN-11

English

HPL 9S-TU(R)W - HPL 18S-TU(R)W 

at A-7 / W35

kW / ---

5.5 / 3,3

---

7,2 / 3,2

---

5,6 / 3,3

10,5 / 3,2

at A2 / W35

kW / ---

7,2 / 4,3

---

9,5 / 

4,1(4,3)

11

---

7,3 / 4,3

12,3 / 3,9 

(4,0)

11

at A7 / W35

kW / ---

8,4 / 4,9

---

11,3 / 4,8

---

8,4 / 5,0

at A7 / W45

kW / ---

8,2 / 3,8

---

10,8 / 3,9

---

8,1 / 3,9

at A7 / W55

kW / ---

8,0 / 3,0

---

10,0 / 3,1

---

7,7 / 3,2

at A10 / W35

kW / ---

8,9 / 5,3

---

12,0 / 5,1

---

8,8 / 5,4

1. For air temperatures between -22°C and -5°C, flow temperature increasing from 45? t
2. Operation with 2 compressors
3. Operation with 1 comressor
4. These data indicate the size and capacity of the system according to EN 14511. For an analysis of the economic and energy efficiency of the system, other parameters, in particular

the defrosting capacity and regulation, should also be taken into consideration. These figures are only achieved with clean heat exchangers. Instructions for care, commissioning
and operation can be found in the relevant sections of the installation and operation instructions. The specified values have the following meaning, e.g. A7/W35: outside air tem-
perature 7 °C and heating water flow temperature 35 °C.

5. Standard nominal flow only possible with an electronically controlled circulating pump with actuation via heat pump manager.
6. The heat output and COP is reduced by approx. 5 % in lower operation
7. When the optional weather protection hood (accessory) is used, the sound pressure level in outlet direction is reduced by 3 dB(A).
8. The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
9. See CE declaration of conformity
10.The heat circulating pump and the heat pump manager must always be ready for operation.
11.The coefficient of performance (COP) in partial load operation can be increased by selecting "energy-optimised heating operation" (natural defrosting)

1

Type and order code

HPL 9S-TURW

HPL 12S-TURW

HPL 18S-TURW

2

Design

Heat source

Air

Air

Air

2.1

Model

Reversible with hydro 

tower

Reversible with hydro 

tower

Reversible with hydro 

tower

2.2

Controller

Integrated (hydro tower)

Integrated (hydro tower)

Integrated (hydro tower)

2.3

Installation location  

Haed pump / Hydro tower

Outdoors / Indoors

Outdoors / indoors

Outdoors / indoors

2.4

Thermal energy metering

Integrated

Integrated

Integrated

2.5

Performance levels

1

1

2

3

Operating limits

3.1

Heating water flow / return 

1

°C 

up to 60 ± 2 / from 18

up to 60 ± 2 / from 18

up to 60 ± 2 / from 18

3.2

Air (heating)

°C

-22 to +35

-22 to +35

-22 to +5

2

 / +35

3

3.2

Cooling water flow

°C

+7 to +20

+7 to +20

+7

3

 / +9

2

 to +20

3.3

Air (cooling)

°C

+15 to +45

+15 to +45

+15 to +45

4

Flow

4

 / sound

4.1

Heating water flow heat pump circuit / free compression

Nominal flow in accordance with EN 14511

at A7 / W35...30

m³/h / Pa

1,5 / 41000

1,9 / 18000

1,5 / 40900

at A7 / W45...40 

m³/h / Pa

1,4 / 46000

1,8 / 24000

1,4 / 45900

at A7 / W55...47 

m³/h / Pa

0,9 

5

 / 67000

1,2 

5

 / 55000

1,4 

5

 / 66900

4.2

Minimum heating water flow rate
Heat pump circuit

m³/h / Pa

1,2

1,4

1,4

4.3

Cooling water flow rate / internal pressure differential

Nominal flow in accordance with EN 14511

A35 / W18...23

m³/h / Pa

1,2  / 56000

1,4 / 46000

2,2 / 8100

Minimum cooling water flow rate

m³/h / Pa

1,2 / 56000

1,4 / 46000

1,6 / 36500

4.4

Sound power level according to EN 12102
Normal operation / reduced operation

6

 

7

dB(A)

53 / 53

54 / 53

54 / 53

4.5

Sound pressure level at a distance of 10 m (air outlet side) 

8

Normal operation / reduced operation

6

 

7

dB(A)

25 / 25

26 / 25

26 / 25

4.6

Air flow
Normal operation / reduced operation 

6

m³/h

2700 / 2100

4700 / 3600

5500 / 3200

5

Dimensions, weight and filling quantities

5.1

Device dimensions without connections

H x W x L 

mm

1650 x 910 x 750

1650 x 910 x 750

1650 x 910 x 750

5.2

Device connections for heating

inches

G 1 1/4" external thread

G 1 1/4" external thread

G 1 1/4" external thread

5.3

Weight of the transportable unit(s) incl. packaging

kg

225

265

295

5.4

Refrigerant / total filling weight

type/kg

R410A / 3.9

R410A / 4.78

R410A / 5,9

5.5

Lubricant / total filling quantity

type/litres

Polyolester (POE)/1.2

Polyolester (POE)/1.2

Polyolester (POE)/1.2

5.6

Volume of heating water in device

Litres

2.6

3.8

3.8

Summary of Contents for HPL 12S-TURW

Page 1: ...o Water Heat Pump for Outdoor Installation with hydro tower Pompe chaleur air eau pour installation ext rieure avec tour hydraulique combin e Montage und Gebrauchsanweisung Deutsch English Fran ais In...

Page 2: ......

Page 3: ...Aufstellung DE 6 6 1 Allgemein DE 6 6 2 Kondensatleitung DE 6 7 Montage DE 6 7 1 Allgemein DE 6 7 2 Heizungsseitiger Anschluss DE 7 7 3 Elektrischer Anschluss DE 8 8 Inbetriebnahme DE 8 8 1 Allgemein...

Page 4: ...rbeiten an der W rmepumpe d rfen nur vom autorisierten und sachkundigen Kundendienst durchgef hrt werden 1 2 Bestimmungsgem er Gebrauch Dieses Ger t ist nur f r den vom Hersteller vorgesehenen Ver wen...

Page 5: ...es Verdampfers zu gew hrleisten Die W rmepumpe ist nicht f r den erh hten W rmebedarf w h rend der Bauaustrocknung ausgelegt deshalb muss der zus tz liche W rmebedarf mit speziellen bauseitigen Ger te...

Page 6: ...nem un gemischten Heizkreis ben tigt werden Ein doppelt differenzdruckloser Verteiler in Kombination mit einem Pufferspeicher er gibt eine energetisch optimale hydraulische Einbindung des W rmeerzeuge...

Page 7: ...tlichen Fassadierungsteile abzunehmen Jedes Verkleidungsblech ist mit zwei Schrauben gesichert Nach dem L sen der Schrauben m ssen die Verkleidungsbleche gekippt und aus dem Sockelblech gezogen werden...

Page 8: ...orschriften sind zu beachten ACHTUNG Bei wandnaher Aufstellung sind bauphysikalische Beeinflussungen zu beachten Im Ausblasfeld des Ventilators sollten keine Fenster bzw T ren vorhanden sein ACHTUNG B...

Page 9: ...folgende Richtwerte eingehalten werden HINWEIS Die Hinweise Einstellungen in der Anweisung des W rmepumpenmanagers sind unbedingt zu beachten und dementsprechend vorzunehmen eine Nichtber cksichtigun...

Page 10: ...ikationsunterbrechung mit dem W rmepumpenmana ger auch keine Regelung des 2 W rmeerzeuger m glich HINWEIS Der in der W rmepumpe eingebaute R cklauff hler R2 ist bei laufendem Verdichter aktiv und darf...

Page 11: ...klauf des Verfl ssigers der W rme pumpe anzuschlie en Danach muss mit geeigneten neutralisierenden Mitteln gr ndlich nachgesp lt werden um Besch digungen durch eventuell im System verbliebene Reinigun...

Page 12: ...L mm 1650 x 910 x 750 1650 x 910 x 750 1650 x 910 x 750 5 2 Ger teanschl sse f r Heizung Zoll G 1 1 4 AG G 1 1 4 AG G 1 1 4 AG 5 3 Gewicht der Transporteinheit en incl Verpackung kg 225 265 295 5 4 K...

Page 13: ...rkaufsbezeichnung HPL 9S TURW HPL 12S TURW HPL 18S TURW 2 Bauform W rmequelle Luft Luft Luft 2 1 Ausf hrung Reversibel mit Hydro Tower Reversibel mit Hydro Tower Reversibel mit Hydro Tower 2 2 Regler...

Page 14: ...8 1 3 9 bei A7 W55 kW 8 0 3 0 10 0 3 1 7 7 3 2 bei A10 W35 kW 8 9 5 3 12 0 5 1 8 8 5 4 10 K hlleistung Leistungszahl 4 12 10 1 K hlleistung Leistungszahl EN 14511 EN 14511 EN 14511 Leistungsstufe 1 2...

Page 15: ...ht vom Lieferer bezogene Teile und Ger te Anlagen m ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf h ren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesse...

Page 16: ...DE 14 452168 66 05 FD 9512 www dimplex de Deutsch HPL 9S TU R W HPL 18S TU R W...

Page 17: ...5 6 Installation EN 6 6 1 General EN 6 6 2 Condensate pipe EN 6 7 Assembly EN 6 7 1 General EN 6 7 2 Connection on heating side EN 7 7 3 Electrical connection EN 8 8 Commissioning EN 8 8 1 General EN...

Page 18: ...e device ensure that all circuits are disconnected from the power supply ATTENTION Work on the heat pump must only be performed by authorised and qualified after sales service technicians 1 2 Intended...

Page 19: ...consump tion required when a building is being dried out For this reason the additional heat consumption should be met using special de vices provided by the customer For drying out a building in au t...

Page 20: ...h an unmixed heating circuit A dual differen tial pressureless manifold with a buffer tank allows an energy op timised hydraulic integration of the heat generator and the heat distribution The integra...

Page 21: ...rame it is necessary to remove the two side panel assemblies Each covering panel is secured with two screws After the screws are loosened the pan els must be tilted and pulled out of the kickplate The...

Page 22: ...ION Observe country specific building regulations ATTENTION The physical impacts must be observed for installation close to walls No windows or doors should be present in the area surrounding the air...

Page 23: ...TE The notes settings in the instructions of the heat pump manager must always be observed and carried out accordingly not doing so will lead to malfunctions Minimum heating water flow rate The minimu...

Page 24: ...If a demand sensor is not connected the second heat generator can not be controlled with the heat pump manager in the event of an interruption in communication either NOTE The return sensor R2 instal...

Page 25: ...cuit we recommend connecting the flushing device di rectly to the flow and return of the liquefier of the heat pump It is then important that the system be thoroughly flushed using appropriate neutral...

Page 26: ...al thread G 1 1 4 external thread G 1 1 4 external thread 5 3 Weight of the transportable unit s incl packaging kg 225 265 295 5 4 Refrigerant total filling weight type kg R410A 3 9 R410A 4 78 R410A 5...

Page 27: ...source Air Air Air 2 1 Model Reversible with hydro tower Reversible with hydro tower Reversible with hydro tower 2 2 Controller Integrated hydro tower Integrated hydro tower Integrated hydro tower 2...

Page 28: ...9 5 3 12 0 5 1 8 8 5 4 10 Cooling capacity COP 4 12 10 1 Cooling capacity COP EN 14511 EN 14511 EN 14511 Performance level 1 2 1 2 1 2 at A27 W18 kW 7 9 4 4 8 6 3 7 8 2 4 5 15 4 3 7 at A27 W9 kW 12 7...

Page 29: ...port FR 5 6 Installation FR 6 6 1 G n ralit s FR 6 6 2 Conduite d coulement des condensats FR 6 7 Montage FR 6 7 1 G n ralit s FR 6 7 2 Raccordement c t chauffage FR 7 7 3 Branchements lectriques FR 8...

Page 30: ...ectriques sont bien hors tension ATTENTION Les travaux sur la pompe chaleur doivent tre effectu s uniquement par un SAV qualifi et agr 1 2 Utilisation conforme Cet appareil ne doit tre employ que pour...

Page 31: ...fonctionnement continu pour garantir un d givrage optimal de l vaporateur La pompe chaleur n tant pas con ue pour le besoin en cha leur lev requis pour le s chage d une construction celui ci devra tre...

Page 32: ...chaleur jusqu sa distribution Un distributeur double sans pression diff rentielle combin un ballon tampon permet une int gration hydraulique optimale en terme d nergie du g n rateur de chaleur et de...

Page 33: ...trous de transport dans le ch ssis il est n ces saire de retirer les deux panneaux d habillage lat raux Chaque panneau d habillage est fix l aide de deux vis Apr s avoir des serr les vis incliner les...

Page 34: ...s d un mur tenir compte des influences physiques sur la construction Aucune porte ou fen tre ne doit se trouver dans le champ d vacuation du ventilateur ATTENTION En cas d installation pr s d un mur l...

Page 35: ...nelle doivent tre respect es selon VDI2035 feuillet1 1 dH 1 7857 f REMARQUE Il est imp ratif de suivre les remarques et consignes et d effectuer en cons quence les r glages mentionn s dans les instruc...

Page 36: ...Sans raccordement de la sonde de demande la r gulation du deuxi me g n rateur de chaleur devient impossible en cas de coupure de la communication avec le gestionnaire de pompe chaleur REMARQUE La sond...

Page 37: ...ndons de raccorder l appareil de nettoyage directement sur le d part et le retour du condenseur de la pompe chaleur Il faut ensuite soigneusement rincer la tuyauterie l aide de pro duits neutralisants...

Page 38: ...en mm 1650x910x750 1650x910x750 1650x910x750 5 2 Raccordements de l appareil pour le chauffage pouces Filet ext 1 1 4 Filet ext 1 1 4 Filet ext 1 1 4 5 3 Poids de des unit s de transport emballage com...

Page 39: ...n du coefficient de performance en charge r duite avec la s lection de l option Mode chauffage consommation nerg tique optimis e d givrage naturel 1 D signation technique et r f rence de commande HPL...

Page 40: ...0 11 pour A7 W35 kW 8 4 4 9 11 3 4 8 8 4 5 0 pour A7 W45 kW 8 2 3 8 10 8 3 9 8 1 3 9 pour A7 W55 kW 8 0 3 0 10 0 3 1 7 7 3 2 pour A10 W35 kW 8 9 5 3 12 0 5 1 8 8 5 4 10 Puissance de rafra chissement c...

Page 41: ...agrams Sch mas d integration hydraulique A X 3 1 Monoenergetische W rmepumpenheizungsanlage mit einem Heizkreis Puffer und Warmwasserspeicher Mono energy heat pump heating system with one heating circ...

Page 42: ...PLQDQWV HQ FDV G LQVWDOODWLRQ VXU HPSODFHPHQW GpJDJp HL ZDVVHUYRUODXI XVJDQJ DXV lUPHSXPSH X HQJHZLQGH HL ZDVVHUU FNODXI LQJDQJ LQ lUPHSXPSH X HQJHZLQGH XUFKI KUXQJVEHUHLFK OHNWUROHLWXQJHQ XUFKI KUXQJ...

Page 43: ...SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH LQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH...

Page 44: ...RQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ...

Page 45: ...RQ GH SXLVVDQFH LQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU...

Page 46: ...FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ...

Page 47: ...XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH LQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3...

Page 48: ...SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ L...

Page 49: ...H LQOHW WHPSHUDWXUH 7HPSpUDWXUH G HQWUpH GH OD VRXUFH GH FKDOHXU t t t t s D d 9HUGLFKWHUEHWULHE FRPSUHVVRU PRGH RQFWLRQHPHQW j FRPSUHVVHXU 9HUGLFKWHUEHWULHE FRPSUHVVRU PRGH RQFWLRQHPHQW j FRPSUHVVHXU...

Page 50: ...WXUH 7HPSpUDWXUH G HDX GH UDIUDvFKLVVHPHQW lUPHVHQNHQHLQWULWWVWHPSHUDWXU HDW VLQN LQOHW WHPSHUDWXUH 7HPSpUDWXUH G HQWUpH GH GLVVLSDWLRQ WKHUPLTXH 9HUGLFKWHUEHWULHE FRPSUHVVRU PRGH RQFWLRQHPHQW j FRPSU...

Page 51: ...ue 3 1 Monoenergetische W rmepumpenheizungsanlage mit einem Heizkreis Puffer und Warmwasserspeicher Mono energy heat pump heating system with one heating circuit buffer tank and hot water cylinder Ins...

Page 52: ...rgetische W rmepumpenheizungsanlage mit einem Heizkreis Puffer und Warmwasserspeicher Electical circuit diagram for a mono energy system with one heating circuits buffer tank and hot water cylinder Sc...

Page 53: ...ise Puffer und Warmwasserspeicher Mono energy heat pump heating system with three heating circuits buffer tank and hot water cylinder Installation de chauffage par pompe chaleur mono nerg tique avec t...

Page 54: ...etische W rmepumpenheizungsanlage mit drei Heizkreise Puffer und Warmwasserspeicher Electical circuit diagram for a mono energy system with three heating circuits buffer tank and hot water cylinder Sc...

Page 55: ...ager Gestionnaire de pompe chaleur E10 1 Tauchheizk rper Immersion heater R sistance immerg e M13 Heizungsumw lzpumpe Hauptkreis Heat circulating pump for main circuit Circulateur de chauffage circuit...

Page 56: ...pumps D signation Pompes chaleur Typ en HPL 9S TUW Type s HPL 12S TUW Type s HPL 18S TUW HPL 9S TURW HPL 12S TURW HPL 18S TURW EG Richtlinien Niederspannungsrichtlinie 2006 95 EG EMV Richtlinie 2004...

Page 57: ...www dimplex de 452168 66 05 FD 9512 A XVII Anhang Appendix Annexes HPL 9S TU R W HPL 18S TU R W...

Page 58: ...A XVIII 452168 66 05 FD 9512 www dimplex de Anhang Appendix Annexes HPL 9S TU R W HPL 18S TU R W...

Page 59: ...www dimplex de 452168 66 05 FD 9512 A XIX Anhang Appendix Annexes HPL 9S TU R W HPL 18S TU R W...

Page 60: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...