Dimplex DCP7W Instruction Manual Download Page 8

• 

Decommissioning

 

Before carrying out this procedure, it is essential that the technician is completely 
familiar with the equipment and all its detail. It is recommended good practice that all 
refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant 
sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. 
It is essential that electrical power is available before the task is commenced.

a) Become familiar with the equipment and its operation.    
b) Isolate system electrically.    
c) Before attempting the procedure ensure that: Mechanical handling equipment 
is available, if required, for handling refrigerant cylinders; All personal protective 
equipment is available and being used correctly; The recovery process is supervised 
at all times by a competent person; Recovery equipment and cylinders conform to the 
appropriate standards.    
d) Pump down refrigerant system, if possible.    
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed 
from various parts of  the system.     
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer's 
instructions.    
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).    
i)  Do not exceed the maximum working pressure of the cylinder, even temporarily.     
j)  When the cylinders have been filled correctly and the process completed, make sure 
that the cylinders and the equipment are removed from site promptly and all isolation 
valves on the equipment are closed off.     
k) Recovered refrigerant shall not be charged into another refrigeration system unless 
it has been cleaned and checked.

• 

Labelling

 

Equipment shall be labelled stating that it has been de-commissioned and emptied 
of refrigerant. The label shall be dated and signed. Ensure that there are labels on the 
equipment stating the equipment contains flammable refrigerant.

• 

Recovery

 

When removing refrigerant from a system, either for servicing or decommissioning, it is 
recommended good practice that all refrigerants are removed safely. When transferring 
refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders 
are employed. Ensure that the correct number of cylinders for holding the total system 
charge is available. All cylinders to be used are designated for the recovered refrigerant 
and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). 
Cylinders shall be complete with pressure relief valve and associated shut-off valves in 
good working order. Empty recovery cylinders are evacuated and, if possible, cooled 
before recovery occurs. The recovery equipment shall be in good working order with 
a set of instructions concerning the equipment that is at hand and shall be suitable 
for the recovery of flammable refrigerants. In addition, a set of calibrated weighing 
scales shall be available and in good working order. Hoses shall be complete with leak-
free disconnect couplings and in good condition. Before using the recovery machine, 
check that it is in satisfactory working order, has been properly maintained and that 
any associated electrical components are sealed to prevent ignition in the event of a 
refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be 
returned to the refrigerant supplier in the correct recovery cylinder, and the relevant 
Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially 
not in cylinders. If compressors or compressor oils are to be removed, ensure that they 
have been evacuated to an acceptable level to make certain that flammable refrigerant 
does not remain within the lubricant. The evacuation process shall be carried out prior to 
returning the compressor to the suppliers. Only electric heating to the compressor body 
shall be employed to accelerate this process. When oil is drained from a system, it shall 
be carried out safely.

8

Summary of Contents for DCP7W

Page 1: ...For domestic household use only INSTRUCTION MANUAL Portable Air Conditioner Model DCP7W...

Page 2: ...ter leakage Ensure that the unit is kept upright at all times Do not place on soft unstable or non horizontal angled surfaces Never operate the appliance if a cable or connector has been damaged after...

Page 3: ...interference Keep the unit at least 1 metre away from electrical appliances such as televisions radios The air conditioner must always be stored and transported upright In case of doubt we suggest you...

Page 4: ...formation presented on the appliance Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer The appliance shall NOT be stored in a room with...

Page 5: ...performed General work area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out Work in confined spaces shall be avoided The area aro...

Page 6: ...to avoid possibility of sparking That there no live electrical components and wiring are exposed while charging recovering or purging the system That there is continuity of earth bonding Repairs to se...

Page 7: ...ant circuit to make repairs or for any other purpose conventional procedures shall be used However it is important that best practice is followed since flammability is a consideration The following pr...

Page 8: ...nt stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good practice that all refrigerants a...

Page 9: ...tension lead may become overloaded Where there is risk of fire or close to a naked flame Where the power cable may be damaged On a slope or uneven surface Where it may be damaged by chemicals If there...

Page 10: ...Minimum Lo 51dB A Noise Level Maximum Hi 62dB A Air Volume Lo Hi 211 272 Refrigerant R290 Fan speeds 2 Modes Cool Fan Dry Timer 24 hours Dimensions w x d x h 329 x 318 x 634mm Min room size 8m2 Max ro...

Page 11: ...er 9 Upper air intake 10 Drain outlet 11 Air outlet 12 Lower air intake 13 Bottom tray drain outlet 1 2 3 4 5 6 7 8 9 10 11 12 13 front rear Note All the illustrations in the manual are for explanatio...

Page 12: ...se and increase buttons Used to adjust increasing decreasing temperature settings in 1 C 2 F or 1 F increments in a range of 17 C 62 F to 30 C 88 F or 86 F NOTE The control is capable of displaying te...

Page 13: ...nit if the malfunction is still present turn off the unit and unplug the power cord Contact the manufacturer or its service agents or a similar qualified person for service Remote Control I SENSE 1 3...

Page 14: ...NO display High speed Medium speed some units Low speed Auto fan speed AUTO COOL HIGH MED LOW DRY HEAT AUTO HEAT COOL FAN DRY Mode display Fan speed indication FAN HIGH MED LOW Displayed when TIMER ON...

Page 15: ...t you install your unit on an even surface to minimize noise and vibration The unit must be installed near a sufficient power outlet and if using a continuous drainage method then the plug areas shoul...

Page 16: ...daptor and unit adaptor clamp automatically by the elastic buckles of the adaptors Unit adaptor Window slider adaptor Exhaust hos e Exhaust hose assembly Type window installation Model A Model B Windo...

Page 17: ...e Preparing the adjustable window slider 1 Choose the window sliders according the size of your window If the sliders need to be cut to meet the window size please take extra care to cut it properly 2...

Page 18: ...W KIT INSTALLATION MODEL B Bolt 1 2 1 2 3 Bolt Bolt 1 2 3 4 Bolt Bolt Bolt Bolt 1 4 Window Slider s After assembl y Before assembl y MODEL C Bolt Bolt 1 2 1 2 3 Bolt Window Slider s After assembl y Be...

Page 19: ...o the window opening between the glass and the window frame to prevent air and insects from getting into the room 3 Cut the non adhesive foam seal C strip to match the width or height of the window In...

Page 20: ...NOTE Cover the hole using the adaptor cap when not in use Wall Exhaust Expansion anchor positio n Adaptor B Adaptor cap Note To ensure proper function DO NOT overextend or bend the hose Make sure that...

Page 21: ...d Buckle O N O F F T E M P S H CO U R TT T O I M NE R T O I M FE FR M O D E FA N S LE E P S W I N G LE D 1 set 1 pc Window Slider B Remote Controller and Battery only for remote control models 1 pc Wa...

Page 22: ...eed Note Under AUTO mode both the AUTO mode and the actual operation mode indicator lights illuminate for some models HEAT operation cooling only models without Press the MODE button until the HEAT in...

Page 23: ...mode and the unit will continue to operate as originally programmed Note This feature is unavailabe under FAN or DRY mode FOLLOW ME TEMP SENSING feature on some models This feature can ONLY be activa...

Page 24: ...ure the unit will automatically quit the power management feature The compressor and or fan motor will run Water Drainage Remove the drain plug Continuous drain hose Note Make sure the hose is secure...

Page 25: ...s will immediately stop However the fan motor will continue to operate this is normal Carefully move the unit to a drain location remove the bottom drain plug and let the water drain away Reinstall th...

Page 26: ...timal performance The water collection tray should be drained immediately after P1 error occurs and before storage to prevent mould In households with animals you will have to periodically wipe down t...

Page 27: ...e Ask for advice by calling your local after sales service agent or the Customer Care Centre on 1300 556 816 AU 0800 666 2824 NZ Maintenance Recycling Do not dispose of electrical appliances as unsort...

Page 28: ...com au Supplied by Glen Dimplex Australia 8 Lakeview Drive Scoresby Victoria 3179 Glen Dimplex Australia All rights reserved Material contained in this publication may not be reproduced in whole or i...

Reviews: