Dimplex DCP7W Instruction Manual Download Page 7

• 

Cabling

 

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, 
sharp edges or any other adverse environmental effects. The check shall also take into 
account the effects of aging or continual vibration from sources such as compressors or 
fans.

• 

Detection of flammable refrigerants

 

Under no circumstances shall potential sources of ignition be used in the searching for or 
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) 
shall not be used.

• 

Leak detection methods

 

The following leak detection methods are deemed acceptable for systems containing 
flammable refrigerants. Electronic leak detectors shall be used to detect flammable 
refrigerants, but the sensitivity may not be adequate, or may need re-calibration. 
(Detection equipment shall be calibrated in a  refrigerant-free area.) Ensure that the 
detector is not a potential source of ignition and is suitable for the refrigerant used. Leak 
detection equipment shall be set at a percentage of the LFL of the refrigerant  and shall 
be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % 
maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants 
but the use of detergents containing chlorine shall be avoided as the chlorine may react 
with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked 
flames shall be removed/ extinguished. If a leakage of refrigerant is found which requires 
brazing, all of the refrigerant shall be recovered from the system, or isolated (by means 
of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen 
(OFN) shall then be purged through the system both before and during the brazing 
process.

• 

Removal and evacuation

 

When breaking into the refrigerant circuit to make repairs or for any other purpose 
conventional procedures shall be used. However, it is important that best practice is 
followed since flammability is a consideration. The following procedure shall be adhered 
to: Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert 
gas; Open the circuit by cutting or brazing. 
The refrigerant charge shall be recovered into the correct recovery cylinders. The system 
shall be flushed with OFN to render the unit safe. This process may need to be repeated 
several times. Compressed air or oxygen shall not be used for this task. Flushing shall be 
achieved by breaking the vacuum in the system with OFN and continuing to fill until the 
working pressure is achieved, then venting to atmosphere, and finally pulling down to a 
vacuum. This process shall be repeated until no refrigerant is within the system. When 
the final OFN charge is used, the system shall be vented down to atmospheric pressure 
to enable work to take place. This operation is absolutely vital if brazing operations on 
the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close 
to any ignition sources and there is ventilation available.

• 

Charging procedures

 

In addition to conventional charging procedures, the following requirements shall be 
followed. Ensure  that contamination of different refrigerants does not occur when using 
charging equipment. Hoses or lines shall be as short as possible to minimise the amount 
of refrigerant contained in them. 
Cylinders shall be kept upright. 
Ensure that the refrigeration system is earthed prior to charging the system with 
refrigerant. 
Label the system when charging is complete (if not already). 
Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging 
the system it shall be pressure tested with OFN. The system shall be leak tested on 
completion of charging but prior to commissioning. A follow up leak test shall be carried 
out prior to leaving the site.

7

Summary of Contents for DCP7W

Page 1: ...For domestic household use only INSTRUCTION MANUAL Portable Air Conditioner Model DCP7W...

Page 2: ...ter leakage Ensure that the unit is kept upright at all times Do not place on soft unstable or non horizontal angled surfaces Never operate the appliance if a cable or connector has been damaged after...

Page 3: ...interference Keep the unit at least 1 metre away from electrical appliances such as televisions radios The air conditioner must always be stored and transported upright In case of doubt we suggest you...

Page 4: ...formation presented on the appliance Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer The appliance shall NOT be stored in a room with...

Page 5: ...performed General work area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out Work in confined spaces shall be avoided The area aro...

Page 6: ...to avoid possibility of sparking That there no live electrical components and wiring are exposed while charging recovering or purging the system That there is continuity of earth bonding Repairs to se...

Page 7: ...ant circuit to make repairs or for any other purpose conventional procedures shall be used However it is important that best practice is followed since flammability is a consideration The following pr...

Page 8: ...nt stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good practice that all refrigerants a...

Page 9: ...tension lead may become overloaded Where there is risk of fire or close to a naked flame Where the power cable may be damaged On a slope or uneven surface Where it may be damaged by chemicals If there...

Page 10: ...Minimum Lo 51dB A Noise Level Maximum Hi 62dB A Air Volume Lo Hi 211 272 Refrigerant R290 Fan speeds 2 Modes Cool Fan Dry Timer 24 hours Dimensions w x d x h 329 x 318 x 634mm Min room size 8m2 Max ro...

Page 11: ...er 9 Upper air intake 10 Drain outlet 11 Air outlet 12 Lower air intake 13 Bottom tray drain outlet 1 2 3 4 5 6 7 8 9 10 11 12 13 front rear Note All the illustrations in the manual are for explanatio...

Page 12: ...se and increase buttons Used to adjust increasing decreasing temperature settings in 1 C 2 F or 1 F increments in a range of 17 C 62 F to 30 C 88 F or 86 F NOTE The control is capable of displaying te...

Page 13: ...nit if the malfunction is still present turn off the unit and unplug the power cord Contact the manufacturer or its service agents or a similar qualified person for service Remote Control I SENSE 1 3...

Page 14: ...NO display High speed Medium speed some units Low speed Auto fan speed AUTO COOL HIGH MED LOW DRY HEAT AUTO HEAT COOL FAN DRY Mode display Fan speed indication FAN HIGH MED LOW Displayed when TIMER ON...

Page 15: ...t you install your unit on an even surface to minimize noise and vibration The unit must be installed near a sufficient power outlet and if using a continuous drainage method then the plug areas shoul...

Page 16: ...daptor and unit adaptor clamp automatically by the elastic buckles of the adaptors Unit adaptor Window slider adaptor Exhaust hos e Exhaust hose assembly Type window installation Model A Model B Windo...

Page 17: ...e Preparing the adjustable window slider 1 Choose the window sliders according the size of your window If the sliders need to be cut to meet the window size please take extra care to cut it properly 2...

Page 18: ...W KIT INSTALLATION MODEL B Bolt 1 2 1 2 3 Bolt Bolt 1 2 3 4 Bolt Bolt Bolt Bolt 1 4 Window Slider s After assembl y Before assembl y MODEL C Bolt Bolt 1 2 1 2 3 Bolt Window Slider s After assembl y Be...

Page 19: ...o the window opening between the glass and the window frame to prevent air and insects from getting into the room 3 Cut the non adhesive foam seal C strip to match the width or height of the window In...

Page 20: ...NOTE Cover the hole using the adaptor cap when not in use Wall Exhaust Expansion anchor positio n Adaptor B Adaptor cap Note To ensure proper function DO NOT overextend or bend the hose Make sure that...

Page 21: ...d Buckle O N O F F T E M P S H CO U R TT T O I M NE R T O I M FE FR M O D E FA N S LE E P S W I N G LE D 1 set 1 pc Window Slider B Remote Controller and Battery only for remote control models 1 pc Wa...

Page 22: ...eed Note Under AUTO mode both the AUTO mode and the actual operation mode indicator lights illuminate for some models HEAT operation cooling only models without Press the MODE button until the HEAT in...

Page 23: ...mode and the unit will continue to operate as originally programmed Note This feature is unavailabe under FAN or DRY mode FOLLOW ME TEMP SENSING feature on some models This feature can ONLY be activa...

Page 24: ...ure the unit will automatically quit the power management feature The compressor and or fan motor will run Water Drainage Remove the drain plug Continuous drain hose Note Make sure the hose is secure...

Page 25: ...s will immediately stop However the fan motor will continue to operate this is normal Carefully move the unit to a drain location remove the bottom drain plug and let the water drain away Reinstall th...

Page 26: ...timal performance The water collection tray should be drained immediately after P1 error occurs and before storage to prevent mould In households with animals you will have to periodically wipe down t...

Page 27: ...e Ask for advice by calling your local after sales service agent or the Customer Care Centre on 1300 556 816 AU 0800 666 2824 NZ Maintenance Recycling Do not dispose of electrical appliances as unsort...

Page 28: ...com au Supplied by Glen Dimplex Australia 8 Lakeview Drive Scoresby Victoria 3179 Glen Dimplex Australia All rights reserved Material contained in this publication may not be reproduced in whole or i...

Reviews: