Dimplex AWP 300 LW Installation And Operating Manual Download Page 12

Page 12 of 

20

 

8.3 

Sacrificial Anode 

 

The sacrificial anode rod installed in the hot water tank for corrosion protection purposes must be checked 
electrically on a regular basis - at least every two years - after commissioning and be replaced, if neces-
sary. The electrical check is to be conducted by means of a suitable ammeter without draining the water in 
the tank.  

 

 

Procedure: 

 
 

n

 

Withdraw PE conductor from tab of sacrificial anode. 

 

o

 

Connect ammeter (0...50 mA) between PE conductor and tab. 

 

p

 

Evaluation of wear of sacrificial anode: 

 

 

 

Measured value > 1 mA  

 sacrificial anode is okay. 

 

 

 

Measured value < 1 mA  

 sacrificial anode must be checked or replaced. 

 
If an unambiguous electrical check is not possible, we recommend that a visual inspection of the sacrificial 
anode be performed. For a replacement of the sacrificial anode that may be necessary [to be performed by a 
qualified technician], the water must be drained from the storage tank via the drain valve (to be provided upon 
installation – see appendix.  
 
Caution: Sacrificial anodes that are impaired in their function will reduce the life of the unit!  
 

 
 
 
 

9. 

Malfunctions / Troubleshooting 

 

( intended for the user )

 

 
Caution! 

Work on the heat pump water heater may only be performed by qualified persons! 
Accident prevention regulations must be adhered to!

 

 
Heat pump fails to run! 
 

Please check that  
 

Ö

Ö

Ö

Ö

 

the plug is plugged in  

 

Ö

Ö

Ö

Ö

 

the power switch is switched on  

 

Ö

Ö

Ö

Ö

 

voltage is present at the wall outlet 

 

Ö

Ö

Ö

Ö

 

the air intake temperature is 

 8°C  

 

Ö

Ö

Ö

Ö

 

the heat pump was not switched off by the thermostat  

 

Ö

Ö

Ö

Ö

 

the hot water temperature has not reached or exceeded 55°C 

 

Heat pump switches off prematurely

 (setpoint temperature has not been reached yet) 

 
Please check whether  
 

 

 

       

Ö

Ö

Ö

Ö

      ventilation ducts are kinked or their openings closed, or  

    air filters that may be provided are severely contaminated (clogged)

 

 

Condensate fails to drain 

water present at or under the unit

  

 

Please check whether 

Ö

Ö

Ö

Ö

 

the sealing lip valve at the end of the condensate hose is contaminated or 
clogged; clean it, necessary. The valve can be easily removed and rein-
stalled. 

Ö

Ö

Ö

Ö

#

#

#

#

the air supply / air discharge rate is greatly reduced  
(kinked airduct / clogged air filter) 

 
If the malfunction cannot be corrected based on the above questions, please consult your installer or 
customer service. 

Summary of Contents for AWP 300 LW

Page 1: ...451901 67 19 FD8405 Installation and Operating Manual Heat Pump Water Heater with Sheet Metal Cabinet Airduct Connection and Supplementary Heat Exchanger AWP 300 LW...

Page 2: ...ter Piping 9 6 2 Connection of Condensate Line 9 6 3 Electrical Connection 9 6 3 1 Opening the Cabinet 10 7 Commissioning 10 7 1 Hot Water Circuit 10 7 1 1 Hot Water Circuit Requirements 10 7 1 2 Comm...

Page 3: ...e ready for connection and essentially consists of a domestic water tank the components of the refrigeration air and water circuits as well as all control regulating and monitoring devices required fo...

Page 4: ...d part of the heat of the compressor motor is transferred to the water Subsequently the high condensing pressure is reduced by means of a throttling device expansion valve to the level of the evaporat...

Page 5: ...located in the well of the immersion heater When the preset switching value 99 C is exceeded the immer sion heater is switched off The immersion heater cannot be restarted unless the hot water tempera...

Page 6: ...ging pump of an additional heat ex changer to be activated via the Heat exchanger relay output In this case the Heat exchanger switch must be in the On position 3 4 Immersion Heater Switch The integra...

Page 7: ...ransport over short distances and provided due care is exercised an inclination angle of up to 45 is permitted Both during transport and storage ambient temperatures of 20 to 70 C are permissible 4 1...

Page 8: ...ly by means of insulated airducts NW 160 which must not exceed a total length of 10 m If the ceiling is lower and no airducts are used an air ducting elbow 90 NW 160 must be used on the outlet air sid...

Page 9: ...ithout pressure is provided which must also be relocated when the condensate hose is shortened valve can be easily removed and reinstalled on the hose 6 3 Electrical Connection The HPWH is pre wired r...

Page 10: ...ise and remove 4 To remove the bottom front panel 4 only required for checking the sacrificial anode or the immersion heater it suffices to loosen the lower two fastening screws d and to slide the bot...

Page 11: ...may still be rotating General No maintenance activities need to be performed on the refrigeration circuit of the heat pump For cleaning the HPWH simply use a damp cloth and some soapy water Caution D...

Page 12: ...es that are impaired in their function will reduce the life of the unit 9 Malfunctions Troubleshooting intended for the user Caution Work on the heat pump water heater may only be performed by qualifi...

Page 13: ...dhered to when repairing or decommissioning the HPWH 12 Appendix 12 1 Refrigeration Cycle with Legend 1 Compressor 8 Temperature control heat pump 15 Evaporator 2 Pressostat HP 9 Safety temperature li...

Page 14: ...2 2 2 Heat Exchanger Plumbing Diagram Example Thermal Solar System Heat exchanger flow Heat exchanger return hot water heating water supply circulation if required heating water return cold water conn...

Page 15: ...K4 M 1 M 2 S1 S2 S3 X1 X2 X3 X5 Legende 2 S1 1 T B1 2 27 55 C Verdichter Ventilator X5 6 X5 7 Pot freier Kontakt f r Heizstabanst 230V AC m in 8A PE 4 5 A2 A1 K1 11 14 X5 2 1 S3 K4 11 14 K4 A1 A2 5 H1...

Page 16: ...C Watt 550 Average heat output 1 at 45 C Watt 1830 COP t as per EN 255 at 45 C 3 4 Sound pressure level 3 dB A 53 Air flow rate m3 h 450 External pressure Pa 100 Maximum airduct connection length tota...

Page 17: ......

Page 18: ...Page 18 of 20...

Page 19: ...Page 19 of 20...

Page 20: ...Page 20 of 20 KKW Kulmbacher Klimager te Werk GmbH Subject to technical modifications Division Dimplex Fax 0 92 21 709 589 Am Goldenen Feld 18 www dimplex de D 95326 Kulmbach...

Reviews: