HEaTER LVC RELaY - 1 pH paRaLLEL
L3
7106222500
L3
L2
L1
7106223000
HEaTER No CoNTRoLs - 3 pH DELTa
L1
ELEmENT
L2
ELEmENT
HEaTER 3 poLE CoNTaCToR/TX - 3 pH DELTa
ELEmENT
HEaTER 2 poLE sTaT - 1 pH paRaLLEL
L2
7106222200
L2
L2
L1
HEaTER No CoNTRoLs - 1 pH paRaLLEL
ELEmENT
L1
L1
7106222700
L2
L1
ELEmENT
ELEmENT
7106224000
7106223500
L3
L1
HEaTER 3 poLE CoNTaCToR - 3 pH DELTa
L2
7106223700
7106223200
HEaTER LVD RELaY - 1 pH paRaLLEL
a
B
sTaT
L1
L2
T1
T2
T2
T1
L1
L2
ELEmENT
a
T2
T1
C
L1
L2
L3
T1
ELEmENT
T2
24V
24V
CoNTaCToR
sTaT
L3
L2
L1
L1 L2 L3
LimiT CoNTRoL
RETuRN WiREs
RELaY
LimiT CoNTRoL
RETuRN WiREs
RETuRN WiREs
RETuRN WiREs
LimiT CoNTRoL
LimiT CoNTRoL
RELaY
LimiT CoNTRoL
LimiT CoNTRoL
RETuRN WiREs
RETuRN WiREs
LimiT CoNTRoL
LimiT CoNTRoL
RETuRN WiREs
RETuRN WiREs
CoNTaCToR
C
HEaTER c/w 2 or 3 poLE sTaT - 3 pH DELTa
www.dimplex.com
2
Wiring Diagrams
wall to keep the heater level.
!
nOTe:
Should the wall surface be uneven, secure
the heater back panel to the high spots. This will avoid a
distorted appearance.
proceed to the wiring instructions.
5.
Floor installation
Unpack the heater and pedestal(s) from the carton( the
1.
pedestals are packed at the end of the carton) .
Remove the front panel and terminal box covers.
2.
!
nOTe:
The front panel screws are recessed in the
bottom louvers at each end of the heater.
Remove the desired knockouts from the terminal box
3.
area.
!
nOTe:
it is only necessary to remove the knockout(s)
that will feed the power supply wiring, keeping in mind
the heater mounting location and supply wire location on
the wall.
Temporarily secure a pedestal to each end of the heater
4.
bottom.
!
nOTe:
Units longer than 4 feet will be provided with 3
or more pedestals. The extra pedestals should be used
to support the middle of the heater.
place the heater in the desired location and mark the
5.
position of the pedestal base on the floor.
Remove the pedestal base(s) from the heater and
6.
secure to the floor within the marked areas with suitable
fasteners. (provided by the customer)
place the heater on the pedestal base and tighten all
7.
fasteners.
proceed to wiring instructions.
8.
Wiring instructions
Recommended minimum supply wire sizes are listed in the
table below:
mAximum WATTS per circuiT uSinG 75 °c Wire
(cOpper Wire)
Rough in
Wire size 120V 208V 240V 277V 347V 480V
600V
14
1440
2496
2880 3324
4164 5760
7200
12
1920
3328 3840 4432
5552 7680
9600
10
2880
4992 5760 6648
8328
11520
14400
Run branch circuit wiring of proper voltage and wire size
1.
to the location of the terminal box of the heater. (See
Chart)
!
nOTe:
supply wire entry is
commonly made into one heater.
Through wiring (factory furnished)
can be used for connection to
adjacent heaters.
Wire all heaters and controls in
2.
accordance with the appropriate
wiring diagram.
!
nOTe:
sample wiring diagrams
beside.
Wrap the supply ground wire
3.
around the green painted ground
screw & tighten.
!
nOTe:
When heaters are mounted
end to end, remove the finished
end plate, install a chase nipple
and locknut in the terminal box to
ensure grounding continuity and to
protect the wiring.
Where headers are spaced apart,
remove the finishing end plate, and use
rigid conduit (provided by customer) for
through wiring and ground continuity.
Do not exceed the allowable number
of conductors allowed by the National
Electric Code.
Do a final and complete check of all
4.
wiring then replace the terminal box
covers being careful not to pinch
any wires.
The front panel may now be
5.
installed.