34
(Humid Band 0.0 %)
Set the humidity range, that is, the deviation of the
humidity set point, to ensure that there is a deviation between the starting
and stopping humidity point of the equipment, and it will not stop frequently
during the partial load. When setting the humidity range, it is compatible
with frequent start-stop and allowable humidity fluctuations.
(Heat on band 0.0 °C)
Set the heating opening deviation, that is to achieve
the temperature deviation after the basic conditions of heating.
(Heat off band 0.0 °C)
Set the heat closing deviation, that is, to meet the
basic conditions of thermal shutdown after the temperature deviation.
(Control mode return air)
The temperature control is based on the risk
control system, and the air supply can be selected.
(repower startup)
Turn on the incoming call function.
(return)
The return key is returned to the previous page.
Many Setting
Figure 6-12 Many Setting
(2018 Year 03 month 20 day 13 hour 22 minute 52 second)
Date and time,
you can set the current date and time.
(Modbus address 0)
Monitor address, you can set the monitor address of the
controller.
(restore factory reset)
Factory setting reset.
(return)
The return key is returned to the previous page.