22
4.2 Set point values
0x0024
INT
R/O
Limit comparators 1...2
Bit 0
Limit comparator 1 (= 0x0001)
Bit 1
Limit comparator 2 (= 0x0002)
0x0025
INT
R/W
Control of the binary outputs (individual)
Bit 0 + Bit 8
Output K1 (= 0x0101)
Bit 1 + Bit 9
Output K2 (= 0x0202)
Bit 2 + Bit 10
Output K3 (= 0x0404)
Bit 3 + Bit 11
Output K4 (= 0x0808)
0x0026
FLOAT
R/O
Analog input [mV]
0x0028
FLOAT
R/O
Internal Pt100 [Ohm]
0x002A
INT
R/O
Sampling cycle time
0x002B
FLOAT
R/O
Analog input [displayed value]
0x002D
FLOAT
R/O
Internal analog value 1
0x002F
FLOAT
R/O
Internal analog value 2
0x0031
FLOAT
R/O
Controller, ramp limit value
0x0033
FLOAT
R/O
Controller, actual value, FILTERED
0x0035
FLOAT
R/O
Controller, actual value, UNFILTERED
0x0037
FLOAT
R/W
Controller set point value
0x0039
FLOAT
R/O
Controller, output value display
0x003B
FLOAT
R/O
Controller, output value, HEATING
0x003D
FLOAT
R/O
Controller, output value, COOLING
0x003F
FLOAT
R/O
Controller, control difference
0x0041
FLOAT
R/O
Controller, control deviation
0x0043
INT
R/O
Controller, switching state, HEATING
0x0044
INT
R/O
Controller, switching state, COOLING
0x0046
INT
R/O
Output value, manual mode
0x0047
LONG
R/O
Timer run time
0x0049
LONG
R/O
Residual timer time
0x004B
INT
R/O
Timer status
Bit 1
Timer stopped (= 0x0002)
Bit 5
Timer runs (= 0x0020)
Bit 6
Timer end (= 0x0040)
Bit 15
Timer signal (= 0x8000)
Address
Data type/
bit number
Access
Signal designation
0x3100
FLOAT
R/W
Set point value W1
0x3102
FLOAT
R/W
Set point value W2
Address
Data type/
bit number
Access
Signal designation
Summary of Contents for TCONTROL-CONT-03
Page 2: ......
Page 4: ...Contents ...
Page 6: ...1 Introduction 6 ...
Page 26: ...4 Modbus addresses 26 ...
Page 28: ......
Page 30: ...Sommaire ...
Page 32: ...1 Introduction 6 ...
Page 52: ...4 Adresses Modbus 26 ...
Page 54: ......
Page 56: ...Inhalt ...
Page 58: ...1 Einleitung 6 ...
Page 78: ...4 Modbus Adressen 26 ...
Page 79: ......