Wiring the AC type power supply
cable
• When the FG terminal is connected,
be sure the wire is grounded. Not
grounding the FP unit will result in
excessive noise. Use your country's
applicable standard for grounding.
Power Cord Specifications
Use copper conductors only.
Wiring
When connecting the power cord, use
the following items when performing
wiring.
(Items are made by Phoenix Contact.)
• Accompanying AC type power
supply connector is CA7-ACCNL-01
from Pro-face or FKC2,5/3-STF-
5,08 is manufactured by Phoenix
Contact.
Connecting the Power Cord
(1) Confirm that the power is not sup-
plied to the FP unit.
(2) Push the Opening button with a
small and flat screw driver to open
the desired pin hole.
(3) Insert each pin terminal into its each
hole. Release the Opening button to
clamp the pin in place.
(4) After inserting all three pins, insert
the Power Plug into the Power Con-
nector at FP. Fix the plug with two
(2) minus screws.
• Confirm that all wires are connected
correctly.
• The torque required to tighten these
screws is 0.5 to 0.6 N
•
m (4.4 to 5.3
lb-in).
• To prevent the possibility of a termi-
nal short, use a pin terminal that has
an insulating sleeve..
USB Cable Clamp Attachment
Procedure
Installation to USB cable
(1) Connect the USB cable to the
connector.
Power Cord
Diameter
0.75 to 2.5mm
2
(18 to 12 AWG)
Conductor
Type
Simple or Stranded
Wire
*1
*1
If the Conductor’s end (individual) wires
are not twisted correctly, the end wires
may either short against each other, or
against an electrode.
Conductor
Length
Recommended
Driver
SZS 0.6x3.5 (1205053)
Recommended
Pin Terminals
AI 0.75-10GY (3201288)
AI 1-10RD (3200182)
AI 1.5-10BK (3200195)
AI 2.5-12BU (3200962)
Recommended
Pin Terminal
Crimp Tool
CRIMPFOX ZA3
(1201882)
10mm
[0.39in]
Using the USB Cable Clamp
Opening Button
AC power supply cord
L
N
FG