DSE Model 5220 Automatic Mains Failure & Instrumentation System Operators Manual
5220 OPERATING MANUAL ISSUE 5.1 18-Jun-07 AM
41
Output settings – Relay
Value
1 Energise
Preheat (during pre-heat timer)
2 Energise
Common alarm
3 Energise
System in auto mode
4 Energise
Close generator
5 De-energise
Close mains
Output settings – Expansion A
Value
1 Energise
Output not used
2 Energise
Output not used
3 Energise
Output not used
4 Energise
Output not used
5 Energise
Output not used
6 Energise
Output not used
7 Energise
Output not used
8 Energise
Output not used
LCD indicator settings
Value
1 Lit
Digital input 1 active
2 Lit
Digital input 2 active
3 Lit
System in auto mode
4 Lit
Common alarm
Timer settings
Value
Mains transient delay
#
1s
Start delay
#
5s
Pre-heat
#
0s
Cranking time
#
10s
Crank rest time
#
10s
Smoke limit
0s
Smoke limit off
0s
Safety on delay
#
10s
Overspeed overshoot
#
2s
Warming up time
#
0s
Transfer time
0.7s
Breaker close pulse
0.5s
Breaker trip pulse
0.5s
Return delay
#
30s
Cooling time
#
30s
ETS solenoid hold
#
0s
Fail to stop delay
30s
Generator transient delay
1s
Battery low volts delay
1m
Battery high volts delay
1m
LCD page timer
5m
Mains (utility) settings – Voltage/frequency
Trip
Return
Under volts trip
#
180V AC
200V AC
Over volts trip
#
280V AC
260V AC
Under frequency trip
#
45Hz 48Hz
Over frequency trip
#
52Hz 55Hz