Aiphone™ LE / LS series 3-wire Call Station Installation 

 

  Set the internal 

ST-MIC

 switch to the 

ST

 

setting  

  Remove Aiphone shorting link between 

E and - terminals 

  Connect 

SPKR 8Ω+

 and 

SPKR 8Ω-

 (J2-

6 and J2-

7) to the “1” and “E” terminals 

on the Aiphone call station 

  Connect 

TALK

 (J2-

5) to Aiphone “–“ 

(minus) terminal 

  Connect 

GND

 (J2-4) to the shield of the shielded wire. Do not connect the 

shield at the call station 

 
 
Aiphon

e™ IE / IF series 2-wire Call Station Installation 

  Set the internal 

ST-MIC

 switch to the 

MIC

 setting  

  Connect 

GND

 and 

TALK

 (J2-4, J2-5) 

to Aiphone terminals 1 and 2 (polarity 
independent) 

  Connect 

GND

 (J2-4) to the shield of 

the shielded wire. Do not connect the 
shield at the door station 

 

 

 
 
Call stations with a separate microphone, speaker and Call button 

  Set the internal 

ST-MIC

 switch to the 

MIC

 setting  

  Connect 

MIC+

 and 

MIC-

 (J2-1, j2-2) to 

the call stations microphone 

  Connect 

GND

 (J2-4) to the shield of 

the shielded wire. Do not connect the 
shield at the call station 

  Connect 

SPKR 8Ω+

 and 

SPKR 8Ω-

 

(J2-6 and J2-7) to the call stations 
speaker terminals 

  Connect 

TALK

 (J2-5) to one contact 

on the call station’s TALK button  

  Connect the other contact on the 

call station’s TALK button to

 GND

 (J2-4) 

or jumper it to one of the speaker terminals (this wire should be limited to 
10ft or 3 meters)  

 

Driving an Analog Paging Amplifier 

 

The IP7-ST/STX has the capability to drive a 

balanced

 600 Ohm input of an 

analog amplifier using 

SPKR 8Ω+

 and 

SPKR 8Ω-

 (J2-6 and J2-7).  Set the 

IP7’s volume level to 6 and adjust the amplifier’s volume control accordingly. 

If the analog amplifier uses an 

unbalanced

 

input, then the IP7’s Line 

Out and GND (J2-3 and J2-4) must be used instead of SPKR 8

Ω+ 

and SPKR 8Ω-. 

Failure to do so will damage the IP7 and void its 

warranty.

 

 

 

Relay Options 

  The integrated 

Relay

 uses 

COMMON

 (J3-2), along with 

NO

 - Normally 

Open (J3-1) or 

NC

 - Normally Closed (J3-3). Use Admin Console to 

configure the options 

Sensor Options 

  The integrated 

Sensor 

can be used to monitor the status of a door by 

connecting 

Sensor

 (J3-5) and 

GND

 (J3-6) to a contact closure sense 

switch. Use Admin Console to configure the options 

 

Power Options 

  Power over Ethernet (PoE - 802.3af compliant) - requires 7 watts from 

Power Source Equipment (PSE) 

  9VDC - 32VDC external via 

J1-1

 and 

J1-2

 connectors or 

Aux Power

 

2.1mm barrel connector 

  An external power supply, if detected, overrides PoE power 

 

Network Installation 

  Connect an RJ-45 cable between the 

Ethernet 10/100 

connector and a 

10/100 network switch 

  On the 

IP7-STx

, after the 

Ethernet 10/100

 is connected, another IP device 

can be connected to 

Port 2 10/100

 jack 

 

Mounting Instructions 

The IP7 series is design to be mounted on standard 35mm DIN rail or 
surface mounted using the surface mounting plate. 

 

DIN Rail Clip 

– Tilt top of unit (J1, J2, J3 connectors facing up with Volume 

buttons facing forward) back towards the DIN Rail until the IP7 DIN clip 
catches the top of the rail. Press in at the bottom of the IP7 to snap into 
place 

 

Surface Mount Plate

 

– Snap the surface mount plate in half and secure it 

to the back of the unit using the provided screws so that the mounting 
holes extend past the edges of the case 

 

Aiphone LE, LS series

J1

J2

J3

Aiphone IE, IF series

J1

J2

J3

No Connection

J1

J2

J3