Pocket AL I/O
Configuration
3.5.1. SMS alarm messages
The message sent by the device in case of alarm to the devices set during the configuration will contain the following
information:
• Pocket AL I/O ID (i.e. HOME)
• Contact number (i.e. 13)
• Contact ID (i.e. Temperature)
• Status
Level1 LOW (level lower than Level1)
Level1 HIGH (level higher than Level1)
Level2 LOW (level lower than Level2)
Level2 HIGH (level higher than Level2)
• Detected value
NOTES:
1. To set a sole level, that means to set 2 zones only, configure Level2 = 1000
In this case you can receive only the following messags: Level1 LOW and Level1 HIGH
2. For the value detection it will be enough to send the message #TEST13# or #TEST14#.
3. The indication Level2 LOW or Level 1 HIGH depend on the previous status (if it was level1 LOW, it sends
level1 HIGH, if it was level2 HIGH, it sends level2 LOW)
Examples of alarm messages
Contact 13 alarm
HOME
13)Temperature Level1 LOW
144
HOME
13)Temperature Level2 HIGH
500
3.6. OUTPUT CONfIGURATION
Pocket AL I/O is equipped with four digital outputs (Open Collector) and two relays outputs to remote interact after an alarm
signalling, for example to open or to close a tank valve after the detection of exceeded level.
Outputs setting:
#
KEY
#
ID
# USER 1 #
USER n #
USER 6
#
NAME
VALUE
DESCRIPTION
Key
5,6,7,8
Key of open collector outputs
11,12
Key of relay outputs
ID
A..Z,a..z,
ID associated to the contact (20 character maximum. “#” and space characters not
0..9
accepted in the ID field)
User n
+ 0..9
Phone numbers enabled to output management (up to six phone numbers can be inserted)
NOTES
1. If you want to add a number to an already set list, it will be necessary to insert all the numbers again.
2. 0 (zero) character in User1 will cause the list cancellation.
3. The factory configuration foresees the User n list empty. That means that anyone can manage the outputs
through the proper command: #OUTPUTn ON# and OUTPUTn OFF#
EXAMPLES
#5#Tap#+393359393491393285554446#
#6#OUTPUT2#0#