6
7
6.2 MANUAL VALVE ACTUATOR INSTALLATION
Rated operating pressure: 20 to 125 PSI
Recommended operating pressure: 20 to 80 PSI
1. Shut off main water supply.
2. Remove the manual stem from the existing valve and temporarily remove the
anti-siphon cap (Figure A).
3. Replace any existing worn washers with the new ones provided (Figure B).
4. Install the actuator into the manual anti-siphon valve body by turning actuator
clockwise. Tighten firmly, but do not over tighten (Figure C). Re-install anti-siphon
cap.
v
5. Turn actuator flow control knob clockwise until it stops (Figure D).
6. Turn on main water supply.
7. Activate the solenoid through the timer manual button, a click will be heard indicating
the valve is open (The manual symbol will appear on the display).
8. Turn the actuator flow control knob counter clockwise to allow flow and
check the system to make sure that the sprinklers or the drip system is
working properly (Figure E).
9. De-activate the solenoid through the timer’s manual button, a faint click will be heard
and the valve will close. (The manual symbol will disappear and water flow will stop).
If flow continues, turn flow knob clockwise, one full turn at the time until flow is
stopped, and the valve is shut off.
10. Repeat steps 7 and 9 and make sure that flow is turned on and off.
Note: Turn the flow control knob clockwise to decrease flow, counter-
clockwise to increase flow. For low-flow drip systems below 60 gallons
per hour, flow control knob should be turned no more than 1 to 3 turns up
(counter-clockwise) from the fully closed position.
11. The unit is now ready to be programmed.
FIGURE A
FIGURE B
FIGURE C
MANUAL STEM
ANTI-SIPHON
CAP
WASHERS
VALVE BODY
FIGURE D
FIGURE E
FLOW CONTROL KNOB
FLOW CONTROL KNOB