Detection of fault probes, maximum flexibility of managing and semplicity of
programming, checking of validity of the insert data during programming phase.
•
Continuos storage of planned and reached values by each channel (limits and
historic highs).
•
Dielectric isolation: 2.5 Kv for 60”.
•
Software configuration to control the environment temperature.
•
Resolution 1° C.
•
Working temperature of device from -40°C to 60°C.
•
Max allowed dampness in the room 90% not condensing.
•
Electrical connections with fast polarised connectors.
•
Possibility of manual relays switch through menu test relays to simulate and check
the reliability of contact.
•
Galvanically insulated output 4-20mA or 0-20mA (MT200 C)
•
Maximum impedance allowed for current output 500 Ohm (MT200 C)
Range 4-20mA (-10°C 4mA / +200°C 20mA)
Transformation formula: lout = (T+10)/210*16 + 4 (current in mA, temperature in °C)
Range 0-20mA (-10°C 0mA / +200°C 20mA)
Transformation formula: lout = (T+10)/210*20 (current in mA, temperature in °C).
•
Technical manual in five languages (and more on request).
•
Construction in accordance with rules
.
•
Input filter for power supply in accordance with rules
.
•
Tropicalization (optional).
ASSEMBLY
Perform a square hole measuring 91x91 mm in the panel board sheet.
Fasten the monitoring system trough the special hooks.
POWER SUPPLY
The device can be supplied with (24÷240) Volt AC/DC ± 10% 50/60 Hz without
respect of polarity.