Conduit Pendant Mount (Figure 3) Installation Steps:
•
For maximum long term reliability and light output, the light must be installed in free air.
o
The Linear fixture design incorporates an over-temperature control circuit that
reduces input power should internal temperatures reach a maximum level. In this
event, light output may be reduced.
•
The Linear fixture is threaded for 3/4” NPT, at the center and each end of the Power
Supply Housing, in order to be assembled to conduit.
o
Attach conduit as shown in figure 3. Use conductive pipe sealant for all fittings and
conduit.
o
Fixture is factory wired for both Pendant and Through wiring. Remove the Power
Supply Covers to attach incoming power to the white wire and black wire leads
with wire nuts at the center of the fixture. Attach the ground wire to the green
ground lead supplied at the center of the fixture. Ensure that the o-rings are
properly seated in the grooves, reattach the Cover using the screws previously
removed. Tighten all screws to 15 in/lbs.
•
Restore power and verify operation.