Conformity with Standards

 

This equipment conforms to the standards specified in the 
Declaration of Conformity. It has been designed, 
manufactured and tested in accordance with BS EN 9001. 
 
Atex Directive 2014/34/EU: Equipment and protective 
systems intended for use in potentially explosive 
atmospheres. EMC Directive 2014/30/EU Directive for 
electromagnetic compatibility. 
 
Equipment Application 
This lighting equipment is intended for use in a potentially 
explosive atmosphere in Zones 1, 21 and 2, 22 to the 
requirements of ATEX Directive 2014/34/EU. 
 
Mounting the Luminaire 
Assemble the mounting bracket to the Luminaire with two 
M8 x 1.25 by 16mm bolts. Torque specification: 2.0Nm 
maximum.  
 
Installation 
Ensure that the mains voltage supply is disconnected 
before connecting the luminaire. Install the equipment in 
accordance with the manufacturer’s instructions as well as 
any other applicable electric codes. 
 
Always transport and store the equipment in its original 
packaging and keep in a dry location. When unpacking 
check for any cracks or damage in the housing or lens. If in 
doubt, do not install! 
 
The cabling used must be suitable for the site application 
and/or the site requirements. 
 
When assembling the cable entries for the mains 
connection, always observe the manufacturer’s 
specifications for the glands used. Unused cable entries 
must be closed and sealed by a certified blanking plug. 
 
Note: Unused cable entries must be closed off with a 
certified blanking plug or stopper. Dust caps must be 
removed and replaced with either a suitable cable gland 
or certified blanking plug. 
 
The cable entries should be securely tightened to ensure 
that the minimum protection rating is achieved. A locknut is 
required for each cable gland to securely hold the cable 
gland to the end covers. The cable entry should be rated to 
a minimum of IP66/67 to maintain the protection level of 
the luminaire. 
 
Do not over tighten as the protection rating may be 
compromised. Always refer to the gland manufacturer’s 
data for torque settings. 
 
Cable gland with O-ring min. thread length C = 10mm. 

P

 = M20 x 1.5mm 

P

 = M25 x 1.5mm (suffix 4) 

 
 
 
 
 
 
The terminal block is suitable for multi-stranded or single 
core wires up to a maximum of 4mm

2

, strip length 10mm. 

 
The LIVE, NEUTRAL and EARTH connections are clearly 
marked on the terminal block or on a label. Push down at 
the ‘cross point’, insert correct wire and release, ensuring all 
the conductor has been securely retained. 
 
3 phase wiring connection 
Connect the designated load phase (e.g. L1) to L on the 
terminal block and the other 2 live phases to appropriate 
live terminals (e.g L2 / L3) on the terminal block as shown in 
the diagram. 
 
Loop in /out electrical connections: 
Connect incoming cable as above then connect the 
outgoing cable to the associated adjoining connection on 
the terminal block to pass to the next luminaire. The  

 
 
 
outgoing cable may also be connected to the terminal  
 
block at the opposite end to the incoming cable (loop 
through) 
 
ONLY SINGLE WIRES TO BE USED ON EACH TERMINAL ENTRY 
POINT. 
 
The improper installation, operation, or maintenance of 
these luminaries may result in the invalidation of the 
warranty, certificate or declaration of conformity. 
 
Taking into Operation 
Prior to operating, check the luminaire for its correct 
installation in compliance with these operating instructions 
and other applicable regulations. 
 
Attention: Only fully certified equipment may be put into 
operation. 
 
Conditions  for use 
The supply to the luminaire must include a fuse which is 
capable of interrupting a 1.5kA short circuit current. 
When used with steel wired armour or braided cable the 
basket weave armour or braid is unable to carry the cable 
load without fracture. The cable must therefore be 
clamped and cleated to prevent pulling on the cable 
being transmitted to the cable terminations. 
 
Improper installation or operation of this luminaire may 
invalidate the warranty, certificate or declaration of 
conformity. For maximum long term reliability and light 
output, the luminaire must be installed in free air. 
 
Maintenance 
There are no user serviceable parts inside.  
 
This LED luminaire should require a minimum amount of 
maintenance. If any unforeseen repairs are required, please 
contact Dialight or its authorised representative. 
 
Inspection 
Within the scope of maintenance or inspection routine the 
following should be included: Protective hoses covering the 
connection cables - cable entries must be free of 
corrosion. 
Perform visual mechanical and electrical inspections on a 
regular basis. 
We recommend routine checks to be made on a yearly 
basis. Frequency of use and environment should determine 
this. 
It is recommended to follow an Electrical Preventive 
Maintenance Program as described in NFPA 70B: 
Recommended Practice for Electrical Equipment. 
 
Repairs / Overhaul / Modification 
Should the luminaire enclosure be damaged, only a 
replacement will be permitted. In case of doubt, the 
equipment should be returned to Dialight for 
inspection/repair. Modifications to the device or changes 
of its design are not permitted. 
 
The equipment must be operated according to the 
intended purpose in a perfect and undamaged condition. 
 
Disposal Recycling 
When the apparatus is disposed of, the respective national 
regulations on waste disposal should be observed. WEEE 
(Waste electrical & electronic equipment) registration 
number W EE/DC2678RY 

Technical Data: 
Category of Application: 

32W: 

Ex e mb IIC T4 Gb 
Ex tb IIIC T135°C Db 

 II 2GD 

64W 

Ex e mb IIC T4 Gb 
Ex tb IIIC T135°C Db 

II 2GD 

IECEx / ATEX: 

SIRA 12ATEX3217X               
IECEx SIR 12.0093X 

Rated Input 
Voltage: 

 
100-277 VAC 50/60 Hz 

Rated Input Current: 

32W: 

175mA at 230V AC 
350mA at 110V AC 

64W: 
 
Inrush Current 
@230VAC 
 
32W: 
 
64W: 

350mA at 230V AC 
700mA at 110V AC 
 
 
 
1A for 6ms 
 
6A for 50μs 

Operating Temp.  -20°C to +60°C 
Housing: 

Marine Grade 316  
Stainless Steel  IP66/67 

Dimensions: 

See diagram page 

Cable Entries: 

Standard 2 OFF M20 x 1.5mm  
(M25 x 1.5mm optional) 

Terminal block: 

Standard: 4-way, max. 4mm² 
5 wire thru: 7-way, max. 4mm² 

Through cable: 

Standard: 3 x 1.5 mm²  
5 wire thru:  7 x  2.5 mm² 

Tightening 
Torques:   
 
 

See page 2 
 

 Weight: 
32W: 

6.5Kg 

64W 

11.4Kg 

 

Safety Instruction: 
The installation, operation and 

maintenance must be carried out by 
an electrician suitably trained in 
hazardous areas with knowledge of 
increased safety explosion protection 

IEC 60079-14.  

 

 • The technical data indicated on the   
     LED luminaires are to be observed. 

 

• Changes of the design or 

   modifications to the LED luminaire 
   are not permitted 

 

• Observe the national electrical safety 

rules and regulations during 

installation. 

 

 • No user serviceable parts inside. 

 

 • No field replaceable parts. 