Reliant High Bay Replacement Power Supplies

 

5.

 

Collect the replacement power supply and install into luminaire by sliding fully into the mounting tabs. Install 2x 8-32 SEMS screws loosely to the 

front of the power supply. Slide the supply forward fully onto the 8-32 SEMS screws. Torque to 14-16 in-lbs. 

 

 

 

 
6.

 

Add zip tie and connect plugs (shown below). 

 

 

 

 

7.

 

Tilt the access cover closed, engage the snap features and tighten the captive screw. Torque to 14-16 in-lbs. 

a.

 

If the luminaire contains an occupancy sensor, replace the sensor lens by sliding it onto the sensor and then twisting ¼ turn clockwise 
until snug. 
 

8.

 

Power the luminaire on and insure proper function. 

a.

 

If the luminaire contains battery backup, press and hold the battery test button for 5 seconds to ensure the luminaire goes into battery 
backup mode. 

 
 

 
 
 

 
 
 

 
 
 

 

Official Statement 

All  statements,  technical  information,  and  recommendations  contained  herein  are  based  on  information  and  tests  that 
Dialight believes to be reliable. The accuracy or completeness thereof is not guaranteed. In accordance with Dialight “Terms 
and Conditions of Sale” and since conditions of use are outside our control, the purchaser should determine the suitability of 
the product for his or her intended use and assumes all risk and liability whatsoever in connection therewith. 