Position Transmitter 

The position transmitter provides a 4 to 20 mA output signal with the plus and minus terminals 
connected in series with an external 24 VDC power supply. Voltage variations from 10 VDC to 40 VDC 
do not affect the current signal. The maximum load is 700 ohms at 24 VDC. The unit is calibrated as 
shown in the following steps. Refer to Figure 3 for component identification. 

1.  Plug the 3-pin potentiometer connector into the appropriate 3 pins on the 5-pin block as 

described in Figure 3. The 5-pin block is located next to the span adjustment. 

2.  Place the valve in the position desired for 4 mA output. Do not connect power until step 4. If the 

valve is in the closed or clockwise position, connect an ohmmeter to terminals 2 and 3 of the 
potentiometer; if the valve is in the open or counterclockwise position, connect an ohmmeter to 
terminals 1 and 2 of the potentiometer. 

3.  Loosen the coupling that drives the potentiometer shaft, and rotate the potentiometer so that the 

ohmmeter reads 500 ± 100 ohms. Then tighten the coupling, and disconnect the ohmmeter from 
the potentiometer. 

4.  Connect a 20 mA ammeter and a 24 VDC power supply to ter and 

– as shown in Figure 

3. 

5.  Adjust the zero trimpot so that the ammeter reads 4 ± 0.1 mA. 

6.  Place the valve in the position desired for 20 mA output. Adjust the span trimpot so that the 

ammeter reads 20 ± 0.1 mA. The zero and span adjustments are not interactive. 

 

Figure 3

—Position Transmitter 

 

Summary of Contents for D10350

Page 1: ...DeZURIK Inc Sartell Minnesota USA Phone 320 259 2000 www dezurik com info dezurik com DEZURIK SWITCH AND POSITIONER TRANSMITTER Instruction D10350 May 2014...

Page 2: ...us pipeline materials Handle valves which have been removed from service with suitable protection for any potential pipeline material in the valve Inspection Your Switch and Position Transmitter has b...

Page 3: ...2014 Page 3 D10350 Table of Contents Description 4 Electrical Connections 4 Mechanical Switches 4 Proximity Switches 5 Position Transmitter 6 Indicator Adjustment 7 Switch Mounting Kit used on PMV Po...

Page 4: ...cribed in the following sections One pipe plug is provided with the unit If the connection is not used install the pipe plug tightly in the connection Do not use thread sealant Mechanical Switches The...

Page 5: ...rating of 0 3 amp at 120 VAC or 0 2 amp at 30 VDC The switch contacts are sealed for low energy switching of solid state signal circuits The top switch is factory set to trip as the valve reaches the...

Page 6: ...4 mA output Do not connect power until step 4 If the valve is in the closed or clockwise position connect an ohmmeter to terminals 2 and 3 of the potentiometer if the valve is in the open or countercl...

Page 7: ...in the indicator drum A4 The shaft adaptor may be a different size and or shape than shown in Figure 3 4 Rotate the indicator drum A4 to the desired position and push the shaft adaptor A1 and spacer...

Page 8: ...DeZURIK D10350 Page 8 May 2014 Switch Mounting Kit used on PMV Positioner Figure 5 Switch Mounting Kit used on PMV Positioner...

Page 9: ...l be the only effective guarantee or warranty binding on Seller despite anything to the contrary contained in the purchase order or represented by any agent or employee of Seller in writing or otherwi...

Reviews: