- 43-
Error code
Description
Solutions
F47
AC_OverFreq_Fault
Grid frequency out of range
1. Check the frequency is in the range of specification or not;
2. Check whether AC cables are firmly and correctly connected;
3. Seek help from us, if can not go back to normal state.
F48
AC_UnderFreq_Fault
Grid frequency out of range
1. Check the frequency is in the range of specification or not;
2. Check whether AC cables are firmly and correctly connected;
3. Seek help from us, if can not go back to normal state.
F52
DC_VoltHigh_Fault
F53
DC_VoltLow_Fault
BUS voltage is too high
1. Check whether battery voltage is too high;
2. check the PV input voltage, make sure it is within the allowed
range;
3. Seek help from us, if can not go back to normal state.
Battery voltage low
1. Check whether battery voltage is too low;
2. If the battery voltage is too low, using PV or grid to
charge thebattery;
3. Seek help from us, if can not go back to normal state.
F58
Battery_comm_Lose
1, it tells the communication between hybrid inverter and battery
BMS disconnected when “BMS_Err-Stop” is active”
2, if don’t want to see this happen, you can disable
“BMS_Err-Stop” item on the LCD.
3, If the fault still exists, please contact us for help
F62
DRMs0_stop
F34
AC_Overload_Fault
F63
ARC_Fault
F64
Heatsink_HighTemp_Fault
1. ARC fault detection is only for US market;
2. Check PV module cable connection and clear the fault;
3. Seek help from us, if can not go back to normal state
1, Check the backup load connected, make sure it is in allowed
power range
2, If the fault still exists, please contact us for help
1, the DRM function is for Australia market only.
2, Check the DRM function is active or not
3, Seek help from us, if can not go back to normal state after
restart the system
Heat sink temperature is too high
1. Check whether the working environment temperature is too
high;
2. Turn off the inverter for 10mins and restart;
3. Seek help from us, if can not go back to normal state.