Instruction Manual
30
P30
Selection of switch-off and
switch-on point for DHW
0 - 1
0 - Switch off point: Domestic water tem-
perature ≥ 65 °C
Switch-on point: Domestic water tempera-
ture ≥ 64 °C
1 - Switch-off point: Domestic water tem-
perature ≥ domestic water se5 °C
Switch-on point: Domestic water tempera-
ture ≥ domestic water setpoint - 1 °C
0
Parameter available
starting from controller
software version no. 12
P31
Selection of activation
source - Tank Timer
0 - 1
0 - from input on control board or command
fromt he LIN interface
1 - only from input on control board
0
Parameter available
starting from controller
software version no. 12
NOTE!
Some parameters may not be visible in the programming mode if the clamp on the control board CMUNI-02 is shorted. To
access the missing parameters, turn off the power, remove the CM clamp, and re-power the device.
5.6.1 Programming Mode entering
To activate the programming mode:
1.
Set the operating mode: STANDBY (see Table/section 5.3)
2.
Turn off the boiler power.
3.
Turn on the boiler power again. Wait until the flashing symbol
disappears from the screen.
4.
Press and hold reset together with the
button for over 8 sec.
5.
The display shows the parameter number and the symbol
no longer flashes but maintains a constant light.
6.
Release the buttons.
7.
Using + / - buttons, select the desired parameter to change.
8.
By pressing button
, it is possible to edit the selected parameter. Use the +/- buttons to change the parameter values
•
Parameters P01 and P03 activate the boiler with the desired power of the C.H. circuit
•
Parameter P02 activates the boiler with the desired power of the DHW circuit, if the flow sensor of DHW is
working.
•
At the end of the gas ignition process, the burner power will be the same as the displayed value
9.
Accept changes with button
; to cancel the change use the reset button.
To save parameters and exit the programming mode: hold down the reset button for about 2 seconds, or wait. Programming
mode switches off automatically after a set period of inactivity.
5.7 PAUSING BOILER OPERATION
•
leave the boiler connected to the power supply,
•
leave the gas valve and water valve of C.H. open,
•
set the boiler mode to STANDBY (section 5.3)
•
in the paused state, the controller of the boiler has a protective function described in section 5.3 - “Performed functions”.
If you decide to discontinue using the boiler for a long time, you should:
•
set the mode on STANDBY (section 5.3)
•
drain the boiler’s water system and also the C.H. system using the drain valve (item 33 Fig 2.2.1.1 and 2.2.1.2) if freezing
is a possibility
•
close the water and gas valves and disconnect the boiler from the power supply.
NOTE!
During winter (because of the risk of water freezing in the system), disconnecting the boiler from the electrical system
is forbidden, if there is still water in the boiler’s water system.