45
Pictures for illustra
Ɵ
ve purposes
only
E
LECTRO
V
AP
RTH-LC
Changing parameters menu
MENU : CHANGING UNIT
CONFIGURATION
CONTROL SIGNAL IN
XXXXXXXXXXXX
STEAM CAPACITY LIMIT
XX %
ADJUST PROP BAND
XX %
ADJUST SET POINT
XX % Hr
MAINTENANCE FRE-
QUENCY 10000 KG
MAINTENANCE FRE-
QUENCY 300 H
MENU: HUMIDIFIER
MENU
Possible value :
1 step on/off, digital control, digital
sensor 4 steps, 0-10V / 2-10V controler, 0-20 / 4-20 mA
controler, 1-5V sensor, Devatec sensor
Possible value : between 20 and 100 % if On/Off control
otherwise 50-100 %
Possible value : between 10 and 99 %
Enables to tune the proportional accuracy.
Possible value : between1 and 50 %
Possible value : between 0 and 999000 kg
This is to preset a number of kg of steam or a number of hours
of running before a visual inspection of the steam boiler takes
place. If the steam boiler needs being maintained, please revert
to the maintenance pages of this manual. Otherwise, a higher
preset maintenance figure can be adjusted (factory preset
value : 300h).
Possible value : between 0 and 2000 H
SETTING WATER T° : YES
Possible value : YES or NO
This is to keep or not the water temperature on when
the unit is on halt.
WATER TEMP. °C MAIN-
TAINED XXX °F XXX °C
Possible value : between 25°C and 85°C
Press on the enter key
from any of these menus