ELECTROVAP
®
RTH-HC
46
5.2
SETUP MENU
PROD. LIMITATION
XXX %
CTRL SIGNAL TYPE
XXXX
XXX
By pressing enter from
this menu
HUMIDIFIER
SETUP
CONTROL
SYSTEM
Adjusting of control signal:
. 1 STEP ON /OFF,
. 4 - 20mA CONTROL, 0 - 5V CONTROL, 0 - 10V CONTROL, 2 -
10V CONTROL .
. DEVATEC SENSOR, 0 - 5V SENSOR, 0 - 10V SENSOR.
. DIGITAL SENSOR, DIGITAL CTRL.
Adjusting of Steam Production
1 STEP - On / Off:
20 % > Limit > 100 %
Other control:
50 % > Limit > 100 %
SET POINT
XX % RH
PID SETTINGS
P: XX I: XX D: XX
END OF SEASON DRAIN?
XXX
EOS TIMER
SETTING:
XX Hrs
Display when a RH sensor is used
Setting the set point (1 - 99 % Rh)
Setting of PID. (0 to 50: P - I
–
D)
Setting: End Of Season (EOS)
Enable or disable of drain system (OFF or ON)
Timeout EOS (1 to72 hrs)
AQUASTAT SETTING
XX
AQUASTAT SP
XX °F XX °C
WATER TYPE USED
XXXX XXXX
EOL SETTING
XXXXXX KG
AQUASTAT setting:
Off or On: frost system enable or disable
Maximum temperature wanted
65°C > °C > 95°C or 149°F > °F > 203°F
Water type: “TAP WATER”, “DI WATER”, “PARTIAL DI
WATER”, “SOFTENED WATER”
End Of Life setting: 100>Kg>20000
Summary of Contents for ElectroVap RTH-HC Series
Page 1: ...ElectroVap HUMIDIFIERS RTH HC Series Instruction Operation Manual ...
Page 30: ...ELECTROVAP RTH HC 30 3 8 6 Wiring diagrams Up V 1x200 240V 50 60Hz ...
Page 31: ...ELECTROVAP RTH HC 31 RTH HC 8 18 Up V 3x200 240V 50 60Hz ...
Page 32: ...ELECTROVAP RTH HC 32 RTH HC 5 30 Up V 3x380 690V 50 60Hz ...
Page 33: ...ELECTROVAP RTH HC 33 RTH HC 40 50 Up V 3x380 690V 50 60Hz ...
Page 34: ...ELECTROVAP RTH HC 34 RTH HC 60 70 Up V 3x380 690V 50 60Hz ...
Page 35: ...ELECTROVAP RTH HC 35 RTH HC 80 100 Up V 3x380 690V 50 60Hz ...
Page 36: ...ELECTROVAP RTH HC 36 RTH HC 8 18 Up V 3x200 240V 50 60Hz ...
Page 37: ...ELECTROVAP RTH HC 37 RTH HC 44 Up V 3x200 240V 50 60Hz ...
Page 39: ...ELECTROVAP RTH HC 39 Case 2 Up V 3x200 240V 50 60Hz Only for Case 3 ...
Page 40: ...ELECTROVAP RTH HC 40 Case 3 Up V 3x380 690V 50 60Hz ...
Page 42: ...ELECTROVAP RTH HC 42 3 9 OPTION TRANSFORMER CONNECTION ...