ELECTROVAP
®
RTH-HC
26
3.8.2
Remote information board
The contact can be changed to NO or NC by wiring according to the following diagrams (e.g. wiring on 30 & 31 = NO
contact).
3.8.3
RS485
–
Hardware connection
RS485 connection must be plugged on the J2 connector:
•
Terminal 1: Data -
•
Terminal 2: Data +
•
Terminal 3: GND
The SW1 switch is used to turn line resistance on or off. Depending on your
needs, these resistances can be activated or deactivated (see diagram).
X22 Connector (36-37-38): Remote
steam production dry contact.
X21 Connector (33-34-35): Remote
general fault dry contact.
X20 Connector (30-31-32): Remote tank
maintenance dry contact.
1
2
3
4
3
2
1
J2
SW1
On
Off
K4A
X10
Main board /
Carte
Principale
SW1
–2
J2
1 : Data
–
2 : Data +
3 : GND
+5V
680
SW1
–3
120
SW1
–1
680
Carte Principale /
Main board
Ref : 500102
X18
Ref 500400
500400
X23
X20
X22
X21
X20
30 31 32
X21
33 34 35
X22
36 37 38
NO
NC
NC
NC
NO
NO
Fig. B 3-8.
Fig. A 3-8.
Summary of Contents for ElectroVap RTH-HC Series
Page 1: ...ElectroVap HUMIDIFIERS RTH HC Series Instruction Operation Manual ...
Page 30: ...ELECTROVAP RTH HC 30 3 8 6 Wiring diagrams Up V 1x200 240V 50 60Hz ...
Page 31: ...ELECTROVAP RTH HC 31 RTH HC 8 18 Up V 3x200 240V 50 60Hz ...
Page 32: ...ELECTROVAP RTH HC 32 RTH HC 5 30 Up V 3x380 690V 50 60Hz ...
Page 33: ...ELECTROVAP RTH HC 33 RTH HC 40 50 Up V 3x380 690V 50 60Hz ...
Page 34: ...ELECTROVAP RTH HC 34 RTH HC 60 70 Up V 3x380 690V 50 60Hz ...
Page 35: ...ELECTROVAP RTH HC 35 RTH HC 80 100 Up V 3x380 690V 50 60Hz ...
Page 36: ...ELECTROVAP RTH HC 36 RTH HC 8 18 Up V 3x200 240V 50 60Hz ...
Page 37: ...ELECTROVAP RTH HC 37 RTH HC 44 Up V 3x200 240V 50 60Hz ...
Page 39: ...ELECTROVAP RTH HC 39 Case 2 Up V 3x200 240V 50 60Hz Only for Case 3 ...
Page 40: ...ELECTROVAP RTH HC 40 Case 3 Up V 3x380 690V 50 60Hz ...
Page 42: ...ELECTROVAP RTH HC 42 3 9 OPTION TRANSFORMER CONNECTION ...