ELECTROVAP® KIT MC
28
3.8.1
Option: REMOTE INFORMATION BOARD
The contact can be changed to NO or NC by
wiring according to the following diagrams
(e.g. wiring on 30 & 31 = NO contact).
Option: Voltage Transformer (TT): 2X115Vac / 2x12 Vac / S=50VA.
Primary Voltage: 230 Vac
Primary Voltage: 115 Vac
Blue
Grey
Brown
Red
Black
Purple
115 Vac
24 Vac
Yellow
Orange
TT
Main board
Ref : 500102
X18
Ref 500400
500400
X23
X20
X22
X21
NO
X22 Connector (36-37-38): Remote steam
production dry contact.
X21 Connector (33-34-35): Remote general fault
dry contact.
X20 Connector (30-31-32): Remote tank
maintenance dry contact.
X20
30 31 32
X21
33 34 35
X22
36 37 38
NF
NF
NF
NO
NO
Diam:
80mm
Transformer fuse
not supplied
Blue
Grey
Brown
Red
Black
Purple
230 Vac
24 Vac
Yellow
Orange
TT