MONITORING
This menu pages allows you to apply the needed settings to the alarms. The following submenus
are available:
•
Alarm Notification
– you can enable/disable the available notification types.
•
Alarms
– gives you full control to all alarms that could be generated.
•
GP Outputs
– from here you can assign function to the General Purpose Outputs.
Alarms
is a special parameter type with its own dialog editor. Each alarm parameter is composed
of the following sub-parameters:
•
Low threshold
– the lower alarm limit of the measured signal. If the value stays below this
limit for predefined time “low alarm” event will be generated;
•
High threshold
– the higher alarm limit of the measured signal. If the value stays above this
limit for predefined time “high alarm” event will be generated;
•
Trigger time
– waiting time before a “low alarm” or “high alarm” event is generated;
•
Release time
– waiting time before an “Idle alarm” event is generated;
• Set of notification channels – In case of alarm, maintenance staff will be immediately alerted
via
,
SNMP
or
GPO
, which allows technicians to restore the normal service as soon
as possible.