background image

 

2- INSTALLATION 

2.1-  LOCATION OF THE FURNACE 

CAUTION 

Carefully  check  your  furnace  upon  delivery  for  any 
evidence  of  damage  that  may  have  occurred  during 
shipping and handling. Any claims for damages or lost 
parts must be made with the Transport Company. 

 
Position  the  furnace  as  closely  as  possible  to  the  chimney  or  vent 
terminal,  providing  ample  clearance  to  permit  easy  accessibility  for 
cleaning  the  inside  of  the  furnace,  the  removal  of  filters,  blower, 
motors, controls and flue connections. This unit can be installed in the 
downflow or horizontal (air left or right) position. 
 
This  furnace  is  approved  for  reduced  clearances  to  combustibles. 
Therefore,  it  may  be  installed  in  an  alcove,  closet,  or  crawl  space. 
Clearances indicated on the rating plate must be respected. 
 
In the downflow position, this furnace is approved for installation on 
combustible floors only when the accessory No CFB-1 "Combustible 
Floor Base" is used. 
 
In the horizontal position (air left or right), this furnace is approved for 
installation on combustible floors only when the accessory No. HFB-
1 "Horizontal Floor Base" is used. It can also be suspending using an 
angle iron frame with treaded rod hangers. 
 
However, do not install furnace directly on carpet or other combustible 
material, which can trap air under the floor. 
 
The furnace must be installed level for safe and quiet operation. 
 

CAUTION 

Do 

NOT

 operate the furnace in a corrosive atmosphere 

containing  chlorine,  fluorine  or  any  other  damaging 
chemicals. Refer to section 2.3.2. 

 

2.2-  VENTING 

2.2.1-  General 

 

The furnaces can be vented in several ways: 
 

Chimney Vented 

 
Using  the  Beckett  AFG  or  Riello  40-F  burner,  the  furnaces  can  be 
chimney  vented  with  or  without  a  barometric  damper.  The  unit  will 
operate at a 

negative

 over fire draft and flue draft. 

 

 

WARNING 

 

Poisonous  carbon  monoxide  gas,  fire  and 
explosion hazard. 

 

Read and follow all instructions in this section. 

 

Failure  to  properly  vent  this  furnace  can  cause 
bodily injury or death, property damage. 

 
 

Side-wall Vented 

 
Using the Beckett AFII  or  Riello  40-BF  burner  with  the  integral  pre- 
and  post-purge  controls,  the  system  can  be  side-wall  vented  for 

maximum  efficiency  and  without  the  use  of  a  side-wall  power  vent. 
The unit will operate at a 

positive

 over fire draft and flue draft. 

 

WARNING 

 

Poisonous carbon monoxide gas hazard. 

 

Never  vent  this  furnace  together  with  another 
combustion appliance when side-wall venting. 

 

To  do  so  may  result  in  asphyxiation  and  death  to 
the occupants 

 

2.2.2-  Chimney installations 

 
When set up for chimney venting, this furnace is certified for use with 
an L-vent, A-vent, tile-lined and metal-liner-tile lined chimney, and can 
be vented both with and without a barometric draft damper. However, 
this furnace is not approved for use without a barometric damper if it 
is  to  be  vented  together  with  another  oil-fired  appliance  such  as  a 
water heater. 
 

With barometric damper 

 
This  furnace  may  be  vented  into  a  chimney  of  suitable  size  and 
adequate chimney base temperature, as specified in the Installation 
Code. When a barometric damper is used, the basement air entering 
the damper reduces the possibility of vent condensation. The relevant 
excerpt from the code is found in this section and can be used as a 
guide  where  local  or  national  codes  do  not  exist.  One  option,  to 
increase  the  chimney  base  temperature,  is  to  use  vent  connection 
insulation. 
 

Without barometric damper 

 
Due to the lack of dilution air that would ordinarily be drawn into the 
barometric damper, the dew point of the flue gases is raised. To offset 
the increased tendency for vent condensation, the chimney must be 
lined.  The  liner  must  be  insulated  according  to  the  insulating 
procedure recommended by the manufacturer of the liner. Also, the 
vent connector should be as short as possible and either be of double 
wall  construction  or  of  single  wall  construction  with  25.4 mm  (1")  of 
insulation. 
 

WARNING 

 

Poisonous carbon monoxide gas hazard. 
 
Never  install  a  hand  operated  damper  in  the  vent 
pipe.  However,  any  Underwriters  Laboratories 
listed  electrically  operated  automatic  type  vent 
damper  may  be  installed  if  desired.  Be  sure  to 
follow  instructions  provided  with  vent  damper. 
Read and follow all instructions in this section. 
 
Failure  to  properly  vent  this  furnace  or  other 
appliances  can  result  in  personal  injury  and/or 
death, property damage.

 

 

CAUTION 

When  the  furnace  (chimney  installation)  is  vented 
together  with  other  combustion  appliances  such  as  a 
water  heater,  the  allowable  venting  materials  (L-Vent, 
etc.) for use with those appliances must be investigated. 

Flue pipe sizing 
 

Summary of Contents for ODH53-F

Page 1: ...MATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE...

Page 2: ...D ADJUSTMENTS 11 3 3 1 General 11 3 3 2 Restart after burner failure 11 3 3 3 Combustion chamber curing 11 3 3 4 Smoke CO2 test 11 3 3 5 Perform the supply air temperature rise test 11 3 3 6 Vent temp...

Page 3: ...failure and cause dangerous operating conditions e Visually check all oil line joints for signs of leakage f Connect furnace to a side wall terminal or chimney g The points in Part 2 Operation are vi...

Page 4: ...ossible Open faucets in appropriate areas b Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing Contact a qualified service ag...

Page 5: ...ide wall power vent The unit will operate at a positive over fire draft and flue draft WARNING Poisonous carbon monoxide gas hazard Never vent this furnace together with another combustion appliance w...

Page 6: ...C 300 F 179 C 355 F 221 C 430 F 41 140 000 1 00 0 1 m 4 0 15 m 6 107 C 225 F 149 C 300 F 185 C 365 F 221 C 430 F 51 175 000 1 25 0 1 m 4 0 15 m 6 116 C 240 F 135 C 275 F 160 C 320 F 185 C 365 F 2 3 AI...

Page 7: ...vapour barrier Comprehensive installation instructions are provided with the kit 2 4 OIL TANKS AND LINES Check your local codes for the installation of the tank and accessories A manual shut off valv...

Page 8: ...tructions supplied with the venting system 2 6 INSTALLING ACCESSORIES WARNING Electrical shock hazard Turn OFF electric power at fuse box or service panel before making any electrical connections and...

Page 9: ...g Failure to properly seal duct can result in death personal injury and or property damage WARNING Poisonous carbon monoxide gas hazard Install evaporator coil on the supply side of the furnace ductin...

Page 10: ...satisfied Also the solenoid valve remains open Thermostat is satisfied 8 Relay contacts open solenoid valve closes and the burner fan motor post purges the combustion chamber and vent for a pre set t...

Page 11: ...after fabrication It is important to clear the chamber of this residue before testing If you smoke test before curing the instrument may become damaged To cure the chamber run the unit for 3 consecut...

Page 12: ...efore a 1 smoke reading occurs 4 If the burner does not shut down before 1 smoke occurs ensure that the burner is set up according to Part 2 section 3 4 2 3 4 Perform the CO2 Smoke Test and allow for...

Page 13: ...amic chambers they are easily damaged Soot will have collected in the first sections of the heat exchangers only if the burner was started after the combustion chamber was flooded with fuel oil or if...

Page 14: ...should be replaced as required Secondary filter The 10 or less micron filter cartridges should be replaced annually 4 2 6 Air filters Air filters are the disposable type They should be replaced at lea...

Page 15: ...Service telephone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperatur...

Page 16: ...only 3 1 5 3 3 3 4 5 AFUE From CSA B212 standard and Canadian regulation 81 5 81 0 80 3 AFUE From ASHRAE 103 standard and US regulation 81 5 81 0 80 3 RIELLO BURNER SIDE WALL INSTALLATION Burner tube...

Page 17: ...17 Figure 5 Furnace Dimensions...

Page 18: ...18 Figure 6 Electrical Diagram ODH53 F...

Page 19: ...19 Figure 7 Parts List Exploded view B50030 Rev C...

Page 20: ...tion B30773 30 Washer 3 8 AA zinc F06F005 31 Hexagonal nut 3 8 16NC brass F07F024 32 Sight glass Z99F061 33 Hexagonal flange nut 3 8 16NC brass F07O001 34A 5 breech plate B30459 34B 3 breech plate B30...

Reviews: