![Dettson AMP1-IE2 Installation Instructions And Homeowner'S Manual Download Page 38](http://html1.mh-extra.com/html/dettson/amp1-ie2/amp1-ie2_installation-instructions-and-homeowners-manual_2488145038.webp)
7
The following requirements are provided for a safe
venting system:
a. Ensure that the chimney flue is clear of any dirt or
debris.
b. Ensure that the chimney is not servicing an open
fireplace.
c. Never reduce the pipe size below the outlet size of
the furnace.
d. All pipes should be supported using the proper
clamps and/or straps. These supports should be
at least every four (4) feet.
e. All horizontal runs of pipe should have at least a
1/4” per foot of upward slope.
f. All runs of pipe be as short as possible with as few
turns as possible.
g. Seams should be tightly joined and checked for
leaks.
h. The flue pipe must not extend into the chimney
but be flush with the inside wall.
i.
The chimney must extend three (3) feet above the
highest point where it passes through a roof of a
building and at least two (2) feet higher than any
portion of a building within a horizontal distance of
ten (10) feet. It shall also be extended at lest five
(5) feet above the highest connected equipment
flue collar.
j.
Check local codes for any variance.
Factory Built Chimneys:
May use listed factory built chimneys. Refer to
chimney manufacturer’s instructions for proper
installation.
2.4) Air inlet and flue outlet pipes
protections (sealed combustion
system only):
At air inlet and flue outlet pipe location, install the pipe
protections as shown on figure # 2.
FIGURE # 2
Pipe protections installation, (SCS only)
2.5) Venting instruction (Sealed
combustion system, SCS):
Refer to the SCS-4 Instruction manual.
2.6) Oil burner:
This furnace is supplied with a high pressure
atomizing retention head type burner (for use with not
heavier than grade 2 Fuel Oil). The mounting flange is
fixed to the burner air tube and no adjustment is
required for insertion length.
Oil Connections:
Complete instructions for installation of the fuel oil
piping will be found in the oil burner installation
instructions included with the furnace.
Oil line entry holes are produced in the side panels.
Two holes are provided in each location, so that a two-
pipe system may be used if desired.
A 10 micron (or less) oil filter should be used with all
oil burners, installed as close as possible to the
burner.
DNS-0640 Rev.A
Summary of Contents for AMP1-IE2
Page 20: ...FIGURE 6 1 Diagramme lectrique AMP1 IE2 LBM090 BMF 090 br leur Beckett 21 DNS 0635 R v A...
Page 21: ...FIGURE 6 2 Diagramme lectrique AMP2 IE2 LBM120 BMF 125 br leur Beckett 22 DNS 0636 R v A...
Page 22: ...FIGURE 6 3 Diagramme lectrique AMP1 IE2 LBM090 BMF 090 br leur Riello 23 DNS 0633 R v A...
Page 23: ...FIGURE 6 4 Diagramme lectrique AMP2 IE2 LBM120 BMF 125 br leur Riello 24 DNS 0634 R v A...
Page 26: ...FIGURE 6 7 Diagramme lectrique AMP1 IE2 LBM090 BMF 090 br leur B SCS 27 DNS 0643 R v A...
Page 27: ...FIGURE 6 8 Diagramme lectrique AMP2 IE2 LBM120 BMF 125 br leur B SCS DNS 0644 R v A 28...
Page 50: ...19 FIGURE 6 1 Wiring diagram AMP1 IE2 LBM090 BMF 090 Beckett burner DNS 0488 Rev B...
Page 51: ...20 FIGURE 6 2 Wiring diagram AMP2 IE2 LBM120 BMF 125 Beckett burner DNS 0489 Rev B...
Page 52: ...21 FIGURE 6 3 Wiring diagram AMP1 IE2 LBM090 BMF 090 Riello burner DNS 0405 Rev B...
Page 53: ...22 FIGURE 6 4 Wiring diagram AMP2 IE2 LBM120 BMF 125 Riello burner DNS 0406 Rev B...
Page 56: ...FIGURE 6 7 Wiring diagram AMP1 IE2 LBM090 BMF 090 B SCS burner 25 DNS 0641 Rev A...
Page 57: ...FIGURE 6 8 Wiring diagram AMP2 IE2 LBM120 BMF 125 B SCS burner 26 DNS 0642 Rev A...