14
GB
Press the Exit key to leave the Test Zone menu.
3.1.2 Point menu
In the Element or Point menu you can access the submenus Show, Enable & Disable.
3.1.2.1 Show points
Pressing OK in the View point menu allows you to check the current status of the
selected item.
With left and right arrow keys you can select the address field of the loop or loop
point selected. By pressing <+> <-> or up and down arrow keys you can increase or
decrease these fields and move from one element to another.
The field zone indicates the zone of the point selected.
The TYPE field shows the configured item type (optical, heat, sounder, etc.).
The MODE field indicates whether the element is: enabled, disabled or test.
The AV field indicates the analogue value of the item.
The TEXT field indicates the name of the point.