3.1.1.4 Disablement zone menu
This menu option allows us enabled zones to be disabled.
3.1.1.5 Test zone menu
This option menu allows selected zones to be put into test mode. This option allows
us to test the sensors without having to reset the unit. If you select this option, the
system asks whether to enable the sounders. If the answer is yes, the sounders will
be activated for a few seconds after a detector in a zone in test mode enters alarm,
after which they will be silenced automatically. If there is any delay associated with
the sounders, in test mode, the delay will be cancelled, to streamline the system test.
After 20 minutes of test mode selection, if the system detects that there has been no
detectors tested, the system will go back to the normal mode, reversing the test mode.